5 CSR 25-500.087
Fire Safety
PURPOSE: This rule establishes the fire safety requirements for
group day care homes and child day care centers.
(1) The following definitions shall be used in interpreting this
rule:
(A) Alterations are changes made to the structure or floor
plan of the facility by removing or adding walls and doors or
adding space;
(B) Dead-end is a corridor or hallway with no exit at the end
that causes occupants to retrace their path to reach an exit;
(C) Exit is the portion of a means of egress that is separated
from all other areas of the building or structure by construction
or equipment required to provide a protected way of travel to
the exit discharge. Exits include exterior exit doors, exit passageways, horizontal exits, separated exit stairs, and separated
exit ramps;
(D) Exit access is the portion of a means of egress that leads
to an exit;
(E) Exit discharge is the portion of a means of egress between
the termination of an exit and a public way;
(F) Fire barrier is a structural element, either vertical or horizontal, such as a wall or floor assembly that is designed and
constructed with a specified fire resistance rating to limit the
spread of fire and restrict the movement of smoke. Such barriers may have protected openings;
AND SECONDARY EDUCATION
(G) Fire resistance rating is the length of time in minutes or
hours that materials or structural elements can withstand fire
exposure;
(H) Flame resistant material is the property of material or
their structural elements that prevents or retards the passage
of excessive heat, hot gases, or flames under the conditions in
which they are used;
(I) Flame retardant is a chemical applied to material or other
substance that is designed to retard ignition or the spread of
fire;
(J) Interior finish includes the interior wall and ceiling finish,
and interior floor finish;
(K) Level exit discharge is a horizontal plane that is located
from the point at which an exit terminates and the exit discharge begins. The horizontal plane shall not vary more than
two inches (2”) in rise or fall;
(L) Level is the portion of a building included between the
upper surface of a floor and the ceiling above it, or any upper
surface of a floor and the ceiling above it that is separated by
more than five (5) steps on a stairway;
(M) Means of egress is a continuous and unobstructed way of
travel from any point in a building or structure to a public way.
A means of egress consists of three (3) distinct parts: the exit
access, the exit, and the exit discharge;
(N) Mixed occupancy is when a facility is located in the same
building or structure as another occupancy. This may include
a business or place of assembly;
(O) Public way is an area such as a street or sidewalk that is
open to the outside and is used by the public for moving from
one (1) location to another;
(P) Remote exit or means of egress is when two (2) exits or
two (2) exit access doors are required. Each exit or exit access
door shall be placed at a distance apart equal to at least onehalf (1/2) the length of the maximum overall diagonal dimension of the building or area to be used;
(Q) Self-closing means to be equipped with an approved device that will ensure closing after having been opened;
(R) Smoke barrier is a structural element, either vertical or
horizontal, such as a wall, floor, or ceiling assembly that is designed and constructed to restrict the movement of smoke. A
smoke barrier may or may not have a fire resistance rating; and
(S) Supervised automatic sprinkler system is a system with
the initiating devices monitored by the fire alarm control
panel. This may include switches used to monitor the position
of valves, a low air pressure switch, a water flow switch, and a
tamper switch.
(2) General Requirements.
(A) The Missouri Division of Fire Safety shall inspect the
facility annually for the capacity specified on the license application and the fire inspection request. The inspection shall
include a determination of whether or not the facility is approved for overlap care as provided in 19 CSR 30-62.162 Overlap
Care of Children.
(B) Hangings or draperies shall not be placed over exit doors
or located to conceal or obscure any exit. All hangings and
draperies shall be treated with a flame retardant material with
verification of the treatment on file at the facility and available
for review by the fire inspector.
(C) Mirrors shall not be placed on exit doors or adjacent to
any exit that may confuse the direction of exit.
(D) Art work and teaching materials attached directly to the
walls shall not exceed thirty percent (30%) of the wall area. No
art work or teaching materials shall be hung from the ceilings
or in the doorways.
(E) The evacuation/emergency plan for fires and tornadoes
shall be posted conspicuously and shall include the route for
the drills and special instructions for infants and nonambulatory children.
(F) Child care staff shall conduct at least one (1) fire drill each
month and a disaster drill at least every three (3) months. The
disaster drills shall include tornado drills. The provider shall
maintain a written record at the facility of the date, type of
drill, time required to evacuate the building, and number of
children present during the drill.
1. Unscheduled drills may be held at the fire inspector’s
discretion.
2. A full evacuation of the facility may be postponed during
severe weather.
3. An evacuation/emergency plan that is approved by the
fire inspector shall be posted in each area of the facility used
for child care. The plan shall include special instructions for
infants and nonambulatory children.
4. The fire alarm system in the building shall be activated
during all fire drills.
5. Fire drills shall be conducted as follows:
A. Drills shall simulate an actual fire condition;
B. The children shall not obtain clothing or other items
after the alarm has sounded;
C. The children shall proceed to a predetermined location outside the building that is sufficiently remote to avoid
fire danger, interference with fire department operations, or
confusion among different groups of children; and
D. Groups shall remain in place until a recall to the
building is issued or the children are dismissed.
(G) Children shall have no access to areas of the building that
do not meet fire safety requirements.
(H) All flammable or combustible liquids, matches, lighters,
or other hazardous items shall be stored so they are inaccessible to the children.
(I) The house numbers shall be plainly visible from the street
in case of emergency.
(J) Housekeeping practices that ensure fire safety shall be
maintained daily.
(K) Stairways, walks, ramps, and porches shall be kept free of
ice and snow.
(L) The provider shall immediately report any fire in the facility to the Office of the State Fire Marshal and the Department of
Health, Bureau of Child Care Safety and Licensure.
(M) No fresh-cut Christmas trees shall be used unless they are
treated with a flame resistant material. Documentation of the
treatment shall be on file at the facility and available for review
by the fire inspector.
(N) The Division of Fire Safety may make additional requirements that provide adequate life safety protection if it is determined that the safety of the occupants is endangered. Every
building or structure shall be constructed, arranged, equipped,
maintained, and operated to avoid danger to the lives and
safety of its occupants from fire, smoke, fumes, or resulting
panic during the period of time necessary for escape from the
building.
(O) Before construction begins or occupancy occurs, a full set
of construction plans shall be submitted to the Division of Fire
Safety for review and approval for new construction and for
alterations to existing buildings.
(P) During the construction or remodeling process, the provider shall request a framing and wiring inspection and an
inspection for the rough-in wiring for the fire alarm system by
the Division of Fire Safety before the walls are enclosed. Failure
to have these inspections conducted will result in an unapproved fire inspection from the Division of Fire Safety.
(Q) Mobile homes manufactured after November 27, 1973,
shall comply with the Missouri Public Service Commission,
regulations for mobile home tie-down systems. Manufactured
homes shall comply with section 700.070, RSMo 1994, regarding tie-down systems.
(R) All facilities shall comply with all local building codes,
fire codes, and ordinances.
(S) The latest edition of the National Fire Protection
Association (NFPA), Chapter 101, Life Safety Code, shall prevail
in the interpretation of this rule.
(T) When the licensed capacity increases, hours of care
change, alterations are completed, or other changes occur that
affect fire safety, the provider shall meet all the requirements
of this rule unless otherwise excepted by the Division of Fire
Safety.
(U) Facilities that were licensed and areas approved for child
care prior to the effective date of this rule shall have ceilings
at least seven feet (7') in height. Facilities initially licensed and
areas initially approved for child care on or after the effective
date of this rule shall meet all the requirements of this rule
and shall have ceilings at least seven feet, six inches (7'6") in
height. If alterations are made in facilities licensed prior to
the effective date of this rule, those facilities shall meet all
the requirements of this rule and shall have ceilings at least
seven feet, six inches (7'6") in height in the altered space. The
fire inspector may make an allowance for the installation of
ductwork and plumbing.
(V) Facilities served by a volunteer or membership fire department shall be a member in good standing with the fire
department. A copy of the membership or receipt for membership shall be on file at the facility and available for review.
(W) Clothes dryers shall be vented and maintained properly.
(3) Mixed Occupancies.
(A) In addition to meeting all the requirements of this rule,
facilities initially licensed and areas initially approved for child
care on or after the effective date of this rule, shall meet the
following requirements. If alterations are made in facilities
licensed prior to the effective date of this rule, those facilities
shall meet these requirements in the altered space—
1. When a facility is located in a building containing mixed
occupancies, the other occupancies shall be separated from the
facility by at least a one (1)-hour fire barrier; and
2. In facilities in apartment buildings, when both exit accesses exit into the same corridor, the corridor shall be protected throughout by a fire barrier with at least a one (1)-hour
fire resistance rated construction. All doors that open into the
corridor shall have a one (1)-hour fire resistance rating and
shall be self-closing.
(B) No facility shall be located next to a high hazard
area or occupancy. A high hazard area or occupancy is an
area, building, structure, or portions thereof, that contains
heat-producing appliances, or that manufactures, processes,
generates or stores materials that constitute a high fire, explosion, or health hazard. This includes any area, structure,
or building posing a degree of hazard greater than normal to
the general occupancy of the area, structure, or building.
(4) Exiting and Means of Egress.
(A) Each level occupied by children shall have at least two
(2) remotely located means of egress. Each door opening in a
means of egress shall be at least twenty-eight inches (28") wide.
In new construction, each door opening shall be a minimum of
thirty-two inches (32") wide.
(B) No room or space that is accessible only by a ladder,
folding stairs, overhead door, or through a trap door shall be
occupied at any time.
(C) Exit doors shall swing in the direction of egress travel and
shall be marked with a lighted exit sign with a battery backup
of ninety (90) minutes.
1. Exit doors required to be kept closed shall be self-closing.
2. Any door in a required means of egress from a facility
having an occupant load of one hundred (100) or more persons,
or any facility caring for children during nighttime hours, shall
be equipped with panic hardware or fire exit hardware. No
other latching devices shall be used.
3. No door in a means of egress shall be locked against
egress travel when the building is occupied. Locking devices
that impede or prohibit egress or that cannot be disengaged
easily shall not be used. Dead bolt locks that require a key to
unlock the door from the inside shall not be used. Locking or
latching devices installed on doors shall not be located higher
than fifty inches (50") above the finished floor.
4. Closet door latches shall be designed so children can
open the doors from the inside. Bathroom door locks shall be
designed to permit opening of the door from the outside in an
emergency. The opening device or key shall be readily accessible to the staff.
(D) In addition to meeting all the requirements of this rule,
facilities initially licensed and areas initially approved for
child care on or after the effective date of this rule, shall have
emergency lighting with a ninety (90)-minute battery backup
installed to light the path of egress. The fire inspector shall
determine the location and number of emergency lights. If
alterations are made in facilities licensed prior to the effective
date of this rule, those facilities shall meet this requirement in
the altered space.
(E) Stairways, landings, and ramps shall be free of all objects.
(F) Children shall not exit through a kitchen, bathroom, storage room, furnace room, garage, or any other rooms or areas
deemed hazardous by the fire inspector.
(G) Dead-ends as defined by 19 CSR 30-62.087(1)(B) Fire Safety
shall not exceed twenty feet (20').
(5) In addition to meeting all the requirements of this rule,
facilities initially licensed and areas initially approved for child
care on or after the effective date of this rule, shall meet the
following requirements. If alterations are made in facilities
licensed prior to the effective date of this rule, those facilities
shall meet these requirements in the altered space—
(A) Stairs in facilities with fifty (50) or more occupants shall
be at least forty-four inches (44") wide. Stairs in facilities with
less than fifty (50) occupants shall be at least thirty-six inches
(36") wide.
1. The maximum height of risers shall be seven inches (7")
with a minimum height of four inches (4").
2. The minimum tread depth shall be ten inches (10").
AND SECONDARY EDUCATION
3. The minimum height from any tread to the finished ceiling shall be six feet, eight inches (6' 8").
4. The maximum height between landings shall be no
more than twelve feet (12').
5. Landings shall be as wide as the clear width of the stairs.
(B) Handrails shall not project into the stairway more than
three and one-half inches (3 1/2") on each side.
1. Handrails shall be mounted at least thirty-four inches
(34”), and no more than thirty-eight inches (38"), above the surface of the treads. They shall have a clearance of at least one
and one-half inches (1 1/2") from the wall. Handrails shall be at
least one and one-half inches (1 1/2"), but no greater than two
inches (2") in diameter.
2. Stairs with no walls on either side shall have balusters
placed on the sides. There shall be no more than four inches
(4") between each baluster. They shall be attached to the stairs
in a sturdy manner.
(C) Ramps used in an exit discharge shall be at least forty-four inches (44") wide if the facility has fifty (50) or more
occupants. They shall be at least thirty-six inches (36") wide if
the facility has less than fifty (50) occupants.
1. Ramps greater than six inches (6") in height shall have
a maximum slope of one inch (1") drop for twelve inches (12")
of run. Ramps less than six inches (6") in height shall have a
maximum slope of one inch (1") drop for ten inches (10") of run.
2. Ramps greater than six inches (6") in height shall have
handrails and balusters placed on each side.
3. Ramps shall have a slip-resistant surface.
(D) The elevation of interior floor surfaces through doorways
shall not present a tripping hazard.
(6) Facilities caring for children under the age of twenty-four
(24) months shall have two (2) means of egress out of each
room that is dedicated for their use. One (1) means of egress
shall lead directly outside at level exit discharge. Both exit
doors shall be a minimum of thirty-six inches (36") wide or
wider to accommodate the largest crib in the room. Doors shall
swing in the direction of egress travel. The direct exit outside is
not required if the entire facility is protected throughout by an
approved supervised automatic sprinkler system.
(A) Children shall not pass through more than one (1) adjoining room to gain access to an exit door that leads directly
outside.
(7) Level of Exit Discharge.
(A) Areas used for day care shall not be located more than
one (1) level below ground level.
(B) In addition to meeting all the requirements of this rule,
facilities initially licensed and areas initially approved for child
care on or after the effective date of this rule, shall meet the
following requirements. If alterations are made in facilities
licensed prior to the effective date of this rule, those facilities
shall meet these requirements in the altered space:
1. Where children are occupying a level below or above
the level of exit discharge (basement or second floor), at least
one (1) means of egress shall be an exit discharging directly to
the outside. The vertical travel to ground level shall not exceed
eight feet (8') for the basement and twelve feet (12.') for the second floor; and
2. Where children are occupying a level below or above
the level of exit discharge (basement or second floor), arrangement of means of egress shall be remote from each other.
(8) Travel Distance to Exits.
(A) The travel distance between any room door intended
as an exit access or an exit shall not exceed one hundred feet
(100'). This travel distance may be increased by fifty feet (50')
in buildings protected throughout by a supervised automatic
sprinkler system that is approved by the fire inspector based
on the National Fire Protection Association’s Standards for
Sprinkler Systems.
(B) The travel distance between any point in a room and an
exit shall not exceed one hundred fifty feet (150’). This travel
distance may be increased by fifty feet (50’) in buildings protected throughout by a supervised automatic sprinkler system
that is approved by the fire inspector based on the National Fire
Protection Association’s Standards for Sprinkler Systems.
(C) The travel distance between any point in a sleeping room
and an exit access to that room shall not exceed fifty feet (50’).
(9) Windows for Rescue and Ventilation.
(A) In addition to meeting all the requirements of this rule,
facilities initially licensed and areas initially approved for child
care on or after the effective date of this rule, shall meet the
following requirements. If alterations are made in facilities
licensed prior to the effective date of this rule, those facilities
shall meet these requirements in the altered space—
1. Every room or space greater than three hundred (300)
square feet used by children shall have at least one (1) outside
window for emergency rescue and ventilation. The window
shall be operable from the inside without the use of tools and
shall provide a clear opening of at least twenty inches (20")
wide, twenty-four inches (24") in height. The total clear opening space shall be no less than 5.7 square feet in size. The bottom of the opening shall be no more than forty-four inches
(44") above the floor and any latching device shall be operated
easily. The clear opening shall be a rectangular solid, with
a minimum width and height that provides the required 5.7
square feet opening and a minimum depth of twenty inches
(20") to allow passage through the opening. The windows shall
be accessible by the fire department and shall open into an
area having access to a public way. This does not apply in the
following situations:
A. In buildings protected throughout by an approved,
supervised automatic sprinkler system; and
B. When the room or space has a door leading directly to
the outside of the building;
2. In rooms located higher than three (3) stories above the
level of exit discharge, the operable clear height, width, and
area of the window shall be permitted to be modified to the
dimensions necessary for ventilation as determined by the fire
inspector; and
3. No windows shall have bars or any other items placed
over them in a stationary manner that would impede a rescue
or evacuation attempt.
(10) Protection.
(A) The door between the main level and any level below
or above it shall be equipped with a one (1)-hour fire rated
self-closing door.
(B) Vertical openings shall be enclosed and protected with a
one (1)-hour fire barrier.
(C) The following rooms and areas used for the storage,
processing, or use of materials shall be separated from the
remainder of the building by fire barriers having a fire resistance rating of at least one (1) hour of protection:
1. Boiler, furnace rooms, and rooms containing water heaters. This does not apply to rooms enclosing only air-handling
equipment;
2. Rooms or areas used for the storage of combustible supplies in quantities deemed hazardous by the fire inspector;
3. Rooms or areas used for the storage of hazardous materials, or flammable or combustible liquids in quantities deemed
hazardous by the fire inspector;
4. Laundries and laundry rooms, maintenance shops, including woodworking and painting areas; and
5. The doors to janitorial closets shall be equipped with
a self-closing device and a fire alarm initiating device in the
room.
(D) The rooms or areas listed in 19 CSR 30-62.087(10)(C)1.–5.
Fire Safety shall be inaccessible to children by use of a locked
doorknob or latch.
(E) The one (1)-hour fire resistance rating required for rooms
or areas listed in 19 CSR 30-62.087(10)(C)1.–5. Fire Safety is not
required if the facility installs a sprinkler head off the domestic
water supply or has an approved automatic sprinkler system.
A fire alarm initiating device shall be installed in the rooms
or areas listed in 19 CSR 30-62.087(10)(C)1.–5. Fire Safety as instructed by the fire inspector.
(11) Interior Finish.
(A) Interior wall and ceiling finishes throughout shall meet
the requirements of the latest edition of the National Fire
Protection Association, Chapter 101, Life Safety Code. Textile
materials having a napped, tufted, looped, woven, nonwoven,
or similar surface shall not be applied to walls or ceilings. Foam
plastic materials or other highly flammable or toxic material
shall not be used as an interior wall, ceiling, or floor finish.
(B) Interior floor finishes within corridors and exits shall be
Class I or II in accordance with Chapter 6 of the latest edition
of the Life Safety Code.
(C) In addition to meeting all the requirements of this rule,
facilities initially licensed and areas initially approved for child
care on or after the effective date of this rule, shall have wall
studs, ceiling joists, and floor joists that are covered with a
minimum of Class C finish with no exposed studs or joists. If
alterations are made in facilities licensed prior to the effective
date of this rule, those facilities shall meet these requirements
in the altered space.
(12) Detection, Alarms, and Extinguishment.
(A) Facilities using equipment or appliances that pose a potential carbon monoxide risk, including facilities with attached
garages, shall install a carbon monoxide detector(s). The
detector(s) shall be installed according to the manufacturer’s
instructions. The fire inspector may require additional carbon
monoxide detectors if the fire inspector determines that the
safety of the occupants is endangered.
1. Carbon monoxide detectors shall be in good operating
condition. If a battery operated detector is not operational, the
provider shall install a detector that is powered by the home’s
electrical system with a battery backup.
2. If an elevated carbon monoxide level is detected during
a fire inspection, the provider shall have all gas-fired appliances
checked by a heating and air conditioning company to identify the source of the carbon monoxide. Until the provider has
documentation on file at the facility verifying that all gas-fired
appliances were checked by a heating and air conditioning
company and are in safe working order, and the facility is determined safe by the fire inspector, the fire inspection shall not
be approved.
3. If a level of carbon monoxide is determined that endangers the children in care, the fire inspector shall take measures
necessary to protect the children. This may include evacuation
of the building or closing the facility. The provider shall obtain
and have on file at the facility, documentation verifying that
all gas-fired appliances were checked by a heating and air conditioning company and are in safe working order. The facility
shall be reinspected by the fire inspector and determined safe
before the children can return to the building or the facility
can reopen.
(B) At least one portable, 5 lb., 2A-10 BC, fire extinguisher
shall be required in all facilities. One (1) fire extinguisher shall
be located in or near the kitchen or a location required by the
fire inspector. The fire inspector may require additional fire
extinguishers based on the floor plan, arrangement of space,
and the number of levels used.
(C) Fire extinguishers shall be installed and maintained
according to the instructions of the fire inspector and shall
be inspected and approved annually by a fire extinguisher
company. Documentation of the inspection and approval shall
be on file at the facility and available for review by the fire
inspector.
(D) A smoke detector(s) shall be installed in each room
where children are being cared for and all other areas that are
deemed necessary by the fire inspector. Smoke detectors shall
be in good operating condition and functional at all times. If
smoke detectors are not operational, the provider shall install
smoke detectors as required by 19 CSR 30-62.087 (12)(F)1. Fire
Safety.
(E) All facilities shall have a manual fire alarm system. Pull
stations shall be mounted at each exit door and at least one (1)
horn or strobe light shall be installed in a central location on
each floor. Additional horns or strobe lights may be required
by the fire inspector dependent upon the floor plan and arrangement of space. The battery backup control panel shall be
Underwriter’s Laboratory (UL) or Factory Mutual (FM) listed and
installed on a circuit used only for this system in the breaker
box. The fire alarm system shall be installed and maintained
in good working order. The fire inspector shall base the inspection of this system on the National Fire Protection Association
Standards, National Fire Alarm Code. This does not apply to
facilities housed in one (1) room only where all exit doors lead
directly outside at level exit discharge.
(F) In addition to meeting all the requirements of this rule,
facilities initially licensed and areas initially approved for child
care on or after the effective date of this rule, shall meet the
following requirements. If alterations are made in facilities
licensed prior to the effective date of this rule, those facilities
shall meet these requirements in the altered space—
1. Group day care homes and day care centers caring for
fifty (50) or fewer children at one (1) time shall have smoke detectors installed in each room used by the children and in other
locations as deemed necessary by the fire inspector. All smoke
detectors shall be powered by the building’s electrical system
and have a battery backup. When more than one (1) smoke detector is required in a facility, they shall be arranged so that the
activation of any detector causes the operation of an alarm in
all detectors. This system may work independently from the
manual fire alarm system;
AND SECONDARY EDUCATION
2. Day care centers caring for more than fifty (50) children
at one time shall have a full coverage fire alarm system. Smoke
detectors shall be installed in each room, throughout hallways, and in other locations as deemed necessary by the fire
inspector. Heat detectors shall be installed in the attic, kitchen,
mechanical rooms, and other locations as deemed necessary
by the fire inspector. The fire alarm system shall be installed
and maintained in good working order. The fire inspector
shall base the inspection of this system on the National Fire
Protection Association Standards, National Fire Alarm Code; and
3. Facilities using a commercial stove, deep fryer, two (2)
home-type ranges placed side-by-side, or a home-type range
that produces grease laden vapor, shall be equipped with a
range hood and extinguishing system with an automatic cutoff of fuel supply and exhaust system in case of fire. The fire
inspector shall inspect these systems to ensure that they are
in good working condition and are installed and maintained
correctly. The inspector shall base this inspection on the
National Fire Protection Association, Chapter 96, Standard for
Fire Protection of Commercial Cooking Operations.
A. Home-type stoves separated by an eighteen inch
(18")-cabinet shall not be required to have an extinguishing
system installed above them.
B. Facilities that cook on a home-type range and have a
menu that does not include frying or emitting a grease-laden
vapor, shall not be required to install a fire extinguishment
system above the range.
C. The range hood fire extinguishment system shall be
interconnected with the control panel of the fire alarm system.
The activation of the range hood fire extinguishment system
shall cause the fire alarm to activate throughout the building.
(G) Day care centers caring for more than one hundred (100)
children at one time shall have a fire alarm system that notifies a monitoring company or the fire department. A copy of
the contract with the monitoring company shall be on file at
the facility and available for review by the fire inspector. The
contract with the monitoring company shall not be terminated
without approval of the fire inspector.
(H) Facilities that have a supervised automatic fire sprinkler
system installed shall have the system tested and approved
annually by a fire sprinkler company. A copy of the test report
and approval of the system shall be kept on file at the facility
and available for review by the fire inspector.
(I) When child care space is located above the second floor,
the entire building shall be protected by a supervised automatic sprinkler system.
(13) Heating, Ventilating, and Air Conditioning Equipment.
(A) Unvented fuel-fired room heaters, portable electrical
space heaters, or floor furnaces shall not be used during child
care hours. The provider shall sign a compliance letter verifying that such equipment will not be used.
(B) Heating equipment and radiators in areas occupied by
children shall have partitions, screens, or other means to protect children from hot surfaces and open flames. If solid partitions are used, provisions shall be made to ensure adequate
air for combustion and ventilation for heating equipment.
Partitions shall be constructed of noncombustible material and
shall not obstruct exit access.
(C) Wood heating systems shall not be used unless the system
is installed outside the facility.
(D) Facilities with a water heater over two hundred thousand
(200,000) British thermal units (Btus) per hour input or larger,
or that is heating with a boiler, shall have a valid permit from
the Division of Fire Safety posted on the premises. A copy of the
permit shall be kept on file at the Division of Fire Safety.
(E) Gas and electric heating equipment shall be equipped
with thermostatic controls. Gas water heaters shall have a
properly sized pressure relief valve and be vented properly by
a galvanized flue pipe with screws at every joint in the pipe or
by material recommended by the manufacturer. The drip leg
pipe on the pressure relief valve shall extend to approximately
six inches (6") above the floor.
(F) Furnaces shall be vented properly. Furnace flue pipes
shall be constructed of galvanized pipe or material recommended by the manufacturer. Galvanized pipe shall be secured
by screws at every joint in the pipe.
(G) Joints in gas supply pipes shall be located outside the
furnace cabinet housing.
(H) Furnaces shall be equipped with an electrical fused
switch to protect the unit from electrical overloading and to
disconnect the electrical supply.
(I) Furnace rooms and rooms containing water heaters shall
have adequate combustion air for the units. The vent size
openings for the combustion air shall be measured at one (1)
square inch per one thousand (1,000) Btu input, if the combustion air is drawn from inside the structure, and one (1) square
inch per four thousand (4,000) Btu input if the air is drawn from
outside the structure. There shall be two (2) combustion air
vent openings in each furnace room. One (1) opening shall be
located at the lower level and the other at the upper level. One
(1) combustion air vent opening shall be permitted if the vent
opening extends directly to the outside of the structure. This
opening shall be one (1) square inch per three thousand (3,000)
Btu input of the total gas appliances located in the room. The
gas appliances shall have a clearance around them of one inch
(1") from the sides and back and six inches (6") from the front
of the unit.
(J) Furnace or air-handling equipment that has an air flow of
two thousand (2,000) cubic feet of air per minute or more shall
have a fan shut-down switch and duct smoke detectors that are
interconnected with the fire alarm system.
(K) Air conditioning, heating, ventilating duct work, and
related equipment shall be installed safely and be in good
operating condition as determined by the fire inspector. The
fire inspector shall base this on the National Fire Protection
Association, Chapter 90A, Standard for the Installation
of Air Conditioning and Ventilating Systems, or National
Fire Protection Association, Chapter 90B, Standard for the
Installation of Warm Air Heating and Air Conditioning Systems,
as applicable.
(L) In addition to meeting all the requirements of this rule,
facilities initially licensed and areas initially approved for child
care on or after the effective date of this rule, shall meet the
following requirements. If alterations are made in facilities
licensed prior to the effective date of this rule, those facilities
shall meet these requirements in the altered space—
1. Gas shut-off valves shall be located next to all gas appliances, furnaces, and water heaters; and
2. If a furnace or water heater is located inside a garage, it
shall be at least eighteen inches (18") above the finished floor
and enclosed inside a fire resistant room as provided in 19 CSR
30-62.087(10) Fire Safety.
(14) Electrical Services.
(A) Electrical wiring shall be installed and maintained in
good working order. If the fire inspector considers the wiring
to be unsafe for the occupants or it is installed improperly, an
inspection by a licensed electrician may be required prior to
fire safety approval. The inspection by the licensed electrician
shall be based on National Fire Protection Association, Chapter
70, National Electrical Code.
(B) Protective covers or inserts for electrical receptacles shall
be installed in all areas occupied by children.
(C) Electrical extension cords shall not be used unless approved in writing by the fire inspector.
(15) Equivalency Concepts.
(A) Nothing in this rule is intended to prevent the use of
systems, methods, or devices of equivalent or superior quality,
strength, fire resistance, effectiveness, durability, and safety as
alternatives required by this rule. These alternatives may be
used only if technical documentation to demonstrate equivalency and the system, method, or device is submitted and
approved by the Missouri Division of Fire Safety.
AUTHORITY: sections 210.221.1(3) and 210.252.5, RSMo Supp.
1999.* This rule originally filed as 19 CSR 30-62.087. Original rule
filed Feb. 18, 1999, effective Sept. 30, 1999. Emergency amendment
filed March 1, 2000, effective March 11, 2000, expired Sept. 6, 2000.
Amended: Filed March 1, 2000, effective Aug. 30, 2000. Moved to 5
CSR 25-500.087, effective Aug. 30, 2021.
*Original authority: 210.221.1, RSMo 1949, amended 1955, 1987,
1993, 1995, 1999; 210.252, RSMo 1993, amended 1999.