10 CSR 26-2.060
Taking USTs Out of Use
PURPOSE: This rule contains the requirements for underground storage tanks that are
taken out of service.
(1) When an underground storage tank (UST)
system is out of use, as defined in 10 CSR 262.012, the owner and/or operator must continue operation and maintenance of corrosion
protection, as described in 10 CSR 26-2.031,
and/or interior lining inspection and maintenance, as described in 10 CSR 26-2.021,
until the site assessment described in 10 CSR
26-2.062 of this rule has been completed.
Release reporting, investigation, and corrective action, as described in 10 CSR 262.050–10 CSR 26-2.083, must be performed
if a release is suspected or confirmed.
(2) Owners and operators must also comply
with the following requirements when a UST
system is out of use for three (3) months or
more:
(A) Leave vent lines open and functioning;
and
(B) Cap and secure all other lines, pumps,
manways, and ancillary equipment.
(3) For a UST that remains out of use, within
twelve (12) months of taking the UST system
out of use, owners and operators must
either—
(A) Permanently close the UST system in
accordance with 10 CSR 26-2.061–10 CSR
26-2.064; or
(B) Complete a site assessment in accordance with 10 CSR 26-2.062.
(4) Within five (5) years of the date on which
the UST was initially taken out of use, the
owner or operator must permanently close
the UST system, as described in 10 CSR 262.061–10 CSR 26-2.064.
(5) To re-open a steel tank system that has
been out of use for more than twelve (12)
months, the tank owner or operator must—
(A) Complete one (1) of the following
three (3) options:
1. Ensure that the steel tank is structurally sound, using an integrity test, as
defined in 10 CSR 26-2.021, and—
A. If cathodically protected, the
owner or operator must recertify the cathodic
protection system in accordance with the
requirements described in 10 CSR 26-2.031;
or
B. If the tank was internally lined,
the owner or operator must ensure that the
lining is still functioning as designed and is in
compliance with 10 CSR 26-2.021(3)(A);
2. Document that the tank has remained
in compliance with the cathodic protection
requirements described in 10 CSR 26-2.031;
or
3. Document that the tank has remained
in compliance with the interior lining requirements described in 10 CSR 26-2.021(3)(A);
(B) Conduct line tightness testing and get a
passing result; and
(C) Ensure that all ancillary equipment is
tested for proper operation.
(6) To re-open a fiberglass-reinforced plastic
tank system that has been out of use for more
than twelve (12) months, the tank owner or
operator must—
(A) Have the tank and piping recertified by
the manufacturer(s); or
(B) Provide tank deflection readings, confirming that these readings are within the
manufacturer’s allowable range; and
(C) Conduct line tightness testing and get a
passing result; and
(D) Ensure that all ancillary equipment is
tested for proper operation.
(7) To re-open a clad steel tank system that
has been out of use for more than twelve (12)
months, the tank owner or operator must—
(A) Have the tank and piping recertified by
the manufacturer(s); or
(B) Conduct line and tank tightness testing
and get a passing result; and
(C) Ensure that all ancillary equipment is
tested for proper operation.
(8) The department may grant an owner or
operator a twelve (12)-month extension to
meet the site assessment requirement in section (3) of this rule. The department will consider at least the following criteria when
reviewing a request for an extension:
(A) The UST had been in use no more than
ten (10) years;
(B) Other USTs remain in use at the site;
(C) The owner or operator demonstrates
that his or her financial responsibility mechanism allows additional time in which to
report a release from the out-of-use UST and
file a claim for that release; and
(D) There is no evidence of a suspected or
confirmed release.
(9) Owners and/or operators must notify the
department within thirty (30) days of any
change in use of the tank (including taking
the tank out of use or re-opening the tank).
AUTHORITY: sections 319.105, 319.107 and
319.111, RSMo 2000, and section 319.137,
RSMo Supp. 2010.* This rule originally filed
as 10 CSR 20-10.070. Original rule filed
April 2, 1990, effective Sept. 28, 1990.
Moved and amended: Filed April 15, 2011,
effective Dec. 30, 2011.
*Original authority: 319.105, RSMo 1989; 319.107, RSMo
1989, amended 1994; 319.111, RSMo 1989; and 319.137,
RSMo 1989, amended 1993, 1995, 2004.