9 CSR 40-1.090
Fire Safety and Emergency Preparedness
PURPOSE: The rule prescribes fire safety
and emergency preparedness requirements for
all residential programs and day programs
subject to licensure by the department in
accordance with 9 CSR 40-1.055. This rule
does not apply to Residential Care Facilities
(RCF) and Assisted Living Facilities (ALF)
dually licensed by the Department of Health
and Senior Services (DHSS).
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule
would be unduly cumbersome or expensive.
This material as incorporated by reference in
this rule shall be maintained by the agency at
its headquarters and shall be made available
to the public for inspection and copying at no
more than the actual cost of reproduction.
This note applies only to the reference material. The entire text of the rule is printed
here.
(1) General Requirements. The program
director shall ensure all local building codes,
fire codes, and ordinances are followed and
all hazard detection systems, alarm systems,
and other safety equipment are maintained in
proper operating condition. Practices shall be
implemented to protect all individuals from
fire, smoke, noxious fumes, and other safety
hazards.
(A) Each residential program and day program shall be inspected at least annually by a
Division of Fire Safety inspector. Initial and
annual inspection reports must be maintained
on site and be available for review by department staff and other authorized representatives.
(B) The 2018 regulations of the NFPA Life
Safety Code 101 will prevail in the interpretation of these rules. The regulations are incorporated by reference and available from
NFPA, 1 Batterymarch Park, Quincy, MA
02169, (617) 770-3000 or 1-800-344-3555,
available at: www.nfpa.org. This rule does
not incorporate any subsequent amendments
or additions to the regulations listed above.
This rule does not prohibit programs from
complying with the regulations set forth in
newer editions of the incorporated by reference material listed in this subsection of this
rule.
(C) The program address must be posted
on the outside of the building where it is
plainly visible from the street with
numbers/letters at least four inches (4") in
height and contrasting color with the building.
(D) Evacuation routes, with diagrams giving clear directions on how to safely exit the
building in a timely manner, must be posted
in locations throughout the building that are
easily accessible to individuals served, staff,
and visitors.
(E) Staff shall demonstrate the knowledge
and ability to implement the program’s emergency preparedness and evacuation plans and
be trained and demonstrate the ability to
operate the fire alarm system, fire extinguishers, and other safety devices. Training must
be documented in personnel records, including date(s) and signature of trainer(s).
(F) A fire drill shall be conducted at least
one (1) time per quarter, with a minimum of
one (1) annual drill during sleeping hours.
All staff and individuals on each shift must
participate in at least one (1) annual fire drill.
All drills must comply with the specifications
of the posted evacuation plan.
(G) In addition to fire drills, staff and individuals served shall participate in other emergency drills at least quarterly and as specified
in the emergency policies and procedures.
1. Individuals who are unable to react to
emergency situations in a safe and expedient
manner must have the supports necessary to
implement their individual emergency plan.
2. Each drill must be documented and
reviewed by staff responsible for execution of
the emergency practices. Documentation
shall include, but is not limited to, number of
staff and individuals present during the drill,
success of the drill or problems encountered,
length of the drill, and corrective action
taken, including training and education of
staff and individuals served, as necessary.
(H) Hangings or draperies shall not be
placed over exit doors or located where they
conceal or obscure any exit.
(I) Stairways, sidewalks, ramps, and porches shall be kept clear of ice, snow, and any
other obstacles that may be a potential fall or
tripping hazard.
(J) Fresh-cut Christmas trees shall not be
used unless they are treated with a flame
resistant material and documentation of such
is maintained on-site.
(K) Candles and other devices that have an
open flame shall not be used indoors. Shortterm, supervised use of candles for special
occasions or dinners is permitted.
(L) A program served by a volunteer or
membership fire department shall maintain
documentation of a current contract or proof
of membership on-site.
(M) Staff shall notify the nearest fire
department when the residential program or
day program becomes operational and maintain the required signed documentation by the
local authority (fire department notification
form) on-site.
(N) Clothes dryers shall be properly maintained and vented to the outside, or as recommended by the manufacturer.
(O) Smoking shall not be allowed inside
the program. At the discretion of the program
director, designated outdoor smoking areas
may be provided away from doors and windows. Supervision must be maintained based
upon individual needs as documented in the
Individual Support Plan (ISP), Individual
Treatment Plan (ITP), or care plan.
(2) Hazard Detection, Alarms, and Extinguishment. All smoke detectors, carbon
monoxide detectors, alarm systems, sprinkler
systems, and adaptive alarm systems must be
installed and maintained in accordance with
the 2018 NFPA Life Safety Code 101, incorporated by reference and available from
NFPA, 1 Batterymarch Park, Quincy, MA
02169, (617) 770-3000 or 1-800-344-3555,
available at: www.nfpa.org. Staff of the Division of Fire Safety may make additional
requirements to provide adequate life safety
protection if it is determined the safety of
individuals is endangered. This rule does not
incorporate any subsequent amendments or
additions to the regulations listed above.
This rule does not prohibit programs from
complying with the regulations set forth in
newer editions of the incorporated by reference material listed in this section.
(A) Fire detection and other emergency
notification systems shall be maintained to
sound an alarm that can be heard throughout
the premises, above the noise of normal activities, radios, and televisions. Notification
must be provided automatically without
delay. Pre-signal systems are prohibited.
Staff of the Division of Fire Safety may make
additional requirements to provide adequate
life safety protection if it is determined the
safety of individuals is endangered.
1. Adaptive emergency alarm systems
must be installed if individuals who are deaf
are being served in the program.
(B) At least one (1) portable, five pound (5
lb.) ABC-rated fire extinguisher, with directions for use on the equipment, must be located on each floor of the building including in
or near every kitchen, storage room, furnace
area, and other mechanical equipment rooms.
Additional fire extinguishers may be required
by the local authority based on the floor plan
and number of levels being used by individuals served so travel distance is no greater than
seventy-five feet (75') between fire extinguishers.
1. All staff of the program must be
knowledgeable on the location and use of the
fire extinguisher(s).
2. Education provided to staff on the use
of fire extinguishers must be documented and
available on site, including date(s) and signature of trainer(s).
3. Fire extinguishers must be inspected
and approved annually by a fire safety authority. Documentation of the inspection and
approval, including date and signature of
inspector, must be maintained on-site.
(C) Programs serving four (4) or fewer
individuals must have at least one (1) certified Underwriters’ Laboratories, Inc. (UL) or
Factory Mutual (FM) smoke detector on each
floor in close proximity to bedrooms, hallways, living spaces, kitchen, storage rooms,
offices, and any other areas deemed necessary by Division of Fire Safety staff.
1. If battery-powered smoke detectors
are used, they must be tested monthly and
batteries changed as needed. Documentation
including the dates, testing, and changing of
batteries must be maintained on site.
2. Smoke detectors that are ten (10)
years old or older must be replaced with new
smoke detectors of the same style. Date(s) of
installation must be maintained on site.
(D) Programs serving five (5) or more
individuals must have a full coverage electrical fire alarm system with battery backup, a
master control panel, smoke detectors, heat
sensors, and pull station. Horns and strobe
lights connected to the fire alarm must be
installed throughout the building(s). All
equipment must be UL- or FM-certified and
installed on a dedicated circuit in the breaker
box.
1. The system must be tested, inspected,
and approved semi-annually by an authorized
inspector. A copy of the test report and
approval of the system must be maintained on
site.
2. Heat detectors shall be installed in all
for Community Residential Programs and Day Programs
mechanical rooms, kitchens, and throughout
the attic.
3. Smoke detectors that are connected to
a fire alarm system must be replaced after ten
(10) years of service or recalibrated by the
manufacturer of the smoke detector. If the
smoke detectors are recalibrated, temporary
smoke detectors must be installed so the fire
alarm system continues to function properly.
(E) In addition to having an electrical
alarm system, programs serving five (5) or
more individuals must have an automatic fire
sprinkler system when any of the following
conditions apply:
1. Individuals served use any floor
above the second (2nd) floor of the building;
2. Individuals who require mechanical
or staff assistance to evacuate the building
use any floor above or below the first (1st)
floor; or
3. Individuals use a floor below the level
of exit discharge, such as a basement, which
exceeds twelve hundred (1,200) square feet in
total area.
A. The water supply for the sprinkler
system may be a domestic water source, if the
domestic water system is designed to adequately support the design flow of the largest
number of sprinklers in any one area.
4. The automatic sprinkler system shall
be installed and maintained in accordance with
the 2019 NFPA Standards for Installation of
Sprinkler Systems, NFPA, 1 Batterymarch
Park, Quincy, MA 02169, (617) 770-3000 or
1-800-344-3555 incorporated by reference and
available at: https://www.nfpa.org/codesand-standards/all-codes-and-standards/list-ofcodes-and-standards/detail?code=13. This
rule does not incorporate any subsequent
amendments or additions to the standards
listed above. This rule does not prohibit programs from complying with standards set
forth in newer versions of the incorporated by
reference material listed in this paragraph of
this rule.
5. The sprinkler system shall be tested,
inspected, and approved semi-annually by an
authorized inspector. A copy of the test
report and approval of the system shall be
kept on file at the program for review by
Division of Fire Safety staff, department
staff, or other authorized representatives.
(F) Programs using a commercial stove,
deep fryer, or two (2) home-type ranges
placed side by side must be equipped with a
range hood and extinguishing system with an
automatic cutoff of the fuel supply and
exhaust system in case of fire.
1. The hood and extinguishment system
must be inspected by a qualified technician to
ensure they are in good operating condition in
accordance with the 2017 NFPA Standards
for Ventilation Control and Fire Protection of
Commercial Cooking Operations, incorporated by reference and available at NFPA, 1 Batterymarch Park, Quincy, MA 02169, (617)
770-3000 or 1-800-344-3555, available at:
h t t p s : / / w w w. n f p a . o rg / c o d e s - a n d -
standards/all-codes-and-standards/list-ofcodes-and-standards/detail?code=96. This
rule does not incorporate any subsequent
amendments or additions to the standards
listed above. This rule does not prohibit programs from complying with standards set
forth in newer versions of the incorporated by
reference material listed in this paragraph of
this rule.
2. The range hood and extinguishment
system shall be connected to the control panel
of the fire alarm system. The activation of
the range hood fire extinguishment system
must cause the fire alarm system to activate
throughout the building.
3. Home-type ranges separated by an
eighteen inch (18") cabinet are not required
to have an extinguishing system installed
above them. Programs using a home-type
range with no more than four (4) burners
and/or grill are not required to have a fire
extinguishing system above the range.
(G) Programs that have an attached garage
and/or use gas utilities, equipment, or appliances that pose a potential carbon monoxide
risk, shall install carbon monoxide detectors
on each level of the building according to the
2018 NFPA Life Safety Code 101 and the recommendation of the local authority. The regulations are incorporated by reference and
available from NFPA, 1 Batterymarch Park,
Quincy, MA 02169, (617) 770-3000 or 1-800344-3555, and available at: www.nfpa.org.
This rule does not incorporate any subsequent amendments or additions to the regulations listed above. This rule does not prohibit
programs from complying with the regulations set forth in newer editions of the incorporated by reference material listed in this
subsection of this rule.
1. If an elevated carbon monoxide level
is detected in a program during a fire inspection, all gas-fired appliances must be checked
by a heating and air conditioning company to
identify the source of the carbon monoxide.
Until program staff have documentation on
file verifying all gas-fired appliances were
checked by a heating and air conditioning
company, are in safe working order, and the
building(s) is determined safe by the local
authority, the fire inspection will not be
approved.
2. If a level of carbon monoxide is determined that endangers the lives of individuals,
the local authority shall take measures necessary to ensure their safety which may include
evacuating or closing the program. Program
staff shall obtain and maintain documentation
on site verifying all gas-fired appliances were
checked by a heating and air conditioning
company and are in safe working order. The
program must be reinspected by the local
authority and determined safe before individuals can return or the program can reopen.
(3) Means of Egress and Exits. Means of
egress and exit from all buildings shall be
maintained in accordance with the 2018
NFPA Life Safety Code 101. The regulations
are incorporated by reference and available
from NFPA, 1 Batterymarch Park, Quincy,
MA 02169, (617) 770-3000 or 1-800-3443555, available at: www.nfpa.org. This rule
does not incorporate any subsequent amendments or additions to the regulations listed
above. This rule does not prohibit programs
from complying with the regulations set forth
in newer editions of the incorporated by reference material listed in this section.
(A) All programs must meet the following
requirements:
1. Each floor used by individuals served
shall have at least two (2) remotely located
means of exit. At least one (1) of these exits
must lead directly outside at ground level, to
an outside stairway, or to an enclosed stairway constructed of materials with at least a
one- (1-) hour fire resistance rating on each
level and an exit leading directly outside;
2. Each exit door shall be at least thirty
inches (30") wide in existing licensed buildings and at least thirty-six inches (36") wide
in buildings constructed after the effective
date of these licensing rules;
3. All means of egress shall be free of
items that would obstruct the path of travel;
4. Doors that serve as a means of exit
shall not be locked or blocked against egress
travel when the building is occupied. Door
locks requiring a key, tool, special code, or
knowledge to unlock from the inside shall not
be used;
5. Overhead garage doors shall not be
considered as exit doorways;
6. Mirrors shall not be placed on exit
doors or adjacent to any exit in such a manner to confuse the direction of the exit;
7. All hallways must have a clear width
of at least thirty-six inches (36") wide and be
kept free of all articles that might impede an
individual’s evacuation from the building,
including wheelchairs, walkers, or other support equipment;
8. Dead-end hallways cannot exceed
twenty feet (20');
9. No primary means of escape or
planned exit shall lead through a bathroom,
storage room, furnace room, garage, or any
other room deemed hazardous by the local
authority;
10. All ramps must be accessible, safe,
and installed in accordance with the 2010
Americans with Disabilities Act Standards
for Accessible Design, established by the
U.S. Department of Justice, Civil Rights
Division, 950 Pennsylvania Avenue NW,
Washington DC 20530, (800)514-0301,
incorporated by reference and available at:
https://www.ada.gov/regs2010/2010ADAStandards/2010ADAstandards.htm. This rule
does not incorporate any subsequent amendments or additions to the standards listed
above. This rule does not prohibit programs
from complying with the standards set forth
in newer editions of the incorporated by reference material listed in this paragraph of this
rule; and
11. Programs that have stairs, including stairs used as a fire escape, shall meet
the requirements of the 2010 Americans
with Disabilities Act Standards for Accessible Design, established by the U.S. Department of Justice, Civil Rights Division, 950
Pennsylvania Avenue NW, Washington DC
20530, (800) 514-0301, incorporated by
reference
and
available
at:
https://www.ada.gov/regs2010/2010ADAStandards/2010ADAstandards.htm, the 2018
NFPA Life Safety Code 101, incorporated by
reference and available from NFPA, 1 Batterymarch Park, Quincy, MA 02169, (617)
770-3000 or 1-800-344-3555, available at:
www.nfpa.org., and the local authority. This
rule does not incorporate any subsequent
amendments or additions to the standards
listed above. This rule does not prohibit programs from complying with the standards set
forth in newer editions of the incorporated by
reference material listed in this paragraph of
this rule.
(B) Programs serving five (5) or more individuals shall meet the following requirements
for means of egress and exit:
1. All outside exit doors must swing in
the direction of egress travel;
2. All exit doors must be clearly marked
and illuminated; and
3. Emergency lighting with battery
backup shall be installed to light all paths of
egress travel. The location and number of
emergency lights shall be determined by the
local authority. Emergency lights shall be
tested monthly with documentation maintained on site indicating which lights were
tested, the date tested, and the name and signature of the staff performing the test.
(C) Each wing or hallway in programs
serving ten (10) or more individuals must be
separated into fire compartment areas by fire
doors and walls having not less than a one-
(1-) hour rating. All fire doors shall be
equipped with a door closer and may be held
open at all times with an electrical magnetic
switch that is interconnected to the fire alarm
system.
(4) Appliances and Mechanical Equipment.
All heating, cooling, ventilation system(s),
other mechanical equipment, and appliances
shall be installed and maintained in accordance with manufacturer’s recommendations.
(A) Use of unvented fuel-fired room
heaters, portable electric space heaters, and
floor furnaces is not permitted.
(B) If wall heaters are used, they must be
installed and approved by the local authority
and include adequate guards.
(C) The home’s primary heat source shall
not be a fireplace.
1. Fireplaces used for decorative purposes shall be installed, operated, and maintained in a safe manner. The use of a wood-
or gas-burning fireplace is permitted only if
the fireplace is built of firebrick or metal,
enclosed by masonry, has a metal or tempered glass screen, and is inspected and
approved by a local authority with documentation maintained on-site.
2. Fireplaces not in compliance with
these requirements may be in the home if
they are for decorative purposes only, or if
they are equipped with decorative-type electric logs or other electric heaters which bear
the UL label and are constructed of electrical
components complying with and installed in
compliance with the NFPA 2017 National
Electrical Code, NFPA, 1 Batterymarch
Park, Quincy, MA 02169-7471, (800) 3443555, incorporated by reference and available
at:
https://www.nfpa.org/NEC/electricalcodes-and-standards. This rule does not
incorporate any subsequent amendments or
additions to the standards listed above. This
rule does not prohibit programs from complying with the standards set forth in newer
editions of the incorporated by reference
material listed in this paragraph of this rule.
(D) If the building has elevator(s), the elevator(s) shall be inspected annually by a
state-licensed inspector and have a stateissued operating permit from the Division of
Fire Safety available for review.
(5) Protection. Smoke stop partition(s) in all
programs must comply with the requirements
of the Division of Fire Safety and the 2018
NFPA Life Safety Code 101, NFPA, 1 Batterymarch Park, Quincy, MA 02169, (617)
770-3000 or 1-800-344-3555, incorporated
by reference and available at: www.nfpa.org.
This rule does not incorporate any subsequent amendments or additions to the regulations listed above. This rule does not prohibit
programs from complying with the regulations set forth in newer editions of the incorporated by reference material listed in this
section.
(6) Interior Finish. Interior finish in all programs must comply with requirements of the
Division of Fire Safety and the 2018 NFPA
Life Safety Code 101, NFPA, 1 Batterymarch
Park, Quincy, MA 02169, (617) 770-3000 or
1-800-344-3555, incorporated by reference
and available at: www.nfpa.org. This rule
does not incorporate any subsequent amendments or additions to the regulations listed
above. This rule does not prohibit programs
from complying with the regulations set forth
in newer editions of the incorporated by reference material listed in this section.
AUTHORITY: sections 630.050 and 630.705,
RSMo 2016.* Original rule filed May 14,
2020, effective Dec. 30, 2020.
*Original authority: 630.050, RSMo 1980, amended 1993,
1995, 2008 and 630.705, RSMo 1980, amended 1982,
1984, 1985, 1990, 2000, 2011, 2014.