R 325.52006
R 325.52006 Direct-fired air heaters.
Cite as Mich. Admin. Code R 325.52006
Rule 6. (1) A direct-fired air heater, wherein combustion products are released
in the supply air stream, may be installed in buildings of industrial occupancy,
garages, laundries, and commercial kitchens. They shall not be installed in offices,
schools, hospitals, and places of public assembly.
(2) A direct-fired air heater shall have an inlet duct connected directly to the out-of-
doors. Room air shall not be circulated across the burner.
(3) A direct-fired air heater shall deliver air which contains not more than 10 ppm
of carbon monoxide and is free from odors of combustion products. Permissible
concentrations of other contaminants in the delivered air may be established by the
director pursuant to their permissible exposure limits and the degree of exposure to a
person.
(4) The air volume supplied to the building by a direct-fired air heater shall
not exceed 110% of the total air volume exhausted. The director may require
interlocking of a heater control system with an
exhaust ventilation system if necessary to ensure that the exhaust systems are
operating.
(5) A direct-fired air heater shall have both of the following:
(a) A pre-ignition purge of fresh air.
(b) A positive fuel supply closure in the event of fuel supply failure, ignition
failure, flame failure, power failure or interruption, or air flow reduction below 50% of
its rated capacity.