R 336.1290
R 336.1290 Permit to install exemptions; emission units with limited emissions.
Cite as Mich. Admin. Code R 336.1290
Rule 290. (1) This rule does not apply if prohibited by R 336.1278 and unless the
requirements of R 336.1278a have been met.
(2) The requirement of R 336.1201(1) to obtain a permit to install does not apply to any
of the emission units listed in subdivision (a) of this subrule, if the conditions listed in
subdivisions (b), (c), (d), and (e) of this subrule are met. Notwithstanding the definition in
R 336.1121(a), for the purpose of this rule, uncontrolled emissions are the emissions from
an emission unit based on actual operation, not taking into account any emission control
equipment. Controlled emissions are the emissions from an emission unit based on actual
operation, taking into account the control equipment.
(a) An emission unit which meets any of the following criteria:
(i) Any emission unit that emits only noncarcinogenic volatile organic compounds or
noncarcinogenic materials that are listed in R 336.1122(f) as not contributing appreciably
to the formation of ozone, if the total uncontrolled or controlled emissions of air
contaminants are not more than 1,000 or 500 pounds per month, respectively.
(ii) Any emission unit for which the CO2 equivalent emissions are not more than 6,250
tons per months, the uncontrolled or controlled emissions of all other air contaminants are
not more than 1,000 or 500 pounds per month, respectively, and all of the following criteria
are met:
(A) For toxic air contaminants, excluding noncarcinogenic volatile organic compounds
and noncarcinogenic materials that are listed in R 336.1122(f) as not contributing
appreciably to the formation of ozone, with initial threshold screening levels greater than
or equal to 0.04 micrograms per cubic meter and less than 2.0 micrograms per cubic meter,
the total uncontrolled or controlled emissions shall not exceed 20 or 10 pounds per month,
respectively.
(B) For toxic air contaminants with initial risk screening levels greater than or equal to
0.04 micrograms per cubic meter, the total uncontrolled or controlled emissions shall not
exceed 20 or 10 pounds per month, respectively.
(C) The emission unit shall not emit any toxic air contaminants, excluding
noncarcinogenic volatile organic compounds and noncarcinogenic materials that are listed
in R 336.1122(f) as not contributing appreciably to the formation of ozone, with an initial
threshold screening level or initial risk screening level less than 0.04 micrograms per cubic
meter.
(D) For total mercury, the uncontrolled or controlled emissions shall not exceed 0.01
pounds per month.
(E) For lead, the uncontrolled or controlled emissions shall not exceed 16.7 pounds per
month.
(iii) Any emission unit that emits only particulate air contaminants without initial risk
screening levels and other air contaminants that are exempted under paragraph (i) or (ii) of
this subdivision if all of the following provisions are met:
(A) The particulate emissions are controlled by an appropriately designed and operated
fabric filter collector or an equivalent control system that is designed to control particulate
matter to a concentration of less than or equal to 0.01 pounds of particulate per 1,000
pounds of exhaust gases and that do not have an exhaust gas flow rate more than 30,000
actual cubic feet per minute.
(B) The visible emissions from the emission unit are not more than 5% opacity in
accordance with the methods contained in R 336.1303.
(C) The initial threshold screening level for each particulate toxic air contaminant,
excluding nuisance particulate, is more than 2.0 micrograms per cubic meter.
(b) The following requirements apply to emission units utilizing control equipment:
(i) An air cleaning device for volatile organic compounds shall be installed, maintained,
and operated in accordance with the manufacturer’s specifications. Examples include the
following:
(A) Oxidizers and condensers equipped with a continuously displayed temperature
indication device.
(B) Wet scrubbers equipped with a liquid flow rate monitor.
(C) Dual stage carbon absorption where the first canister is monitored for breakthrough
and replaced if breakthrough is detected.
(ii) An air cleaning device for particulate matter shall be installed, maintained, and
operated in accordance with the manufacturer’s specifications or the owner or operator
shall develop a plan that provides to the extent practicable for the maintenance and
operation of the equipment in the manner consistent with good air pollution control
practices for minimizing emissions. It shall also be equipped to monitor appropriate
indicators of performance, for example, static pressure drop, water pressure, and water flow
rate.
(c) A description of the emission unit is maintained throughout the life of the unit.
(d) Records of material use and calculations identifying the quality, nature, and quantity
of the air contaminant emissions are maintained in sufficient detail to demonstrate that the
emissions meet the emission limits outlined in this rule. Volatile organic compound
emissions shall be calculated using mass balance, generally accepted engineering
calculations, or another method acceptable to the department.
(e) The records are maintained on file for the most recent 2-year period and are made
available to the department upon request.