19 CSR 30-22.010
General Design and Construction Standards for Rehabilitation Hospitals
PURPOSE: The Department of Health, Division of Health Resources has the authority to
establish construction standards for rehabilitation hospitals. This rule provides standards
for facilities to ensure functional, sanitary
and fire-safe facilities.
PUBLISHERS NOTE: The publication of the
full text of the material that the adopting
agency has incorporated by reference in this
rule would be unduly cumbersome or expensive. Therefore, the full text of that material
will be made available to any interested person at both the Office of the Secretary of State
and the office of the adopting agency, pursuant to section 536.031.4, RSMo. Such
material will be provided at the cost established by state law.
(1) All new rehabilitation hospitals and additions to and remodeling of existing licensed
rehabilitation hospitals shall be designed to
provide all of the facilities required by these
rules and fire safety standards, arranged to
accommodate with maximum convenience all
of the functions required by these rules and
arranged to provide comfortable, attractive,
sanitary, fire-safe, secure and durable facilities for the patients. Any additions or alterations to a rehabilitation hospital shall comply with these rules and shall provide all
required facilities proportional to the number
of beds. These rules are applicable to rehabilitation hospitals which began operation or
one which began operation or one which
began construction or renovation of a building for the purpose of operating a rehabilitation hospital on any date after November 21,
1969.
(A)
General
Construction—Related
Authorities.
1. Construction of all rehabilitation hospitals and additions to or remodeling of rehabilitation hospitals shall comply with all local
and state regulations and codes. Facilities and
equipment shall comply with the American
Standards Association Specification A 117.11961 (R-1971) entitled “American Standard
Specifications for Making Buildings and
Facilities Accessible to, and Usable by, the
Physically Handicapped”.
(B) Planning and Construction Procedure.
1. Plans and specifications shall be prepared for the construction of all rehabilitation
hospitals and additions to and remodeling of
rehabilitation hospitals. The plans and specifications shall be prepared by an architect or
a professional engineer licensed to practice in
Missouri.
2. Construction shall be undertaken only
after the plans and specifications have
received the written approval of the Department of Health and the construction shall be
in conformance with the approved plans and
specifications. The Department of Health
shall be notified within five (5) days after
construction begins. If construction of the
project is not started within one (1) year after
the date of approval of the plans and specifications, the plans and specifications shall be
resubmitted to the Department of Health for
its approval and shall be amended, if necessary, to comply with the then current rules
before construction work commences.
A. Preliminary Plans and Sketches.
(I) When construction is contemplated, either for new buildings, additions to
existing buildings or material alterations to
existing buildings, the preliminary plans or
sketches shall be submitted in duplicate to the
Department of Health for review and
approval before the preparation of working
drawings is undertaken. The preliminary
plans may be reviewed by the Department of
Health in schematic form, but before they are
declared acceptable for procedure with working drawings and specifications, they should
also include the following information, stated
briefly and not in detailed form required in
working drawings and specifications: site
plan showing scale, orientation, street names,
topography, walks, drives, parking areas and
utilities, including fire plug location; plans
and elevations of the buildings at a scale of
not less than one-eighth inch to one foot
(1/8"-1'); rooms and corridors, designated by
name and number; windows, note wired glass
where it is required; doors, including door
swings; identify fire doors by time rating and
Underwriters’ Laboratories label; plumbing
fixtures; show fixtures in proper shape and
scale for positive recognition; identify special
types such as service sinks and clinic sinks;
brief descriptive notes on type of supplies,
vacuum breakers, and the like are advisable;
plans of patient rooms shall indicate principle
items of furniture accurately scaled; all other
principle items of equipment such as boiler(s), chiller(s), cooling tower(s), electrical
substation(s), tank(s), air handler(s), fan-coil
unit(s), kitchen equipment, laundry equipment, cabinet(s), counter(s) and any other
item(s) which take up space and affect the
final layout; fire- and smoke-barrier partition
designations; floor lines, top ceiling line and
grade lines, designated and preferably dimensioned and with basic elevations shown; ceiling height; only one (1) typical room of a
group need be so shown; area of each room
for which the rules establish a minimum area;
only one (1) typical room of a group need be
so noted; and brief noted descriptions of the
general construction and finish, the structural
system, the heating, ventilating and air-conditioning system, including the fuel supply,
the plumbing system, including the water
supply and sewage disposal and the electrical
system.
(II) In the case of a project which is
an addition to an existing building, it will be
necessary to give the Department of Health
sufficient information about the existing
building on which to base a determination of
acceptability of the plans for the addition.
This information shall cover all items
required to be provided in a rehabilitation
hospital by the rules of the Department of
Health and shall be submitted in such form as
required by the Department of Health for the
particular project.
B. Working Drawings and Specifications.
(I) Working drawings and specifications, complete in all respects, shall be submitted in duplicate covering all phases of the
construction project including: site preparation; paving; general construction; mechanical work, including plumbing, heating, ventilating and air conditioning; electrical work;
and all built-in equipment, including elevators, kitchen equipment, cabinet work, and
the like; each sheet of the plans and each set
of the specifications shall identify the project
by name and location and shall bear the
names and addresses of the architect or professional engineer and the owner; each sheet
of the plans and each set of specifications
shall bear the official seal and signature of the
registered architect or registered professional
engineer who prepared it; each sheet of the
plans and each set of specifications shall bear
the date of its completion or its latest revision; and the plans shall be on sheets of the
same size, securely bound into complete sets,
with the sheets in the proper order; and the
specifications shall be securely bound into
complete sets.
(II) The plans and specifications
are to include a survey and soil investigation
of the proposed site. The following information shall be provided: items previously listed
under subparagraph (1)(B)2.A. Preliminary
Plans and Sketches; courses and distances of
property lines; dimensions and locations of
any buildings, structures, easements, rightsof-way or encroachments on the site; details
of party walls or walls and foundations adjacent to lot lines; the position of trees, dimensions, position and elevation of all cellars,
evacuations, wells, backfilled areas and the
elevation of any water; detailed information
by the city engineer or other official report as
to established curbs, building lines, streets,
alleys and sidewalks; all utilities including
size, characteristics and location of these services; piping, mains, sewers, poles, wires,
hydrants and manholes upon, over or under
this or the adjacent site; complete information as to the disposal of sanitary, storm water
and subsoil drainage; official date upon
which elevations are based and benchmark
established on or adjacent to the site; contours on elevations at two foot (2') intervals
over site and elevations at the bottom of excavation; contemplated date and description of
proposed improvements to approaches or utilities adjacent to the site; thickness, consistency, character and estimated safe bearing value
of various strata encountered; amount and
elevation of groundwater encountered in each
test pit; elevation of rock, if known and probability of encountering quicksand; average
depth of frost effect below ground; high and
low water levels of nearby bodies of water
affecting groundwater level; whether the soil
contains alkali in sufficient quantities to
effect the concrete; elevation and location of
mine shafts or excavations if the site is underlaid with mines or old workings; and whether
the site is subject to mineral rights which
have not been developed.
(C) Site.
1. The facility shall be located reasonably accessible to the center of population of
the community served, close to where competent medical and professional consultation
is readily available and where employees can
be recruited and retained.
2. The site shall be away from nuisances
detrimental to the proposed project’s program.
3. Adequate vehicular and pedestrian
access shall be provided within the lot lines to
the main entrance, ambulance entrance, community activities and services including loading and unloading space for delivery trucks.
Roads, walks, ramps and entrances, etc., are
to comply with the “American Standards
Associations Specification” A 117.1-1961
(R-1971), entitled “American Standard Specifications for Making Buildings and Facilities
Accessible to, and Usable by, the Physically
Handicapped.”
4. Adequate off-street parking shall be
provided.
(D) General Construction—Structural
Requirements.
1. All new rehabilitation hospitals and
additions to and remodeling of existing rehabilitation hospitals shall be of sufficient structural strength to resist all stresses imposed by
dead loads, live loads and lateral or uplift
forces, such as wind, without exceeding, in
any of the structural materials, the allowable
working stresses established for these materials by generally accepted good engineering
practice.
2. Compliance with the Basic Building
Codes of the Building Officials Conference of
America (BOCA Code) insofar as it may
apply, shall be deemed to be in compliance
with this rule.
(E) General Design—Facilities.
1. Rehabilitation hospitals shall provide
the following facilities:
A. Administrative area. Business
office with information counter, telephone,
switchboard and cashier’s window; administrator’s office; director of nurse’s office;
medical records room; medical library; lobby
and waiting room; public telephone booth;
public toilets and personnel toilets;
B. Evaluation and treatment facilities.
Clinical laboratory; radiology and radiographic room adjoining dark room, toilet and
office; pharmacy, drug room with minimum
facilities for compounding; conference room;
offices, examination rooms and work space
for medical personnel; office and work space
for provision of appropriate dental treatment;
office and work space for physical therapy
staff; rehabilitation gymnasium; hydrotherapy area; electro-diagnosis area; thermotherapy and massage area; storage for physical
therapy supplies and equipment; office and
work space for occupational therapy staff;
occupational therapy area; storage space for
occupational therapy supplies and equipment;
facilities for teaching activities of daily living; artificial appliance facilities; space for
fitting and adjustment service; office and
work space for psychological testing, evaluation and counseling; office space for private
interview and counseling; office and work
space for counseling, evaluation, pre-vocational programs and placement; schoolroom
for children if children are included in program; locker, toilet for outpatients; and clean
and soiled linen facilities;
C. Nursing unit for adults. This unit
shall be located convenient to the treatment
area; each patient’s rooms shall have a lavatory, mirror, convenience electrical outlet and
wardrobe space; toilet room shall be accessible to each patient room; nursing unit shall
not exceed fifty (50) beds; patients’ room
area shall be at least eighty (80) square feet
per bed in multi-bed patients’ rooms and one
hundred (100) square feet per bed in private
patients’ rooms and a continuous aisle not
less than three feet (3') wide shall be available around the foot and along both sides of
each bed; nurses’ station with medicine
preparation area; nurses’ toilet; clean and
soiled utility rooms; accessible examination
and treatment room with lavatory; floor
pantry with lavatory; recreation area of twenty (20) square feet per bed; a toilet room for
each sex at a ratio of one (1) water closet to
each five (5) beds and one (1) of the water
closet enclosures in each centralized toilet
room shall be at least five feet by six feet (5'
× 6') to permit toilet training unless toilets in
patient rooms are five feet by six feet (5' ×
6'); bedpan cleaning facilities; separate bathroom with tub for each sex; one (1) shower to
each eight (8) beds; stretcher and wheelchair
parking space; clean linen storage; all rooms
occupied by patients shall be outside rooms;
each patient room shall have a minimum window area of not less than one-eighth (1/8) of
the floor area; equipment and supply storage;
janitor’s closet; and one (1) telephone alcove
per floor;
D. Nursing unit for children is the
same as for adults except at least sixty (60)
square feet per bed is to be provided in crib
rooms; and
E. Service departments. Central sterilizing and supply room shall include receiving and clean-up room; clean workroom
including sterilizing facilities and unsterile
supply storage area; dietary facilities shall
include food preparation area with handwashing facilities, food serving facilities for makeup of patient trays, commercial-type dishwashing equipment adequately isolated and
ventilated, lavatory in dishwashing area, three
(3) compartment sinks, refrigerated and
freezer storage, day storage, food cart storage
area, trash and waste disposal facilities, canwashing facilities, staff dining facilities,
patient dining facilities at ratio of twenty (20)
square feet per bed; janitor’s closet with floor
receptor or service sink and space for housekeeping supplies and equipment; lockers and
toilet facilities; housekeeping supply storage
facilities; unless commercial or other laundry
facilities are available, each rehabilitation
facility shall have a laundry of sufficient
capacity to process full seven (7) days’ laundry in a work week and contain a soiled sorting area, processing area, clean linen and
sewing room separate from laundry; mechanical facilities, including boiler and pump
room(s), mechanical room(s), engineers’
space and maintenance shops, at least one (1)
room; female staff and volunteers’ locker
room including lockers and toilet and shower
room; female help locker room, including
lockers and toilet and shower room; male
staff and volunteers’ locker room including
lockers and toilet and shower room; male
help locker room, including toilet and shower room; and twenty (20) square feet of general storage space per bed and to be concentrated in one (1) area.
(I) When no laundry is provided in
the hospital, a soiled linen room and clean
linen and sewing room shall be provided.
(F) General Design—Details.
1. All new rehabilitation hospitals and
additions to and remodeling of existing rehabilitation hospitals shall comply with the following general design details:
A. Required corridors and aisles shall
be at least eight feet (8') wide and no less
than ten feet (10') wide at elevators. No part
of the area of any required corridor or aisle
shall be counted as part of the required area
of any space adjacent to the corridor or aisle.
A continuous system of unobstructed corridors and aisles shall extend through the
enclosed portion of each story of the building, connecting all rooms and spaces with
each other and with all entrances, exitways
and elevators with the following exceptions:
work suites such as the administrative suite
and the dietary area, which are occupied primarily by employed personnel, may have
within them, corridors or aisles as are
deemed advisable; but these are not subject to
the regulations applicable to required corridors or aisles;
B. The width of stairways shall be not
less than three feet eight inches (3' 8"). The
width shall be measured between handrails
where handrails project more than three and
one-half inches (3 1/2");
C. Doors through which residents
will pass, including exit doors, shall be at
least forty-four inches (44") wide except
doors to toilets and bathrooms, which shall
be at least thirty-six inches (36") wide;
D. Exits shall swing outward. Doors
to rooms shall generally swing into the rooms
they serve. Doors to small toilet rooms may
swing outward into the adjacent room and if
they swing inward they shall be equipped for
emergency access. No doors shall swing into
required corridors or aisles except doors to
janitors’ closets, linen closets or doors to
similar small spaces which are open only
temporarily;
E. Ceilings in corridors, storage
rooms, patients’ toilet rooms and other minor
rooms shall not be less than seven feet six
inches (7' 6"). Ceilings in all other rooms
shall not be less than eight feet (8’);
F. Drinking fountains shall be located
in or near the lobby and recreation area and
in each nursing unit corridor. The fountain
shall
be
accessible
to
residents
in
wheelchairs;
G. Toilet room doors shall be
equipped with privacy and release-type hardware;
H. The floors of toilets, baths, bedpan
rooms, floor pantries, utility rooms and janitors’ closets shall have smooth, waterproof
surfaces which are wear-resistant. The floors
of residents’ rooms and corridors shall be
easily cleanable. The floors of kitchens and
food preparation areas shall be waterproof,
greaseproof, smooth, slip-resistant and
durable;
I. The walls of kitchens, utility
rooms, baths, showers, dishwashing rooms,
janitors’ closets and spaces with sinks shall
have waterproof painted, glazed or similar
finishes to a point at least thirty inches (30”)
above the sink or countertop. The remaining
wall surfaces of such rooms and rooms where
food is stored shall have a smooth surface
with painted or equally washable finish in
light color. The base shall be waterproof and
free from spaces which may harbor insects;
J. The ceilings of all kitchens, dishwashing and other rooms where food and
drink are prepared shall have a smooth washable finish;
K. Wall and ceiling surfaces of all
occupied rooms and of all exitways shall be of
such material or so treated as not to have a
flame-spread classification of more than fifty
(50) according to the method for the “Fire
Hazard Classification of Building Materials”
of Underwriters’ Laboratories, Inc. Floor finish shall have a flame-spread rating of not
more than seventy-five (75). Carpeting,
including the backing or underpad, shall have
a flame-spread rating of not more than seventy-five (75);
L. Adequate space, consistent with
the need, shall be provided for residents using
crutches, walkers, wheelchairs, wheel
stretchers, and the like. Accessibility to all
required facilities, including toilets, lavatories, baths, showers, drinking fountains, telephones, furniture, and the like, shall be provided;
M. Showers shall be at least four feet
(4') square. Curbs shall not exceed one inch
(1") in height and shall have sloped edges;
N. Handrails or grab bars shall be
placed in positions to be reached from any
point within a toilet or bathroom area. Grab
bars or handrails shall be provided adjacent
to all bathtubs, within all showers and on
both sides of all water closets.
O. Lavatories for patients’ use shall be
positioned to be accessible to wheelchair
patients and shall not have cabinets underneath or any other unnecessary obstruction to
the maneuverability of wheelchairs;
P. Mirror sizes and positions shall be
such as to make the mirrors convenient both
for residents in wheelchairs and those in a
standing position;
Q. Bathtubs other than therapeutic
tubs are not to be elevated;
R. Paper towel dispensers shall be
provided at all lavatories used for handwashing; and
S. Telephone alcoves shall be a minimum of four (4) feet square. Telephone shall
be located on a shelf convenient for residents
in wheelchairs. Doors to telephone booths are
not recommended.
(G) General Construction—Specifications
and Details.
1. All rehabilitation hospitals and additions to and remodeling of existing rehabilitation hospitals shall be constructed to provide
safe, comfortable, secure, fire-safe, sanitary
and durable facilities for the patients. Existing buildings, if converted to use as rehabilitation hospitals, shall be considered to be new
rehabilitation hospitals and shall comply with
all of the requirements for new rehabilitation
hospitals.
2. The requirements of the Life Safety
Code by the National Fire Protection Association shall be complied with insofar as they
may apply and to the extent they are not
superseded by requirements specifically stated in these rules.
3. Specific requirements.
A. The following elements of the
building shall be constructed to qualify for
fire-resistance ratings not less than the following: one (1)-hour exterior walls of one
(1)-story buildings thirty feet (30') or more
from any other building(s) or from a lot line;
two (2)-hour exterior walls of one (1)-story
buildings less than thirty feet (30') from
another building(s) or from a lot line; two
(2)-hour exterior walls of multi-story buildings; two (2)-hour noncombustible fire walls;
two (2)-hour columns, interior bearing walls
and other structural elements supporting
floor construction; one (1)-hour columns,
interior bearing walls and other structural
elements supporting roof construction only
and in buildings not more than one (1) story
in height, exclusive of the basement; one (1)-
hour for other construction, including nonbearing partitions, curtain walls, and the like.
B. The height and area of each building, or fire section between fire walls, shall
be within the limitations established by the
BOCA Code for buildings of the same occupancy and the next less restrictive type of
construction.
C. Doors between rooms and the
required corridors shall not have louvers or
transoms. Doors shall be one and threefourths inches (1 3/4") solid core wood or
metal doors with equivalent or greater fire
resistance.
D. If linen and refuse chutes are used,
they shall be designed as follows: service
openings to chutes shall have approved class
B, one and one-half (1 1/2)-hour fire doors;
service openings to chutes shall be located in
a room or closet of not less than one (1)-hour
fire-resistive construction and the entrance
door to the room or closet shall be a class C,
three-fourths (3/4)-hour fire door; minimum
diameter of gravity-type chutes shall be two
feet and no inches (2' 0"); chutes shall terminate in or discharge directly into a refuse
room or linen chute room separated from the
incinerator or laundry, the rooms shall be of
not less than two (2)-hour fire-resistive construction and the entrance door shall be class
B, one and one-half (1 1/2)-hour fire door;
chutes shall extend at least four feet (4')
above the roof and shall be covered by a metal
skylight glazed with thin plain glass.
E. Dumbwaiters, conveyors and material handling systems shall not open into any
corridor or exitway but shall open into a
room enclosed by not less than one (1)-hour
fire-resistive construction. The entrance door
to the room shall be a class C, three-fourths
(3/4)-hour fire door.
F. Any penetrations of fire walls other
than doors, such as openings for ducts, shall
be protected by approved automatic protective assemblies with a fire-resistance rating at
least as high as that of the wall.
G. Each floor of a rehabilitation hospital shall have at least two (2) exits remote
from each other and so located that the distance of travel to the exit shall not be more
than one hundred feet (100') from the door to
any room nor one hundred fifty feet (150')
from any point in a room. If the entire building is completely protected by a standard
automatic sprinkler system, these distances
may be increased by fifty feet (50').
H. Every exit shall be so arranged
that no corridor has a pocket or dead end
exceeding thirty feet (30') in which occupants
might be trapped. Distance shall be measured
from the door of the room to the exit.
I. Interior exitways shall be isolated
from the rest of the building by floors, ceilings
and walls with a two (2)-hour fire-resistance
rating as determined by the Underwriters’
Laboratories and shall have one and one-half
(1 1/2)-hour B-label interior fire doors.
J. Horizontal exits are permissible
where located in compliance with subparagraphs (1)(G)3.G. and H. of this rule. A horizontal exit shall be through a fire wall to a
fire-safe area on the same story of the building and shall be subject to all requirements of
other exits except that the door may swing in
either direction. The fire-safe area on either
side of the fire wall shall be sufficiently large
to provide a floor area of at least thirty (30)
square feet per person for all persons who
would normally occupy the space on both
sides of the fire wall. The fire wall shall have
a fire-resistance rating of not less than two (2)
hours and shall extend from floor-to-floor or
roof, from exterior wall to exterior wall, shall
have no doors except the required exit and
shall have no other penetrations except ducts
with automatic fire dampers.
K. Each story of a facility or each
portion of a story between fire walls, which
is in excess of five thousand (5000) square
feet in floor area, shall be subdivided by
smoke-barrier partitions located to provide
floor areas between them of not more than
five thousand (5000) square feet, and located
to provide a total floor area on either side of
each such partition of at least thirty (30)
square feet each for all patients on the entire
floor. Smoke-barrier partitions shall be provided where necessary to separate elevator
lobbies and required aisles from adjoining
required corridors as directed.
L. Smoke-barrier partitions shall have
a fire-resistance rating of not less than one (1)
hour. They shall be continuous from exterior
wall to exterior wall and from the floor to the
floor or roof deck above and shall be penetrated only to the extent allowed by subparagraphs (1)(G)3.P. and Q. of this rule.
M. Doors in smoke-barrier partitions
required by subparagraph (1)(G)3.K. of this
rule shall be located only in main corridors
or in rooms open to the public. They shall be
one and three-fourths inches (1 3/4") thick
solid core wood doors or one and threefourths inches (1 3/4") thick metal doors with
three-fourths (3/4)-hour fire-resistance rating
and if glazed shall be glazed with wired
glass.
N. Any penetrations of smoke-barrier
partitions other than doors, such as openings
for ducts, shall be equipped with automatic
fire dampers.
O. All doors to required exitways and
to the outside at grade level and all vestibule
doors shall swing outward in the direction of
exit travel. They shall be self-closing and
shall be normally closed.
P. All exit doors to required exitways
shall be one and one-half (1 1/2)-hour B-label
doors. All doors in horizontal exits shall be
one and one-half (1 1/2)-hour B-label doors.
All doors in smoke-barrier partitions,
required corridor partitions and one (1)-hour
partitions around hazardous areas shall be
one and three-fourths inches (1 3/4") solid
core wood doors or metal doors with equivalent or greater fire resistance. Doors in two
(2)-hour partitions at boiler rooms, furnace
rooms, incinerator rooms and rooms for similar hazardous occupancy shall be one and
one-half (1 1/2)-hour B-label doors.
Q. Doors in fire separations, horizontal exits and smoke-stop partitions may be
held open only by electric hold-open devices.
If these doors are in main corridors, they
shall be a pair of doors not less than five feet
four inches wide (5'4"). The doors shall
close upon actuation of the fire alarm system
and shall be capable of being opened and
closed manually. In addition, these doors
shall close by at least one (1) of the following
methods: activation of the sprinkler system;
and actuation of a smoke detector.
R. Any door to stairway enclosures or
in walls surrounding hazardous areas shall
not be equipped with hold-open devices.
S. The aggregate width of required
exitways shall be such as to provide twentytwo inch (22") wide exit units at the rate of
one (1) exit unit of stair width for each fifteen
(15) persons served and one (1) exit unit of
width for passageways within the exitways
other than stairs for each thirty (30) persons
served.
(H) Mechanical Requirements.
1. Prior to completion of the contract
and final acceptance of the facility, the architect or engineer shall obtain from the contractor certification that all mechanical systems have been tested and performance of
these systems conform to the requirements of
the plans and specifications. Upon completion of the contract, the contractor shall furnish the owner with a complete set of specifications and as-built drawings and a bound
volume containing operating instructions,
manufacturers’ catalog number(s) and
description and parts list for each piece of
equipment.
2. Incinerators, if provided, shall be gas-
, electric- or oil-fired and shall be capable of,
but need not be limited to, complete destruction of pathological wastes. Design and construction of incinerators and refuse chutes
shall be in accordance with Part III of the
NFPA Standard No. 82. Incinerators shall
conform to current rules of the Air Conservation Commission.
3. Steam and hot water systems.
A. Boilers shall have the capacity,
based upon the published Steel Boiler Institute or Institute of Boiler and Radiator Manufacturers’ Net Ratings, to supply the normal
requirements of all systems and equipment.
The number and arrangement of boilers shall
be such that when one (1) boiler breaks down
or when routine maintenance requires that
one (1) boiler be temporarily taken out-ofservice, the capacity of the remaining boiler(s) shall be no less than seventy percent
(70%) of the total required capacity.
B. Boiler feed pumps, condensate
return pumps, fuel oil pumps and circulating
pumps shall be connected and installed to
provide standby service when any pump
breaks down.
C. Supply and return mains and risers
of space heating and process steam systems
shall be valved to isolate the various sections
of each system. Each piece of equipment
shall be valved at the supply and return end.
D. Boilers, smoke breeching, steam
piping, high pressure steam return piping and
hot water space heating supply and return
piping shall be insulated with insulation having a flame spread rating of twenty-five (25)
or less and a smoke-developed rating of fifty
(50) or less.
4. Air-conditioning, heating and ventilating systems.
A. A minimum temperature of seventy-five degrees Fahrenheit (75°F) shall be
provided for all occupied areas at winter
design conditions.
B. All air-supply and air-exhaust systems shall be mechanically operated. All fans
serving exhaust systems shall be located at or
near the point of discharge from the building.
The ventilation rates shown on Table I shall
be considered as minimum acceptable rates
and shall not be construed as precluding the
use of higher ventilation rates if they are
required to meet design conditions.
C. Outdoor ventilation air intakes,
other than for individual room units, shall be
located as far away as practicable but not less
than twenty-five feet (25') from the exhaust
from any ventilating system or combustion
equipment. The bottom of outdoor intakes
serving central air systems shall be located as
high as possible but not less than eight feet
(8') above the ground level or, if installed
through the roof, three feet (3') above roof
level.
D. The ventilation systems shall be
designed and balanced to provide the general
pressure relationship to adjacent areas shown
in Table I.
E. Room supply air inlets, recirculation and exhaust air registers shall be located
not less than three inches (3") above the
floor. This does not apply to cabinet units.
F. Corridors shall not be used to supply air to or exhaust air from any room,
except that exhaust air from corridors may be
used to ventilate rooms such as bathrooms,
toilet rooms or janitors’ closets which open
directly on corridors.
G. Central systems designed for recirculation of air shall be equipped with a minimum of two (2) filter beds. Filter bed No. 1
shall be located upstream of the conditioning
equipment and shall have a minimum efficiency of thirty percent (30%). Filter bed No.
2 shall be located downstream of the conditioning equipment and shall have a minimum
efficiency of ninety percent (90%).
H. Central systems using one hundred
percent (100%) outdoor air shall be provided
with filters rated at eighty percent (80%) efficiency.
I. The stated filter efficiencies shall
be warranted by the manufacturer and shall
be based on the National Bureau of Standards
Dust Spot Test Method with Atmospheric
Dust.
J. Filter frames shall be durable and
carefully dimensioned and shall provide an
airtight fit with the enclosing ductwork. All
joints between filter segments and the enclosing ductwork shall be gasketed or sealed to
provide a positive seal against air leakage.
K. A manometer shall be installed
across each filter bed serving central air systems.
L. Ducts shall be constructed of iron,
steel, aluminum or other approved materials
such as clay, fiberglass or asbestos cement.
M. Duct interiors or linings shall
meet the Erosion Test Method described in
UL Pub. No. 181. Duct linings, coverings,
vapor barriers and the adhesives used for
applying them shall have a flame-spread classification of not more than twenty-five (25)
and a smoke-developed rating of not more
than fifty (50).
N. Ducts which pass through fire
walls shall be provided with approved automatic fire dampers on both sides of the wall
except that three-eighths inch (3/8") steel
plates may be used in lieu of fire dampers for
openings not exceeding eighteen inches (18")
in diameter. An approved fire damper shall
be provided on each opening through each
fire partition and on each opening through the
walls of a vertical shaft. Ducts which pass
through a required smoke barrier shall be
provided with dampers which are actuated by
products of combustion other than heat.
Access for maintenance shall be provided at
all dampers.
O. Cold air ducts shall be insulated
wherever necessary to maintain the efficiency
of the system or to minimize condensation
problems.
P. The air from dining areas may be
used to ventilate the food preparation areas
only after it has passed through a filter with
eighty percent (80%) efficiency.
Q. Exhaust hoods in food preparation
centers shall have a minimum exhaust rate of
one hundred (100) cubic feet per minute per
square foot of hood face area. All hoods over
cooking ranges shall be equipped with automatic fire extinguishing systems and heatactuated fan controls. Extinguishing systems
shall be provided with steam, dry powder or
carbon dioxide. Cleanout openings shall be
provided every twenty feet (20') in horizontal
exhaust duct systems serving hoods.
R. Boiler rooms shall be provided
with sufficient outdoor air to maintain combustion rates of equipment and reasonable
temperatures in the rooms and in adjoining
areas.
5. Plumbing and other piping systems.
A. The requirements of the current
edition of the National Plumbing Code shall
be complied with insofar as they may apply
and to the extent they are not superceded by
requirements specifically stated in these
rules.
B. The material used for plumbing
fixtures shall be of nonabsorptive material.
C. Lavatories and sinks required in
patient-care areas shall have the water supply
spout mounted so that its discharge point is a
minimum distance of five inches (5") above
the rim of the fixture. All lavatories used by
medical and nursing staff and food handlers
shall be trimmed with valves which can be
operated without the use of hands. Where
blade handles are used for this purpose, they
shall not exceed four and one-half inches (4
1/2") in length, except the handles on clinical
sinks shall not be less than six inches (6")
long.
D. Clinical sinks shall have an integral trap in which the upper portion of a visible trap seal provides a water surface.
E. Water supply systems shall be
designed to supply water to the fixtures and
equipment on the upper floors at a minimum
pressure of fifteen (15) pounds per square
inch during maximum demand periods.
F. Each water service main, branch
main, riser and branch to a group of fixtures
should be valved.
TABLE I
PRESSURE RELATIONSHIPS AND VENTILATION OF CERTAIN HOSPITAL AREAS
All Supply
Minimum Total
Pressure
Changes of
Minimum Air
Exhausted
All Air
Area
Relationship to
Air From
Outdoor Air
Air Changes
Directly
Recirculated
Designation
Adjacent Areas
Outdoors
Per Hour
Per Hour
to Outdoors
Within Room
Intensive care
+
—
2
6
—
No
Patient room
0
—
2
2
—
—
Patient area corridor
0
—
2
4
—
—
Isolation room
0
—
2
6
Yes
No
Isolation anteroom
0
—
2
6
Yes
No
Treatment room
0
—
2
6
—
No
X-ray, fluoroscopy room
–
—
2
6
Yes
No
Physical therapy &
hydrotherapy
–
—
2
6
—
—
Soiled workroom
–
—
2
4
—
No
Clean workroom
+
—
2
4
—
—
Autopsy and darkroom
–
—
2
12
Yes
No
Toilet room
–
—
—
10
Yes
No
Bedpan room
–
—
—
10
Yes
No
Bathroom
–
—
—
10
Yes
No
Janitor’s closet
–
—
—
10
Yes
No
Sterilizer equipment room
–
—
—
10
Yes
No
Linen and trash chute rooms–
—
—
10
Yes
No
Laboratory, general
–
—
2
6
—
—
Food preparation centers
0
—
2
10
Yes
No
Dishwashing room
–
—
—
10
Yes
No
Dietary day storage
0
—
—
2
—
No
Laundry, general
0
—
2
10
Yes
No
Soiled linen sorting and
storage
–
—
—
10
Yes
No
Clean linen storage
+
—
2
2
—
—
Central medical
and surgical supply
Soiled or decontamination
room
–
—
2
4
—
No
Clean workroom
+
—
2
4
—
—
Unsterile supply storage
0
—
2
2
—
—
+=Positive –=Negative 0=Equal —=Optional
Stop valves shall be provided at each fixture.
G. Hot, cold and chilled water piping
and waste piping on which condensation may
occur shall be insulated. Insulation of cold
and chilled water lines shall include an exterior vapor barrier.
H. Backflow preventers (vacuum
breakers) shall be installed on hose bibbs and
on all fixtures to which hoses or tubing can
be attached such as janitors’ sinks and bedpan
flushing attachments.
I. Flush valves installed on plumbing
fixtures shall be of a quiet operating type,
equipped with silencers.
J. Hot water distribution systems shall
be arranged to provide hot water and at each
fixture at all times.
K. Plumbing fixtures which require
hot water and which are intended for patient
use shall be supplied with water which is controlled to provide a maximum water temperature of one hundred ten degrees Fahrenheit
(110°F) at the fixture.
L. The hot water heating equipment
shall have sufficient capacity to supply the
water at the temperatures and amounts indicated in the following:
Use
Clinical
Dietary
Laundry
gal/hr/bed
6 1/2
4
4 1/2
Temp °F
110°
180°
180°
M. Storage tank(s) shall be provided
and shall be fabricated of corrosion-resistant
metal.
N. Piping over food preparation centers, food serving facilities, food storage
areas and other critical areas shall be kept to
a minimum and shall not be exposed. Special
precautions shall be taken to protect these
areas from possible leakage of or condensation from necessary overhead piping systems.
O. Building sewers shall discharge
into a community sewage system. Where such
a system is not available, the facility shall
provide a private sewage disposal system
approved by the Department of Health, the
Water Pollution Board, or both.
P. Automatic fire-extinguishing systems shall be installed in areas such as central soiled linen holding rooms, maintenance
shops, trash rooms, bulk storage rooms and
adjacent corridors, attics accessible for storage, range hoods and laundry and trash
chutes. Storage rooms of less than a one hundred (100) square foot area and spaces used
for storage of nonhazardous materials are
excluded from this requirement. Sprinkler
heads shall be installed at the top and at alternate floor levels of trash and laundry chutes.
Q. Nonflammable medical gas system
installations shall be in accordance with the
requirements of NFPA Standard No. 565.
(H) Electrical Requirements.
1. All material including equipment,
conductors, controls and signaling devices
shall be installed to provide a complete electrical system with the necessary characteristics and capacity to supply the electrical facilities shown in the specifications or indicated
on the plans. All materials shall be listed as
complying with applicable standards of
Underwriters’ Laboratories, Inc. or other
similarly established standards.
2. The installing contractor shall be
responsible for testing all electrical installations and systems and shall show that the
equipment is correctly installed and operated
as planned or specified.
3. Circuit breakers or fuses that provide
disconnecting means and overcurrent protection for conductors connected to switchboards and distribution panelboards shall be
enclosed or guarded to provide a dead-front
type of assembly. The main power distribution panel shall be located so as to be accessible only to authorized persons. It shall be
readily accessible for maintenance, clear of
traffic lanes and in a dry ventilated space
devoid of corrosive fumes or gases. Overload
protective devices shall be suitable for operating properly in the ambient temperature
conditions.
4. Lighting and appliance panelboards
shall be provided for the circuits on each
floor. This requirement does not apply to
emergency-system circuits.
5. All spaces occupied by people,
machinery and equipment within buildings
and the approaches thereto and parking lots
shall have electric lighting. Patients’ bedrooms shall have general lighting and night
lighting. A reading light shall be provided for
each patient. At least one (1) luminaire for
night lighting shall be switched at the
entrance to each patient room. Patients’ reading lights and other fixed lights not switched
at the door shall have switch controls convenient for use at the luminaire. All switches
for control of lighting in patient areas shall be
of the quiet operating type.
6. Each patient bedroom shall have
duplex receptacles as follows: one (1) on each
side of the head of each bed (for parallel adjacent beds); receptacles for luminaires, television and motorized beds, if used; and one (1)
receptacle on another wall.
7. Single receptacles for equipment such
as floor cleaning machines shall be installed
approximately fifty feet (50') apart in all corridors. Duplex receptacles for general use
shall be installed approximately fifty feet
(50') apart in all corridors and within twentyfive feet (25') of ends of corridors.
8. A nurses’ calling station shall be
installed at each patient bed and in each
patient toilet, bath and shower room. The
nurses’ call-in toilet, bath or shower rooms
shall be an emergency call. All calls shall
register at the nurses’ station and shall actuate a visible signal in the corridor at the
patient’s door, in the clean workroom, soiled
workroom and nourishment station of the
nursing unit. In multi-corridor nursing units,
additional visible signals shall be installed at
corridor intersections. In rooms containing
two (2) or more calling stations, indicating
lights shall be provided at each calling station. Nurses’ call systems which provide two
(2)-way voice communication shall be
equipped with an indicating light at each calling station which lights and remains lighted
as long as the voice circuit is operative.
9. A manually-operated, electricallypowered fire alarm system which will serve
to alert all areas of the hospital when activated shall be installed in each facility. In multistory buildings or in multi-building facilities,
the signal shall be coded or otherwise
arranged to indicate the location of the station
operated. Pre-signal systems will not be permitted, except when telephone switchboard is
attended at all times.
10. To provide electricity during an
interruption of the normal electric supply that
could affect the nursing care, treatment or
safety of the occupants, an emergency source
of electricity shall be provided and connected
to certain circuits for lighting and power.
11. The source of this emergency electric service shall be an emergency generating
set when the normal service is supplied by
one (1) or more central station transmission
line(s) or an emergency generating set or a
central station transmission line, when the
normal electric supply is generated on the
premises.
12. The required emergency generating
set shall be located on the premises and shall
be reserved exclusively for supplying the
emergency electrical system. The emergency
generator set shall be of sufficient kilowatt
capacity to supply all lighting and power load
demands of the emergency system. The
power factor rating of the generator shall be
not less than eighty percent (80%).
13. Emergency electric service shall be
provided to at least the following circuits:
A. Lighting. Exitways and all necessary ways of approach including exit signs
and exit direction signs, exterior of exits, exit
doorways, stairways and corridors; dining
and recreation rooms (if located other than on
grade level); nursing station and medication
preparation area; generator set location,
switch gear location and boiler room; elevator (if required for emergency); telephone
switchboard; and kitchen, X ray and laboratory;
B. Equipment. Nurses’ calling system; alarm system including fire alarm actuated at manual stations; water flow alarm
devices of sprinkler systems if electrically
operated; fire detecting and smoke detecting
systems; paging or speaker systems if intended for issuing instructions during emergency
conditions; and alarms required for nonflammable medical gas systems, if installed;
fire pump, if installed; sewerage or sump lift
pump, if installed; all required duplex receptacles in patient corridors; one (1) elevator,
where elevators are used for vertical transportation of patients; equipment such as
burners and pumps necessary for operations
of one (1) or more boilers and their necessary
auxiliaries and controls, required for heating
and sterilization; and equipment necessary
for maintaining telephone service;
C. Where electricity is the only
source of power normally used for space
heating, the emergency service shall provide
for heating of patient rooms. Emergency heating of patient rooms will not be required in
areas where the design temperature is higher
than plus twenty degrees Fahrenheit (+20°F)
based on the Median of Extremes as shown in
the current edition of the ASHRAE Handbook
of Fundamentals or when the hospital is supplied by at least two (2) utility service feeders, each supplied by separate generating
sources, or a network distribution system fed
by two (2) or more generators, with the hospital feeders so routed, connected and protected that a fault any place between the generators and the hospital will not likely cause
an interruption of more than one (1) of the
hospital service feeders; and
D. The emergency electrical system
shall be so controlled that after interruption
of the normal electric power supply, the generator is brought to full voltage and frequency and connected within ten (10) seconds
through one (1) or more primary automatic
transfer switches to all emergency lighting,
all alarms, nurses’ call, equipment necessary
for maintaining telephone service and receptacles in patient corridors. All other lighting
and equipment required to be connected to
the emergency system shall either be connected through the previously described primary automatic transfer switching or shall be
subsequently connected through other automatic or manual transfer switching. Receptacles connected to the emergency system shall
be distinctively marked for identification.
Storage-battery-powered lights, provided to
augment the emergency lighting or for continuity of lighting during the interim of transfer switching immediately following an interruption of the normal service supply, shall
not be used as a substitute for the requirement
of a generator. Where fuel is normally stored
on the site, the storage capacity shall be sufficient for twenty-four (24)-hour operation of
required emergency electric services. Where
fuel is normally piped underground to the site
from a utility distribution system, storage
facilities on the site will not be required.
(I) Elevators.
1. All rehabilitation hospitals where
either patients’ beds or facilities such as diagnostic, recreation, patient dining or therapy
rooms are located on other than the first
floor, shall have electric or electrohydraulic
elevators as follows:
A. At least one (1) hospital-type elevator shall be installed where one to fiftynine (1–59) patient beds are located on any
floor other than the first (for purposes of
these requirements, the first floor is that floor
first reached from the main front entrance);
B. At least two (2) hospital-type elevators shall be installed where sixty to two
hundred (60–200) patient beds are located on
floors other than the first or where inpatient
facilities are located on a floor other than that
containing the patient beds;
C. At least three (3) hospital-type elevators shall be installed where two hundred
one to three hundred fifty (201–350) patient
beds are located on floors other than the first
or where inpatient facilities are located on a
floor other than that containing the patient
beds;
D. For hospitals with more than three
hundred fifty (350) beds, the number of elevators shall be determined from a study of the
hospital plan and the estimated vertical transportation requirements;
E. Elevator cars and platforms shall
be constructed of noncombustible material
except that fire-retardant-treated material may
be used if all exterior surfaces of the car are
covered with metal. Cars of hospital-type elevators shall have inside dimensions that will
accommodate a patient’s bed and attendants
and shall be at least five feet wide by seven
feet six inches (5' × 7' 6") deep, with a
capacity of four thousand (4000) pounds. The
car door shall have a clear opening of not less
than three feet ten inches (3' 10");
F. Elevators shall have automatic leveling of the two (2)-way automatic maintaining type with accuracy within plus or minus
one-half inch (±1/2"); and
G. Elevators (except freight elevators)
shall be equipped with a two (2)-way special
service switch to permit cars to bypass all
landing button calls and be dispatched directly to any floor.
2. The contractor shall be required to
cause inspections and tests to be made and
shall deliver to the owner written certification
that the installation meets the requirements
set forth in this section and all pertinent safety requirements.
AUTHORITY: section 197.080, RSMo Supp.
1993.* This rule previously filed as 13 CSR
50-22.010 and 19 CSR 10-22.010. Original
rule filed Nov. 21, 1969, effective Jan. 21,
1970.
*Original authority 1953, amended 1993.