R 325.2434
R 325.2434 Supply ventilation systems.
Cite as Mich. Admin. Code R 325.2434
Rule 34. (1) A supply ventilation system shall be provided to ensure a flow of air
into the working environment to replace the volume of air exhausted.
(2) A mechanical air supply system shall be provided if its absence will result in
building negative pressures sufficient to cause back-drafting of vents from fuel-fired
equipment or ineffective control.
(3) Mechanical air supply volumes shall be heated to maintain a minimum air
temperature of 65 degrees Fahrenheit measured at the point of air discharge to the
space. Exceptions to this requirement are refrigerated storage rooms, special process
rooms, and similar locations where lower air temperatures are essential to the
preservation of the product or service, or, if in the opinion of the director, a lower air
temperature will not be
harmful to the health of the persons affected.