11 CSR 40-5.065
Missouri Minimum Safety Codes for Existing Elevator Equipment
PURPOSE: The purpose of this rule is to take
exceptions to the referenced Codes or provide
alternatives. It has been noted that some
areas of the referenced Codes are too restrictive or may not be feasible to implement, or
may be unreasonable for certain types of
installations.
(1) In a political subdivision or municipality
that had adopted an edition of ASME A17.1
code, elevator equipment shall conform to the
code requirements adopted and enforced at
the time the elevator equipment was installed.
The following standards apply to all existing
elevator equipment installed prior to July 1,
1999 as provided in 11 CSR 40-5.060. Any
installation which is in compliance with the
latest ASME A17.1 version adopted and
amended by the Elevator Safety Board, unless
as exempted by 701.359, RSMo shall be considered to be in compliance with 11 CSR 405.065.
(A) Hoistways.
1. Each passenger elevator hoistway
landing shall be protected with a door or
gate. The door or gate shall be of solid construction and shall guard the entire entrance.
2. All automatic passenger elevators
with power doors shall have non-vision panels on hoistway doors.
3. Each hoistway landing in any elevator
hoistway shall be continuously provided with
a properly working door or gate.
4. Where freight elevator hoistway doors
or gates are of open or lattice construction
they shall be at least six feet (6') high and
shall come within two inches (2") of the floor
when closed. Gates shall be constructed as to
reject a ball two inches (2") in diameter. They
shall withstand a force of two hundred fifty
(250) pounds pressure applied in the center of
the gate without breaking or forcing it out of
its guides.
5.
Manually
operated
bi-parting
entrances of elevators which can be operated
from the landings shall be provided with pull
straps on the inside and outside of the upper
panel where the lower edge of the upper panel
is more than six feet six inches (6'6") above
the landing when the panel is in the fully
opened position.
6. Each hoistway door or gate shall be
provided with interlocks designed to prevent
the car from moving unless the doors or gates
are closed. Where doors or gates do not lock
when closed they shall lock when the elevator is not more than twelve inches (12") away
from the floor. Passenger elevator hoistway
doors shall be closed and locked before the
car leaves the floor.
7. All hoistway-door interlocks shall be
of the hoistway unit type.
8. Automatic fire doors shall not lock
any landing opening in the hoistway enclosure from the hoistway side nor lock any exit
leading from any hoistway landing to the outside of the building.
9. Emergency keys for hoistway doors
and service keys shall be kept readily accessible to authorized persons.
10. Access means shall be provided at
one (1) upper landing to permit access to the
top of the car, and at the lowest landing if this
landing is the normal point of access to the
pit.
11. Each hoistway door or gate, which is
counterweighted, shall have its weights
enclosed in a box-type guide or run in metal
guides. The bottom of the guides or boxes
shall be so constructed as to retain the counterweight if the counterweight suspension
means breaks.
12. Hoistways containing freight elevators shall be fully enclosed. Enclosures shall
be unperforated to a height of six feet (6')
above each floor or landing and above the
treads of adjacent stairways. Unperforated
enclosures shall be so supported and braced
as to deflect not over one inch (1") when subjected to a force of one hundred (100) pounds
applied horizontally to any point. Open work
enclosure may be used above the six-foot (6')
level and shall reject a ball two inches (2") in
diameter.
13. Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full
height.
14. Except where vertical opening biparting doors are provided, all elevators provided with automatic leveling, inching, or
teasing devices and where the landing sills
project within the hoistway, shall be equipped
with a bevel on the underside of the landing
sill. Bevels shall be constructed of smooth
concrete or not less than sixteen (16) gauge
metal securely fastened to the hoistway
entrance. Bevels shall extend the full depth of
the leveling zone plus three inches (3").
15. Every hoistway window opening
seven (7) stories or less on an outside wall
above a thoroughfare and every such window
three (3) stories or less above a roof of the
building or of an adjacent building shall be
guarded to prevent entrance by fire or emergency rescue persons. Each such window
shall be marked “hoistway” in a readily visible manner.
16. All electrical wiring in the hoistway
shall be enclosed in metal conduit, flexible
conduit or metal raceway or be in compliance
with NFPA 70, National Electric Code.
17. No pipes conveying liquids, gases,
or vapors shall be located in a hoistway.
Exception: branch lines for sprinkler system
and low pressure steam lines for heating.
(B) Car Enclosure: Passenger.
1. Each passenger car shall be fully
enclosed except on the sides used for entrance
and exit. The enclosure shall be of solid construction. Grill work at the top of the sides
shall not be more than eight inches (8") high.
If the car is provided with a solid door and
there is no grill work in the enclosure, adequate means of ventilation shall be provided.
2. Each passenger car enclosure shall
have a top constructed of solid material. The
top shall be capable of sustaining a load of
three hundred (300) pounds on any area of
two feet (2') on a side and one hundred (100)
pounds applied at any point. Simultaneous
application of these loads is not required.
3. Passenger car enclosure tops shall
have an emergency exit with cover. Opening
size shall be as set forth in ASME A17.1,
rule 204.1E, 1955 edition. Exception:
Hydraulic elevators provided with a manual
lowering valve.
4. Each passenger car shall have a door
or gate at each entrance. Doors or gates shall
be of the horizontally sliding type. Doors
shall be of solid construction. Gates shall be
of the collapsible type. Gates and doors shall
conform to ASME A17.1, rule 204.4, 1955
edition.
5. Each passenger car door or gate shall
have an electric contact to prevent the car
from running with doors or gates open.
Exceptions:
A. By a car-leveling or truck-zoning
device;
B. By a combination hoistway access
switch and operating device; or
C. When a hoistway access switch is
operated.
6. All automatic passenger elevators
with power doors shall have reopening
devices on the doors, designed to reopen
doors in the event the doors should become
obstructed.
7. Where a car door or gate of an automatic or continuous-pressure operation passenger elevator is closed by power, or is of
the automatically released self-closing type,
and faces a manually operated or self-closing
hoistway door, the closing of the car door or
gate shall not be initiated unless the hoistway
door is in the closed position; and the closing
mechanism shall be so designed necessary to
prevent closing of a horizontally sliding car
door or gate from rest shall be not more than
thirty (30) pounds. Exception: Where a car
door or gate is closed by power through continuous pressure of a door-closing switch, or
of the car operating device, and where the
release of the closing switch or operating
device will cause the car door or gate to stop
or to stop and reopen.
8. Each passenger car shall have lighting
inside the enclosure of not less than five (5)
foot-candles. Bulbs and tubes shall be guarded to prevent breakage.
9. Each passenger elevator shall have a
capacity plate prominently displayed in its
enclosure. The capacity plate shall list its
capacity in pounds.
10. All passenger elevator car floors
shall be maintained so that persons are not
exposed to the hazards of tripping or falling.
11. All automatic passenger elevators
shall be provided with an alarm bell capable
of being activated from inside the car and
audible outside the hoistway. If the elevator is
not equipped with a bell, a two- (2-) way conversation device to the elevator and a ready
accessible point outside the hoistway may be
acceptable.
12. All automatic passenger elevators
shall have their door open zones adjusted to
where the door shall not open unless the car
has stopped within six inches (6") of floor
level.
(C) Car Enclosure: Freight.
1. Each freight elevator car shall have a
solid enclosure of at least six feet (6') in
height. The space between the solid section
and the car top shall be covered solid or with
perforated or lattice-type work. The perforated or lattice work shall reject a ball one and
one-half inches (1 1/2") in diameter. The portion of open-type enclosure, which passes the
counterweights, shall be of solid construction
the entire width of the counterweights plus
six inches (6") on either side. The enclosure
top shall be provided with an emergency exit.
Exception: Hydraulic elevators provided with
a manual-lowering valve.
2. Each freight car enclosure shall have
doors or gates at each entrance and shall be
not less than six feet (6') high. Each door or
gate shall be constructed in accordance with
ASME A17.1, rule 204.4, 1955 edition.
3. Each car door or gate on a freight elevator shall have electric contacts to prevent
the car from running with doors or gates
open. Exceptions:
A. By a car-leveling or truck-zoning
device;
B. By a combination hoistway access
switch and operating device; or
C. When a hoistway access switch is
operated.
4. Each freight elevator car enclosure
shall be provided with a top. The top may be
solid or open-work construction and shall be
of metal. The open work shall reject a ball
two inches (2") in diameter. Car tops shall
be constructed to sustain a load of two hundred (200) pounds applied at any point on the
car top. The top shall not have hinged or
folding panels other than the emergency exit
cover.
5. Each freight car enclosure shall have
lighting not less than two and one-half (2 1/2)
foot-candles. Bulbs or tubes shall be guarded
to prevent breakage.
6. Each freight car enclosure shall have
capacity plate, loading class plates, and a
“No Passengers” sign conspicuously posted.
Letters shall not be less than one-half inch
(1/2") high.
7. Freight elevators shall not be loaded
to exceed the rated load as stated on their
capacity plates.
8. Each freight elevator car floor shall
be maintained so that personnel will not readily slip or trip. The floor shall be maintained
so that it will hold its rated load without
breaking through at any place in the car.
9. Freight elevators shall not be permitted to carry passengers other than persons to
load and unload material and the operator.
Permission may be granted to allow the carrying of employees on freight elevators.
Application shall be submitted and may be
approved by the authorized representative
after which the installation shall be tested as
determined by the Department of Public
Safety.
(D) Brakes.
1. Each electric elevator shall be provided with an electric brake.
2. Each brake shall be of the friction
type applied by a spring or springs or gravity
and released electrically. The brake shall be
capable of holding the car at rest with its
rated load.
(E) Machines.
1. Friction gearing or clutch mechanisms shall not be used for connecting the
drum or sheaves to the main driving mechanism.
2. Set screw fastenings shall not be used
on power elevators in lieu of keys or pins on
connections subject to torque or tension.
3. Portable power-chain or cable hoist
machines shall not be used to raise or lower
an elevator car.
4. No belt or chain driven power
machine shall be used for any elevator unless
the machine is provided with a broken belt or
broken chain safety switch of the electrical
non-automatic
reset
type.
Exception:
Hydraulic machines.
(F) Electrical Switches.
1. All electric elevators shall have a
labeled emergency stop switch. The switch
shall be located on or adjacent to the operating panel.
2. All electric elevators shall have upper
and lower final limit switches. Open-type
switches shall not be accepted. Drum-type
machines shall have final limit switches
mounted on the machine and hoistway final
limit switches.
3. All operating devices of car switch
operations shall automatically return to the
stop position and latch there when released.
4. Tiller-cable operations shall not be
used unless all direction switches on controllers are mechanically operated. Contacts
on direction switches shall be broken when
the cable is at the centered position.
5. No elevator shall be provided with a
switch or device which makes more than one
(1) door or gate switch inoperative at any one
time. Exception: Fire fighter service switches.
6. No person at any time shall make any
required safety device or electrical protective
device inoperative, except where necessary
during tests, inspections or maintenance.
Such devices shall be restored to their normal
operating conditions as soon as all tests,
inspections and maintenance has been completed. The facility shall not be left unattended while any of these devices are inoperative.
7. Each winding drum machine shall be
provided with an electrical switch which shall
disconnect power to the hoisting motor and
brake when cables are slackened.
8. Any persons entering an elevator pit
for any reason shall have the power to the elevator removed at the main line disconnect
switch. The disconnect switch shall be red
tagged to prevent the power from being
placed back on the elevator controls. Exception: Elevators provided with a pit stop
switch.
9. A fused disconnect means for all elevators shall be provided. Disconnect switch
shall be located in the machine room and be
readily accessible from the machine.
(G) Maintenance, Repair and Alterations.
1. All maintenance, repair and replacement shall comply with the applicable standard established by 11 CSR 40-5.050(1)
ASME A17.1, section 8.6 Safety Code for
Elevators and Escalators.
2. All alterations shall comply with the
applicable standards established by 11 CSR
40-5.050(1) ASME A17.1, section 8.7 Safety Code for Elevators and Escalators.
3. All maintenance, repair and alterations to platform lifts and stairway chair lifts
shall comply with the applicable standards
established by 11 CSR 40-5.050(1) ASME
A18.1, Safety Standard for Platform Lifts and
Stairway Chair Lifts.
(H) Machine Rooms.
1. All means of access to elevator
machine rooms shall be of a permanent
nature and shall be constructed and maintained in a clear and unobstructed manner.
2. The elevator machine and control
equipment shall be located in a separate room
or separated space designed as an elevator
machine room or space and shall be accessible only to authorized personnel. Existing
machines and equipment essential to the
operation and purpose of the building are permitted but must not interfere with the safety
and work area for maintaining elevator equipment. Pipes conveying liquid, gas, or vapor
that cross overhead of elevator equipment or
come in close proximity of the equipment
shall be guarded or guttered. Where other
existing machines and equipment essential to
the operation and purpose of the building are
located in the machine room or space, the
elevator related equipment and machines
shall be separated by a substantial grill constructed of noncombustible material not less
than six feet (6') high and the grill shall be of
a design that will reject a ball two inches (2")
in diameter. All rooms or enclosures shall
have a self-closing and self-locking door and
shall be operable from the interior space
without use of a key. After the effective date
of this rule, no equipment shall be added to
the machine room or space that is not used in
connection with the operation of the elevator.
3. All elevator machine rooms shall be
provided with a floor. The floor shall cover
the entire area of the machine room and
hoistway.
4. Machine room floors shall be kept
clean and free of grease and oil. Articles or
materials not necessary for the maintenance
or operation of the elevator shall not be stored
therein. Flammable liquids having a flash
point of less than one hundred ten degrees
Fahrenheit (110°F) shall not be stored in the
machine room.
5. Lighting in the machine room shall be
not less than ten (10) foot-candles at floor
level.
6. Where there is more than one
machine in a room, each machine shall have
a different number conspicuously marked on
it. The controller, disconnect switch, and
relay panels for each machine shall be conspicuously numbered to correspond to the
machine it controls.
7. All electrical equipment in the
machine room shall be grounded which shall
conform to ASME A17.1, 1996 edition and
NFPA, 70, National Electric Code.
8. All electrical wiring in the machine
room shall be enclosed in metal conduit, flexible conduit or metal raceways or be in compliance with NFPA 70, National Electric
Code.
9. Each elevator having polyphase alternating current power supply shall be provided with means to prevent the starting of the
elevator motor if:
A. The phase rotation is in the wrong
direction; or
B. There is a failure of any phase.
This protection shall be considered provided
in the case generator-field control having
alternating current motor-generator driving
motors, provided a reversal of phase will not
cause the elevator driving-machine motor to
operate in the wrong direction. Controllers
whose switches are operated by polyphase
torque motors provide inherent protection
against phase reversal or failure.
(I) Pits.
1. All pits shall be kept dry, clean, and
free of equipment or material not relating to
the operation of the elevator. Exception:
Sump pumps.
2. Buffers (spring or oil type) under cars
and counterweights shall be permanently fastened to the floor or their supporting beams.
3. All elevators shall have counterweight
guards. Guards shall be of unperforated metal
of at least the strength of or braced to the
equivalent strength of number fourteen (14)
gauge sheet steel. Guards shall extend from
a point not more than twelve inches (12")
above the pit floor to a point not less than
seven feet (7') above the pit floor. Where
guards are not feasible, warning chains shall
be installed on the bottom of the counterweights and shall extend no less than five feet
(5') below counterweight. Chains shall be of
a number ten (10) U.S. gauge wire or of
equal size. Exception: When compensating
chains or ropes are used, a counterweight
guard is not required.
4. Buffers shall be installed where elevator pits are not provided with buffers and
where the pit depth will permit, buffers shall
comply with ASME A17.1, 1955 edition,
section 201.
5. Where the depth of any pit is four feet
(4') or more it shall have a ladder permanently installed. The ladder shall extend not
less than thirty inches (30") above the sill of
the access door, or hand grips shall be provided to the same height. Ladder shall be of
noncombustible material.
6. A permanent lighting fixture shall be
provided in all pits to provide an illumination
of not less than five (5) foot-candles at the pit
floor. The fixture switch shall be provided
and accessible from the pit access door.
7. An enclosed stop switch meeting the
requirements of ASME A17.1, 1995 edition,
rule 210.2(e) shall be installed in the pit of all
power elevators and be accessible from the pit
access door.
8. Pit sump holes, with or without
pumps, and well holes that are accessible,
shall be covered flush with the pit floor. The
covering shall consist of a noncombustible
material.
(J) Counterweights.
1. Broken or cracked sections of counterweights shall be replaced.
2. Counterweight hanger rods, tie rods
or both shall firmly support and secure the
counterweight sections in place.
3. Wire ropes extending through counterweights from one (1) stack to another shall
be guarded by metal sleeves attached to the
wire ropes. Guards shall be of a suitable
design to prevent accidental crushing or
deforming for the ropes and rope sockets.
Stacks shall not be spaced less than eight
inches (8") apart.
(K) Car Platforms and Car Slings.
1. All platforms shall be soundly constructed without cracks or breaks in stringers
or frames. All floors shall be free of holes.
2. All car slings shall be soundly constructed and free of cracks or breaks.
3. Where cable sheaves are used on the
crosshead, they shall be firmly attached and
free of cracks or breaks.
4. All elevators shall have data plates
attached to the crosshead.
5. All elevators with automatic leveling,
inching or teasing devices shall have a platform guard or an apron. All other elevators
shall have warning chains hung within two
inches (2") of the edge of the platform on the
entrance sides. Chains shall be of number ten
(10) U.S. gauge wire or of equal size. Chains
shall extend not less than five feet (5') below
the platform and shall not be spaced more
than four inches (4") apart.
6. All car slings shall have guide shoes
at the top and bottom of the sling. Shoes that
are worn to a degree which affect the safe
operation of the car shall be repaired or
replaced.
(L) Wire Ropes—Hoisting, Governor, and
Tiller.
1. All hoisting and governor ropes,
when replaced, shall have rope tags. The tags
shall provide the following information:
A. The diameter in inches;
B. The manufacturer’s rated breaking
strength;
C. The grade of material used;
D. The month and year ropes were
installed;
E. Whether preformed or non-preformed;
F. Construction classification;
G. Name of person or firm who
installed ropes; and
H. Name of manufacturer of ropes.
2. Wire ropes on drum-type machines
shall be resocketed in compliance with
ASME A17.1, 1996 edition, rule 1206.3.
3. Suspension ropes on drum-type
machines shall have not less than one (1) turn
of the rope on the drum when the car is resting on the fully compressed buffers.
4. Winding drum machines shall not be
used unless they are provided with not less
than two (2) hoisting ropes. Each counterweight stack shall be provided with not less
than two (2) ropes.
5. Tiller cables on cable-operated elevators shall be kept free of breaks.
6. On tiller-cable operations, the cable
shall pass through a guiding or stopping
device mounted on the car. The cable shall
be provided with adjustable stop balls and be
provided with means to lock and hold the car
at a floor. Stop balls at top and bottom shall
be adjusted to automatically stop the car.
The tiller cable shall be completely enclosed
in the hoistway.
7. All hoisting or counterweight ropes
located outside of the hoistway that are
exposed shall be covered with a box-type
guard. The guard shall be not less than six
feet (6') high from floor level.
8. Hoisting, governor, and tiller ropes
shall not be lengthened or repaired by splicing.
9. Suspension means of chains other
than a roller chain type shall not be allowed.
Any elevator suspended by a roller chain type
shall not be used for the carrying of passengers. Exception: Elevators for the disabled.
10. Hoisting ropes for power elevators
shall not be less than three-eighths inch
(3/8") in diameter.
11. Hoisting rope fastening means shall
be of the socket, babbitting, or wedge type.
Clamps shall not be used.
12. Rope (cable) replacement. Hoisting,
governor, and tiller ropes shall be replaced
when the Inspection of Elevators, Escalators
and Moving Walks, ASME A17.2, 1996 edition Inspectors’ Manual, Division 103, Item
103.4 dictates they shall be changed.
(M) Car Safeties and Speed Governors.
1. Each elevator suspended by ropes
shall be provided with mechanically applied
car safeties which shall be capable of stopping and sustaining its rated load.
2. Broken rope or slack rope safeties
may be allowed if the car speed is not in
excess of fifty feet per minute (50 fpm).
3. Elevators which are provided solely
with broken rope or slack rope safeties shall
not be used for passenger service. Exception:
Elevators for the disabled.
4. All safeties shall be adjusted so that
clearances from the rail shall be in accordance with ASME A17.1, 1955 edition rule
1001.2.
5. All slack cable safeties shall be provided with an electrical switch which disconnects power to the elevator machine and
brake when setting of the safeties occurs.
6. All safeties operated by a speed governor shall be provided with a speed switch
operated by the governor when used with
type B or C car safeties on elevators having a
rated speed exceeding one hundred fifty (150)
fpm. A switch shall be provided on the speed
governor when used with a counterweight
safety for any car speed.
7. Speed governors shall have their
means of speed adjustment sealed.
8. For hoistways not extending to the
lowest floor and where space below the hoistway is used for a passageway or is occupied
by persons, or if unoccupied but not secured
against unauthorized access, the counterweights of the elevator shall be provided with
safeties. Safeties shall be tripped by a speed
governor if the car speed is in excess of one
hundred fifty (150) fpm. Speed governors
shall be set to trip above the car governor
tripping speed but not more than ten percent
(10%) greater.
(N) Guide Rails.
1. All guide rails and brackets whether
of wood or steel shall be firmly and securely
anchored or bolted in place. Where T rail is
used all fish-plate bolts shall be tight. This
shall comply with ASME A17.1, 1955 edition, section 200.
2. Where guide rails which are worn to
such a point that proper clearance of safety
jaws cannot be maintained, the worn sections
shall be replaced to achieve clearances as
specified in ASME A17.1, 1996 edition, rule
1001.2.
(O) Existing Hydraulic Elevators.
1. Cylinders of hydraulic-elevator
machines shall be provided with a means for
releasing air or other gas.
2. Each pump or group of pumps shall
be equipped with a relief valve conforming to
the following requirements:
A. Type and location. The relief valve
shall be located between the pump and the
check valve and shall be of such a type and so
installed in the bypass connection that the
valve cannot be shut off from the hydraulic
system;
B. Setting. The relief valve shall be
preset to open at a pressure not greater than
that necessary to maintain one hundred twenty-five percent (125%) of working pressure;
C. Size. The size of the relief valve
and bypass shall be sufficient to pass the
maximum rated capacity of the pump without
raising the pressure more than twenty percent
(20%) above that at which the valve opens.
Two (2) or more relief valves may be used to
obtain the required capacity; and
D. Sealing. Relief valves having
exposed pressure adjustments if used, shall
have their means of adjustment sealed after
being set to the correct pressure. Exception:
No relief valve is required for centrifugal
pumps driven by induction motors, provided
the shut-off, or maximum pressure which the
pump can develop, is not greater than one
hundred and thirty-five percent (135%) of the
working pressure at the pump.
3. Storage and discharge tanks shall be
covered and suitably vented to the atmosphere.
4. All repair and alterations of hydraulic
elevators shall comply with ASME A17.1,
1996 edition, section 1201 with supplements
thereto.
(P) Existing Sidewalk Elevators.
1. Hoistways shall be permanently
enclosed. The enclosures shall conform to
ASME A17.1, 1955 edition rule 401.1.
2. All interior landings shall have a door
or gate which shall be provided with an interlock.
3. Doors opening in sidewalks or other
areas exterior to the building shall be of the
hinged type. Doors or covers shall be
designed to hold a static load of three hundred pounds per square foot (300 ppsf).
Doors shall always be closed unless elevator
is at the landing.
4. Stops shall be provided to prevent the
cover in the opening of the sidewalk from
opening more than ninety degrees (90°) from
its closed position.
5. Covers in sidewalk shall be designed
to close when the car descends from the top
landing.
6. Recesses or guides which will securely hold the cover in place on the car stanchions shall be provided on the underside of
the cover.
7. All electrical wiring shall be enclosed
in metal conduit, flexible conduit, or metal
raceways. If hoistway opens in the sidewalk,
the wiring shall be weatherproof.
8. Operating devices and control equipment shall comply with ASME A17.1, 1955
edition, rule 402.4.
9. All electric sidewalk elevators shall
have upper and lower final limit switches.
Open-type switches shall not be allowed.
10. Cars shall have enclosures which
shall be not less than six feet (6') in height
provided the stanchions and bow iron are of
sufficient height. The enclosure shall be provided with electric contacts to prevent the car
from running with doors or gates open.
11. Cars shall have safeties. Where the
speed of the elevator does not exceed fifty
(50) fpm, car safeties which operate as a
result of breaking or slackening of the hoisting ropes may be used. Such safeties may be
of the inertia type or approved type without
governors. Governors shall not be required
when car speed does not exceed fifty (50)
fpm.
12. Car enclosures and car gates shall
not be required for hand-powered sidewalk
elevators.
13. All repair and alterations shall comply with ASME A17.1, 1955 edition, section
1200.
(Q) Existing Hand Elevators.
1. Hand-powered elevators shall have
hoistway doors. Doors shall be of the selfclosing and self-locking type.
2. Hoistway doors shall have signs
attached to them indicating elevator hoistway.
Sign shall be as follows in not less than twoinch (2") letters: DANGER ELEVATOR—
KEEP CLOSED.
3. All hand-powered elevators shall be
provided with safeties or slack cable devices.
Safeties do not have to be operated by a speed
governor unless the speed is in the excess of
fifty (50) fpm.
4. Hand-powered elevators shall have a
car enclosure which shall be constructed of
metal or sound seasoned wood. The enclosure shall cover all sides which are not used
for entrance or exit. The enclosure shall be
secured to the car platform or frame in such
a manner that it cannot work loose or become
displaced in ordinary service.
5. Each hand-powered elevator shall be
provided with a brake which shall be capable
of stopping and sustaining the car whether
loaded or unloaded.
6. Hand-powered elevators shall not be
converted or changed to electric powered
unless the complete facility is brought into
conformity with ASME A17.1, 1996 edition.
7. Repair or replacement of worn or
broken parts shall be in compliance with
ASME A17.1, 1996 edition, rule 1202.2.
(R) Power Operated Special Purpose Elevators.
1. Elevators complying with the following requirements may be installed in any
structure where the elevator is not accessible
to the general public, is used exclusively for
designated operating and maintenance
employees only, and where transportation of
one (1) or two (2) persons is required to
attend machinery or equipment frequently.
2. The inside platform area of the car
shall not exceed nine (9) square feet. The
rated speed shall not exceed one hundred
(100) fpm. The rated load shall not exceed
six hundred fifty (650) pounds.
3. Hoistways shall be enclosed to their
full width, to a height of not less than seven
feet (7') with solid or perforated noncombustible material braced to deflect not more
than one inch (1") when subjected to a force
of one hundred (100) pounds applied horizontally at any point. Open work enclosures
shall be at least number thirteen (13) steel
wire gauge or expanded metal at least number thirteen (13) U.S. gauge and shall reject
a ball two inches (2") in diameter. Where
counterweights pass, landing and stairway
side shall be of solid construction.
4. Wiring shall comply with the requirements of ASME A17.1, 1978 edition and
NFPA 70.
5. Counterweights shall comply with the
requirements of ASME A17.1, 1978 edition,
Part XV.
6. Hoistway doors shall comply with
rules ASME A17.1, 1978 edition, Part XV.
7. Cars shall be solidly constructed in
accordance with ASME A17.1, 1978 edition,
Part XV.
8. Car enclosure.
A. Except at the entrance, the car
shall be enclosed on all sides and the top.
The enclosure at the sides shall be solid or
open work. All open work shall reject a ball
one inch (1") in diameter. The enclosure
shall be constructed of sufficient strength that
it will not deflect more than one inch (1") at
any one (1) point.
B. There shall be an electric light to
illuminate the car or hoistway with the switch
placed on or near the operating panel.
C. There shall be no glass used in the
elevator car except for the car light.
9. A car door shall be provided at each
car entrance. Door or gate shall guard the
complete entrance. The door or gate shall be
at least seven feet (7') high, of metal construction with solid or open construction to
reject a ball one inch (1") in diameter. A contact switch shall be provided to prevent the
operation of the elevator with doors or gates
open. The door or gate shall be provided with
interlocks.
10. Guide rails shall comply with
ASME A17.1, 1978 edition, Part XV.
11. The means and methods of suspension shall comply with ASME A17.1, 1978
edition, Part XV.
12. Electrical switches shall comply
with ASME A17.1, 1978 edition, Part XV.
13. Brakes shall comply with ASME
A17.1, 1978 edition Part XV.
14. Emergency signal or communication
shall comply with ASME A17.1, 1978 edition, Part XV.
(S) Fire Service.
1. Elevators with fire service features
shall comply with the edition of ASME
A17.1 that the elevator was constructed to
meet.
(T) Existing Dumbwaiters, Escalators, and
Moving Walks.
1. Dumbwaiters.
All
dumbwaiters
whether electric or hand powered shall conform to ASME A17.1, 1971 edition, section
700. Exceptions: Required rules for hoistway
construction as set forth in ASME A17.1,
1971 edition shall not apply to existing installations.
2. Escalators.
A. Each escalator shall be provided
with an electrically released mechanically
applied brake capable of stopping the up and
down traveling escalator with any load up to
and including the rated load. The brake shall
be located either on the driving machine or
on the main drive shaft.
B. Starting switches shall be of the
key-operated type. Starting switches shall be
located on or near the escalator.
C. Emergency stop buttons or other
type manually operated switches having red
buttons or handles shall be accessibly located
at or near the bottom and top landings. The
buttons or levers shall be protected to prevent
accidental operation.
D. A broken step-chain device shall
be provided on each escalator that will cause
interruption of power to the driving machine
if a step chain breaks or if excessive sag
occurs in either step chain.
E. Each escalator shall have comb
plates at top and bottom landings of the escalator. Comb plate teeth shall be meshed with
and set into slots in the tread surface of the
steps so that the points of the teeth are always
below the upper surface of the treads.
F. Each escalator balustrade or molding on the balustrade shall have a smooth surface. Screw heads shall set flush with the surface or be of the oval head type without any
burrs or rough places on their surface.
G. The clearance on either side of the
steps between the step tread and the adjacent
skirt panel shall be not more than three-sixteenths inch (3/16").
H. Step treads shall be illuminated
throughout their run. The light intensity shall
be not less than two (2) foot-candles.
I. An enclosed fused disconnect
switch or circuit breaker arranged to disconnect the power supply to the escalator shall be
in each machine room or wherever the controller is located.
J. A stop switch shall be provided in
each machinery space where means of access
to the space is provided. The switch when
opened shall cause electric power to be
removed from the escalator driving-machine
motor and brake. The switch shall be of the
manually opened and closed type and shall be
marked “STOP.”
K. Hand or finger guards shall be
provided at the point where the handrail
enters the balustrade.
L. Where the clearance of the upper
outside edge of the balustrade and a ceiling or
scaffold is less than twelve inches (12") or
where the intersection of the outside
balustrade and a ceiling or soffit is less than
twenty-four inches (24") from the centerline
of the handrail, a solid guard shall be provided in the intersection of the angle of the outside balustrade and the ceiling or soffit. The
vertical front edge of the guard shall project
a minimum of fourteen inches (14") horizontally from the apex of the angle. The escalator side of the vertical face of the guard shall
be flush with the face of the wellway. The
exposed edge of the guard shall be rounded.
3. Moving walks.
A. Each moving walk shall be provided with an electrically released, mechanically applied brake capable of stopping and
holding treadway with a load up to and
including the rated load.
B. Starting switches shall be of the
key-operated type and shall be located within
sight of the exposed treadway.
C. Each moving walk shall be provided with an emergency stop button or manually operated switch at each entrance and exit.
The switches shall be protected to prevent the
accidental operation of them. The operation
of any of these switches shall interrupt the
power to the driving-machine motor and
brake.
D. A device shall be provided which
will cause interruption of power to the driving-machine motor and brake if the connecting means between pallets break.
E. The entrance to and exit from a
moving treadway shall be provided with a
threshold plate which shall have teeth and be
adjusted so that the teeth are below the treadway.
F. An enclosed fused disconnect
switch or a circuit breaker arranged to disconnect the power supply to the moving walk
shall be provided in the space where the controller is located.
G. If the balustrade covers the edge of
the treadway the clearance between the top
surface of the treadway and the underside of
the balustrade shall not exceed one-fourth
inch (1/4"). Where skirt panels are used the
horizontal clearance on either side of the
treadway and the adjacent skirt panel shall be
not more than one-fourth inch (1/4").
H. A stop switch shall be provided in
each machinery space where means of access
to the space is provided. The switch when
opened shall cause electrical power to be
removed from the driving-machine motor and
brake. The switch shall be of the manually
operated type, and shall be marked “STOP.”
I. Hand or finger guards shall be provided at the point handrails enter the
balustrade.
J. All balustrades shall be smooth and
free of rough surfaces. All screws shall be
flush or oval head. Screw heads shall be
smooth and free of burrs.
K. On pallet type treadways adjacent
ends of the pallets shall not vary in elevation
more than one-sixteenth inch (1/16"). The
distance between pallets shall not exceed five
thirty-seconds inch (5/32").
L. All repairs and alterations shall
comply with ASME A17.1, 1996 edition.
(U) Existing Vertical and Inclined Platform
Lifts.
1. Existing vertical and inclined platform lifts shall meet the requirements of
ASME A17.1, 1984 edition, Part 20.
(V) Existing Manlifts.
1. Existing manlifts shall be inspected
per the requirements of ASME A90.1, 1997
edition.
AUTHORITY: section 701.355, RSMo 2016.*
Original rule filed Aug. 26, 1998, effective
July 1, 1999. Amended: Filed Aug. 17, 2000,
effective Feb. 28, 2001. Emergency amendment filed April 30, 2001, effective May 10,
2001, expired Nov. 5, 2001. Amended: Filed
April 30, 2001, effective Oct. 30, 2001.
Amended: Filed Dec. 16, 2002, effective June
30, 2003. Amended: Filed June 14, 2004,
effective Dec. 30, 2004. Amended: Filed Dec.
4, 2006, effective May 30, 2007. Amended:
Filed Oct. 16, 2019, effective April 30, 2020.
*Original authority: 701.355, RSMo 1994.