9 CSR 45-5.150
Fire Safety for Group Homes Serving 17 or More People
PURPOSE: This rule establishes fire safety requirements for group
homes serving seventeen (17) or more people funded through the
Medicaid home and community-based waiver. The department
delegates its authority for fire safety inspections under this rule to
the Department of Public Safety, Division of Fire Safety.
(1) General Requirements.
(A) The staff shall conduct at least one (1) fire drill per month
and one (1) natural disaster drill per quarter, with a minimum
of two (2) drills, one (1) fire and one (1) natural disaster,
conducted annually while the individuals are sleeping. A drill
must be conducted within one (1) week of the arrival of a new
individual. The staff shall maintain a written record at the
facility of the date, type of drill, time required to evacuate the
building, whether the evacuation was completed, notation of
any problems evacuating, and number of occupants present
during the drill.
(B) Unscheduled drills shall be held at the Division of Fire
Safety inspector’s discretion.
(C) During severe weather, fire drills may be postponed.
(D) Each fire drill shall evacuate all persons from the
building, or evacuate to an area of refuge and defend in place
and be conducted as follows:
1. Drills simulate an actual fire condition;
2. Occupants (referred to hereafter as “individuals”) and
staff members do not obtain clothing or personal effects after
the alarm has sounded;
3. The individuals and staff members proceed to a
predetermined point outside the building that is sufficiently
remote to avoid fire danger, or to a predetermined point inside
of the building; and
4. Individuals and staff members remain in place until a
recall is issued or until they are dismissed.
5. Exception. If there is potential harm to individuals
during drills because a resident is medically fragile, the
provider may arrange the drill to not involve the medically
fragile. However, all individuals who are medically fragile
must participate in a drill at least once per year. This must be
documented in the home.
(E) No window in a facility shall have bars or any other item
placed over them in a stationary manner that would impede a
rescue or evacuation.
(F) All flammable/combustible liquids, matches, toxic
cleaning supplies, poisonous materials, or other hazardous
items shall be stored so as to be inaccessible to the occupants
if the occupants cannot handle the materials safely. If there
are firearms and/or ammunition on the premises, they shall be
kept in a locked space without access by individuals.
(G) Clothes dryers shall be vented to the outside and
maintained per the manufacturer’s instructions.
(H) The house numbers shall be plainly visible from the street
in case of emergency, at least four inches (4") in height and
contrasting color with the building.
(I) Good housekeeping practices ensuring fire safety will be
maintained daily.
(J) Stairways, walks, ramps, and porches shall be kept free of
ice and snow.
(K) Fresh-cut Christmas trees shall not be used unless they
are treated with a flame resistant material and documentation
of the treatment is on file at the facility and available for review
by the Division of Fire Safety.
(L) Candles and other devices that have an open flame shall
not be used indoors. However, short-term supervised use of
candles for special occasions or dinners is permitted.
(M) The facility may use a cellular phone when all of the
following conditions are met:
1. The phone must always have a signal;
2. The phone must always be charged;
3. The phone must be able to make and receive normal
calls;
4. The phone must remain at the facility at all times; and
5. The emergency plan for the facility must address the use
of cellular phones.
(N) The facility shall notify the nearest fire department that
the facility is in operation and have required documentation
completed and signed by the local fire authority (fire
department notification form) on file at the facility and
available for review by the Division of Fire Safety inspector.
(O) Facilities served by a volunteer or membership fire
department shall be a member in good standing with the
fire department. A copy of the membership or receipt for
membership shall be on file at the facility and available for
review.
(P) The facility shall, as soon as possible, no later than the
following business day, report any fire in the facility to the
Division of Fire Safety office and the Department of Mental
Health.
(Q) The Division of Fire Safety may make additional
requirements that provide adequate life safety protection if it
is determined that the safety of the occupants is endangered.
Every building or structure shall be constructed, arranged,
equipped, maintained, and operated to avoid danger to the
lives and safety of its occupants from fire, smoke, fumes, or
resulting panic during the period of time necessary for escape
from the building.
(R) Prior to new construction, remodeling existing structures,
and any structural alterations to existing facilities, the provider
shall submit two (2) copies of plans and specifications prepared
to scale for review and approval. One (1) copy shall be
submitted to the Department of Mental Health’s Licensure
and Certification Unit; the second copy to the Division of
Fire Safety. The plans shall include a narrative indicating
the utilization of each area of the facility. The architect
or contractor shall certify in writing that the plans are in
compliance with these certification rules. The provider shall
not begin construction until the plans have been reviewed
and approved by the Division of Fire Safety. All plans for new
construction, remodeling, or additions shall comply with the
Americans with Disabilities Act, Accessibility Guidelines.
(S) During the construction or remodeling process, the
provider shall request a framing and wiring inspection and
an inspection for the rough-in wiring for the fire alarm system
by the Division of Fire Safety before the walls are enclosed.
Failure to have these inspections conducted will result in an
unapproved fire inspection from the Division of Fire Safety.
(T) The ceiling height in all facilities shall be a minimum of
seven feet six inches (7'6"). An allowance will be made by the
Division of Fire Safety for some areas that are below seven feet
six inches (7'6") for the installation of ductwork and plumbing.
No more than forty percent (40%) of the ceiling in each room
shall be below minimal height, with no portion of the ceiling
less than six feet eight inches (6' 8").
(U) Facilities shall comply with all local building codes, fire
codes, and ordinances.
(V) The latest edition of the National Fire Protection
Association (NFPA), Chapter 101, Life Safety Code prevails in the
interpretation of these rules.
(W) Each residential facility shall be inspected at least once
annually by a Division of Fire Safety inspector. The department
will initiate the fire safety inspection. If a facility is found out
of compliance with the fire safety rules, the department will
apply procedures for achieving compliance as promulgated
under 9 CSR 45-5.060.
(2) Means of Egress Requirements.
(A) Each floor occupied in the home shall have not less than
two (2) remotely located means of egress. Required means of
egress shall not be a window. Each exit door shall not be less
than thirty-six inches (36") wide.
(B) Individual sleeping rooms in all new group homes
certified after the effective date of this rule shall have two (2)
means of egress, or a primary means of egress and a means of
escape.
(C) Wheelchairs, walkers, and other support equipment shall
not be stored in corridors.
(D) No door in the path of travel to the means of egress shall
be less than thirty-six inches (36") wide.
(E) No primary means of escape shall lead through a
bathroom, storage room, furnace room, kitchen, garage, or any
other room deemed hazardous by the Division of Fire Safety
inspector.
(F) All exit doors shall swing in the direction of egress travel
and shall have door closures attached.
(G) Emergency lighting that has a battery backup shall be
installed to light the path of egress. The location and number
of emergency lights shall be determined by the Division of Fire
Safety inspector. Emergency lights shall be tested monthly and
documentation indicating which lights were tested, the date
tested, and the name of the person performing the test kept for
review by the Division of Fire Safety.
(H) Lighted exit signs with a battery backup shall be installed
above exit doors and as needed throughout the facility to
direct the occupants to the exits.
(I) No locks that require a key or special knowledge to unlock
the lock from the inside shall be allowed. Delayed egress locks
complying with section 7.2.1.6.1 of the 2012 edition NFPA 101 are
permitted, provided that no more than one (1) such device is
located in any egress path.
(J) Overhead garage doors are not recognized as exit
doorways.
(K) Mirrors shall not be placed on exit doors or adjacent to
any exit in such a manner to confuse the direction of the exit.
All exit doors shall be readily recognizable.
(L) All hallways shall have a clear width of at least thirty-six
inches (36") wide and shall be kept free of all articles that might
impede the occupants’ evacuation from the home.
(M) Dead-end corridors/hallways shall not exceed twenty
feet (20').
(N) Each wing or corridor of the facility shall be separated
into fire compartment areas by fire doors and walls, having not
less than a one- (1-) hour rating. All fire doors shall be equipped
with a door closure and may be held open at all times with an
electrical magnetic switch that is interconnected to the fire
alarm system.
(O) Facilities initially certified and areas initially approved on
or after the effective date of this rule, shall meet the following
requirements. All facilities that have a set of stairs, or use stairs
as a fire escape shall be constructed as follows:
1. All stairs shall be at least thirty-six inches (36") wide.
Fire escapes shall be constructed of noncombustible materials.
Existing fire escapes shall be of sturdy construction and, at the
discretion of the Division of Fire Safety, may be required to be
load tested;
2. A maximum rise of eight inches (8");
3. A minimum tread of nine inches (9");
4. A maximum height between landings of twelve feet
(12');
5. A minimum landing size of forty-four inches (44");
6. Handrails placed on both sides of sturdy construction
and positioned thirty-four to thirty-eight inches (34"–38")
above the tread;
7. An outside diameter of the handrails of at least one and
one-fourth inches (1 1/4") and no greater than two inches (2")
in size;
8. Handrails with a clearance of at least one and one-half
inches (1 1/2") between the handrail and the wall or upright to
which it is attached;
9. Spiral staircase or winder is not permitted.
(P) Every ramp used in the component of the means of egress
shall be a minimum of forty-four inches (44") wide, and have
landings at the top and bottom being the same width as the
ramp. Ramp height shall comply with the following:
1. Ramps less than three inches (3") in height have a slope
of one inch (1") per eight inches (8") of run;
2. Ramps with a height of three to six inches (3"–6") have a
slope of one inch (1") per ten inches (10") of run;
3. Ramps with a height greater than six inches (6") have a
slope of one inch (1") per twelve inches (12") of run.
(Q) All ramps shall have a slip-resistant surface and be
designed so that water or snow does not accumulate on their
surface.
(R) All ramps over ten inches (10") in height shall have
guardrails and handrails on both sides.
(3) Travel Distance to Exits.
(A) The travel distance between any room door intended
as an exit access or an exit shall not exceed one hundred feet
(100').
(B) The travel distance between any point in a room and an
exit shall not exceed one hundred fifty feet (150').
(C) At the discretion of the Division of Fire Safety inspector
and in consideration of the presence of an automated sprinkler
system, the distances in subsections (A) and (B) of this section
may be extended by fifty feet (50').
(4) Protection.
(A) Vertical openings shall be protected so that no primary
means of egress is exposed to an unprotected vertical opening.
The vertical opening shall be considered protected if the
opening is cut off and enclosed in a manner that provides
a fire-resisting capability of not less than one- (1-) hour and
resists the passage of smoke. Any doors or openings shall have
fire- and smoke-resisting capability equivalent to that of the
enclosure and shall be self-closing or automatic closing.
(B) Exception. Specific residential facilities that were certified
prior to the effective date of this rule with twenty- (20-) minute
fire barriers shall be considered in compliance with current
requirements, unless renovations or significant changes have
occurred in the way the building is being used or the number
of residents is increased.
(C) Interior stairways shall be closed with one- (1-) hour fire
barriers, with all openings equipped with smoke-actuated
automatic-closing or self-closing doors having a fire resistance
comparable to that required for the enclosure.
(D) All furnace rooms, rooms containing water heaters,
boiler rooms, storage rooms, laundry rooms, and all other
rooms or areas deemed hazardous by the Division of Fire
Safety inspector shall be separated from the remainder of the
building by construction having not less than a one- (1-) hour
fire resistance rating. All doors to these rooms shall have a selfclosing device attached and shall have a minimum one- (1-)
hour fire rating.
(E) All doors to sleeping rooms shall have a fire resistance
rating of twenty (20) minutes.
(F) All buildings shall be protected throughout by an
approved, automatic sprinkler system installed and maintained
in accordance with the National Fire Protection Association,
Standards for Installation of Sprinkler Systems. Quick response
or residential sprinkler heads shall be installed throughout the
structure.
(G) The sprinkler system shall initiate the fire alarm system
upon activation of water flow.
(H) Tamper switches shall be installed on the sprinkler
system valves and shall transmit a supervisory signal to the fire
alarm control panel.
(I) All facilities shall have the sprinkler system tested,
inspected, and approved annually by a fire sprinkler company.
A copy of the test report and approval of the system shall be
kept on file at the facility for review by the Division of Fire
Safety inspector.
(5) Interior Finish.
(A) Interior wall and ceiling finishes throughout shall be a
minimum Class B finish, as specified in the definition section
of these fire safety rules. Textile material having a napped,
tufted, looped, woven, non-woven, or similar surface shall not
be applied to walls or ceilings. Foam plastic materials or other
highly flammable or toxic materials shall not be used as an
interior wall, ceiling, or floor finish.
(B) All wall studs, ceiling joists, and floor joists shall be
covered with a minimum of Class B finish, and no exposed
studs or joists shall be allowed.
(C) Hangings or draperies shall not be placed over exit doors
or be located to conceal or obscure any exit. All other hangings
and draperies shall be treated with a flame retardant material
with verification to this effect on file for the Division of Fire
Safety inspector to review. Exception shall be made for small
window valances. These exceptions shall be noted on the fire
inspection survey.
(6) Detection, Alarms, Extinguishment.
(A) All facilities shall have a full coverage electrical fire alarm
system. Pull stations shall be mounted at each exit door. Horns
and strobe lights connected to the fire alarm shall be installed
throughout the facility. Smoke detectors shall be installed
in all sleeping rooms, throughout all corridors, in all living
spaces, storage rooms, and offices. Additional smoke detectors
may be required by the Division of Fire Safety as deemed
necessary. Heat detectors shall be installed in all mechanical
rooms, kitchens, and throughout the attic. The battery backup
control panel shall be Underwriters Laboratories, Inc. (UL) or
Factory Mutual (F.M.) listed and installed on a dedicated circuit
in the breaker box. The fire alarm system shall be installed and
maintained in good working order and should be Underwriters
Laboratories, Inc. (UL) or Factory Mutual (F.M.) listed. The fire
system shall be installed and maintained per the National Fire
Alarm Code (NFPA 72) and the National Electrical Code.
(B) All smoke detectors that are ten (10) years old or older
shall be replaced with new smoke detectors of the same style.
The new smoke detectors shall have the installation date
written on the side of the detector for the Division of Fire Safety
to reference.
(C) All smoke detectors that are connected to a fire alarm
system shall be replaced after ten (10) years of service, or
recalibrated by the smoke detector’s manufacturer. If the
smoke detectors are recalibrated, temporary smoke detectors
shall be installed so that the fire alarm system continues
working properly and providing protection to the occupants
while the original smoke detectors are being serviced.
(D) Any facility that has hearing-impaired occupants shall
make adequate provisions so that the activation of any fire
alarm system shall notify the occupants of the home. The
Division of Fire Safety inspector may require additional
requirements for the hearing-impaired occupants to insure
adequate notification.
(E) Occupant notification shall be provided automatically
without delay. Pre-signal systems shall be prohibited.
(F) All facilities shall have the fire alarm system tested,
inspected, and approved annually by a fire alarm company and
a copy of the test report and approval of the system kept on file
at the facility for review by the Division of Fire Safety inspector.
(G) Facilities using any equipment or appliances using wood
or fossil fuel, and that pose a potential carbon monoxide
risk, including facilities with attached garages, shall install a
carbon monoxide detector(s). The detector(s) shall be installed
according to the manufacturer’s instructions. The Division of
Fire Safety inspector may require additional carbon monoxide
detectors if the Division of Fire Safety inspector determines
that the safety of the occupants is endangered.
1. Carbon monoxide detectors shall be in good operating
condition. If a battery-operated detector is not operational, the
facility shall install a detector that is powered by the home’s
electrical system with a battery backup.
2. If an elevated carbon monoxide level is detected during
a fire inspection, the facility shall have all gas-fired appliances
checked by a heating and air conditioning company to identify
the source of the carbon monoxide. Until the facility has
documentation on file at the home verifying that all gas-fired
appliances were checked by a heating and air conditioning
company and are in safe working order, and the facility is
determined safe by the Division of Fire Safety inspector, the fire
inspection shall not be approved.
3. If a level of carbon monoxide is determined that
endangers the lives of the occupants, the Division of Fire
Safety inspector shall take measures necessary to protect
the occupants. This may include evacuation of the building
or closing the facility. The facility shall obtain and have on
file at the facility, documentation verifying that all gas-fired
appliances were checked by a heating and air conditioning
company and are in safe working order. The facility shall be
reinspected by the fire inspector and determined safe before
the occupants can return to the building or the facility can
reopen.
(H) At least one (1) portable (five pound (5 lb)) 2A-10B:C
fire extinguisher shall be required in all facilities. One (1)
fire extinguisher shall be located in the kitchen. Additional
fire extinguishers shall be placed throughout the facility,
with a travel distance no greater than seventy-five feet (75')
between fire extinguishers. Additional fire extinguishers may
be required by the Division of Fire Safety inspector depending
on the floor plan arrangement of space and the number of
levels used.
(I) Fire extinguishers shall be installed and maintained
according to the instructions of the Division of Fire Safety
inspector and inspected and approved annually by a fire
extinguisher company. Documentation of the inspection and
approval shall be on file at the facility and available for review
by the Division of Fire Safety inspector.
(J) Facilities using a commercial stove, deep fryer, or two (2)
home type ranges placed side by side, or a home type range
that produces a grease laden vapor shall be equipped with
a range hood and extinguishing system with an automatic
cutoff of the fuel supply and exhaust system in case of fire. The
Division of Fire Safety inspector shall inspect these systems
to insure they are in good working condition and installed/
maintained correctly. The Division of Fire Safety inspector shall
base this inspection on the National Fire Protection Association,
Chapter 96, Standard for Fire Protection of Commercial Cooking
Operations.
(K) The range hood fire extinguishment system shall be
connected to the control panel of the fire alarm system. The
activation of the range hood fire extinguishment system
shall cause the fire alarm system to activate throughout the
building.
(7) Heating, Ventilating, Air Conditioning, and Mechanical
Equipment.
(A) Unvented fuel-fired room heaters, portable electric space
heaters and floor furnaces shall not be permitted for use.
(B) No facility shall be allowed to heat the home with a wood
burning stove, fireplace, or wood burning furnace located
inside of the structure as a primary source of heat.
(C) All gas and electric heating equipment shall be equipped
with thermostatic controls. All water heaters, if gas fired, shall
have the exhaust properly vented with galvanized pipe with
screws at all joints or with a material recommended by the
manufacturer. All water heaters shall have a properly sized
pressure relief valve installed with a drip leg. The drip leg
pipe on the pressure relief valve shall extend to approximately
six inches (6") above the floor and shall be of rigid material
such as copper or black iron pipe. Chlorinated polyvinyl
chloride (CPVC) or PVC pipe can only be used if manufactured
specifically for use on drip legs. No drip leg may be reduced in
size from the opening of the temperature and pressure valve.
(D) Facilities with a water heater two hundred thousand
British thermal units (200,000 Btus) per hour input or larger,
or that is heating with a boiler, shall have a valid permit from
the Division of Fire Safety posted on the premises. A copy of the
permit shall be kept on file at the Division of Fire Safety.
(E) All furnace rooms shall be properly vented. Furnace
flue pipes shall be constructed of galvanized pipe or material
recommended by the manufacturer. All galvanized pipe shall
be secured by screws at every joint in the pipe.
(F) All joints in the gas supply pipe shall be located outside of
the furnace cabinet housing.
(G) A gas shutoff valve shall be located next to all gas
appliances, furnaces, and hot water heaters.
(H) All furnaces shall be equipped with an electrical fused
switch to protect the unit from electrical overloading and to
disconnect the electrical supply.
(I) If a furnace or water heater is located inside a garage, the
burner or ignition source shall be at least eighteen inches (18")
above the finished floor and enclosed inside a fire resistant
room as described in subsection (4)(C) of this rule having a fire
rating of thirty (30) minutes. The door to this room shall also
have a minimum thirty (30) minute fire rating and have a door
closure attached. Open penetrations, including combustion
air or return air vents, shall not be allowed to penetrate these
enclosures or doors. Louvers that close on activation of the fire
alarm or smoke detectors are allowed.
(J) All furnace rooms and rooms containing the gas water
heater shall have adequate combustion air for the units. The
vent size opening for the combustion air shall be measured
at one (1) square inch per one thousand (1,000) Btus input if
the combustion air is drawn from inside the structure and
one (1) square inch per four thousand (4,000) Btus input if the
air is drawn from outside of the structure. There shall be two
(2) combustion air vent openings in each furnace room, one
(1) located at the lower level and the other at the upper level.
Combustion air or return air vents shall not penetrate the rated
or smoke enclosure.
(K) One (1) combustion air vent opening shall be permitted
if the vent opening communicates directly to the outside of
the structure. This opening shall be one (1) square inch per
three thousand (3,000) Btus input of the total gas appliances
located in this room. The gas appliances must be installed per
the manufacturer’s instructions with proper clearance or have
a minimum clearance of one inch (1") from the sides and back,
and six inches (6") from the front of the unit.
(L) Air conditioning, heating, ventilating ductwork, and
related equipment shall be installed in a safe manner and be
in good operating condition as determined by the Division of
Fire Safety inspector.
(M) Any furnace or air handling equipment that has airflow
of two thousand (2,000) cubic feet per minute or more, shall
have a fan shutdown switch that is interconnected with the
fire alarm system.
(N) All elevators shall be inspected bi-annually by a state
licensed elevator inspector and shall obtain an annual state
operating permit form from the Division of Fire Safety and post
it as required.
(O) If any combustibles are stored in a furnace room, they
must be enclosed in a metal container.
(8) Electrical Services.
(A) Electrical wiring shall be installed and maintained in
good working order. If the Division of Fire Safety considers
the wiring to be unsafe for the occupants or if it is installed
improperly, an inspection by a licensed electrician may be
required prior to fire safety approval. The inspection by
the licensed electrician shall be based on the National Fire
Protection Association, Chapter 70, National Electrical Code.
(B) No electrical extension cords will be allowed, unless
approved in writing by the Division of Fire Safety. Extension
cords shall not be permanently affixed to the structure or
replace permanent wiring. Exception: The use of UL approved
fused power surge strips is acceptable.
(9) Equivalency Concepts. Nothing in this rule is intended to
prevent the use of systems, methods, or devices of equivalent
or superior quality, strength, fire resistance, effectiveness,
durability, and safety as alternatives required by this rule. These
alternatives may be used only if technical documentation to
demonstrate equivalency and the system, method, or device is
submitted and approved by the Missouri Division of Fire Safety.
AUTHORITY: section 630.655, RSMo 2016.* Original rule filed Sept.
5, 2003, effective April 30, 2004. Amended: Filed March 20, 2018,
effective Nov. 30, 2018.
*Original authority: 630.655, RSMo 1980.