10 CSR 23-5.080
Plugging of Heat Pump Wells
PURPOSE: This rule sets standards on the proper plugging of wells
used in heat pump applications.
(1) Vertical Closed-Loop Heat Pump Wells. To plug a properly
constructed vertical closed-loop heat pump well the following
specifications must be met:
(A) Remove all heat transfer fluid from the closed-loop and
take necessary precautions to ensure groundwater protection;
and
(B) Dig down to the top of borehole and cut off the loop pipe
at least three feet (3') below the surface. Pump the remaining
loop full of bentonite or cement slurry. Allow the grout to fill
the upper one foot (1') of borehole. Fill remaining hole with
compacted earth or pavement.
(2) Open-Loop Heat Pump Wells. Wells used to supply water for
heat pump and water return wells must be plugged pursuant
to 10 CSR 23-3.110.
AUTHORITY: sections 256.606, 256.623, and 256.626, RSMo 2016.*
Emergency rule filed Nov. 16, 1993, effective Dec. 11, 1993, expired
April 9, 1994. Original rule filed Aug. 17, 1993, effective March
10, 1994. Amended: Filed May 17, 2013, effective Dec. 30, 2013.
Amended: Filed June 27, 2018, effective Feb. 28, 2019.
*Original authority: 256.606, RSMo 1991; 256.623, RSMo 1985, amended 1991; and
256.626, RSMo 1985, amended 1991.