19 CSR 30-30.100
General Design and New Construction Standards for Birthing Centers
PURPOSE: Section 197.225, RSMo authorizes the Department of
Health to establish physical standards for birthing centers in
order to provide care in a safe environment. Birthing centers are
considered ambulatory surgical centers as defined by section
197.200(1), RSMo and are subject to licensure as required by section
197.205, RSMo. This rule establishes up-to-date construction
requirements for new birthing center construction to help ensure
accessible, functional, fire-safe and sanitary facilities. A new
birthing center is one for which plans are submitted to the
Department of Health after the adoption of this rule for the
construction of a new facility, expansion or renovation of an
existing birthing center or the conversion of an existing facility not
previously and continuously licensed as a birthing center under
Chapter 197, RSMo.
PUBLISHER’S NOTE: The publication of the full text of the material
that the adopting agency has incorporated by reference in this
rule would be unduly cumbersome or expensive. Therefore, the
full text of that material will be made available to any interested
person at both the Office of the Secretary of State and the office of
the adopting agency, pursuant to section 536.031.4, RSMo. Such
material will be provided at the cost established by state law.
(1) Planning and Construction Procedures.
(A) Any birthing center constructed or renovated after
the date of the adoption of this rule shall have plans and
specifications prepared by an architect registered in Missouri.
These plans and specifications shall be submitted to the
department for review and approval prior to beginning of
construction. The design and construction of birthing centers
shall conform to the most stringent requirements of this rule
and the local governing building code.
(B) The Department of Health shall be notified in writing
within five (5) days after construction begins. If construction
of the project is not started within one (1) year after the date
of the approval of the plans and specifications, the plans
and specifications shall be resubmitted to the Department of
Health for its approval and shall be amended, if necessary, to
comply with the then current rules before construction work
begins.
(C) Requests for variations from requirements on physical
facilities shall be requested in writing to the Department of
Health and must contain information which demonstrates the
providers ability to meet the intent or objectives of the rule
through alternative methods. Approvals for deviations shall be
requested in writing and both requests and approvals shall be
made a part of the permanent Department of Health records
for the birthing center.
(D) Where renovation or replacement work is done within
an existing facility, all new work or additions, or both, shall
comply with the applicable sections of this rule.
(E) Birthing centers which expand their capacity to four (4)
or more birthing rooms must comply throughout the facility
with the applicable requirements for birthing centers of this
size or larger.
(F) References in this rule to, National Fire Protection
Association (NFPA), publications are those contained in
the twelve (12)- volume 1994 Compilation of NFPA Codes,
Standards, Recommended Practices and Guides. Where there
are discrepancies between referenced NFPA publication
requirements and this rule, the requirements of this rule shall
apply.
(2) Design Considerations for the Physically Handicapped.
Roads, parking facilities, walks, ramps and entrances shall be
accessible and usable by persons who are physically disabled.
At least one (1) toilet, telephone and drinking fountain which
are accessible for use by handicapped public and clinic
patients shall be provided on each floor of a birthing center.
Elevator controls and alarms shall be accessible to wheelchair
occupants and shall be provided with tactile signage for the
visually impaired. Design details for handicapped accessible
facilities shall be consistent with the Guidebook to: The Minimum
Federal Guidelines of Requirements for Accessible Design
published January 6, 1981 by the United States Architectural
and Transportation Barriers Compliance Board.
(3) Site.
(A) Adequate vehicle and pedestrian access, including
loading and unloading space for delivery vehicles, shall be
provided within the lot lines to the main entrance, emergency
vehicular entrance, community activities and services.
(B) Adequate off-street parking shall be provided. Space
shall be provided at the ratio of one (1) space for each of the
maximum number of staff persons on duty at any given time
plus one (1) parking space for the patient capacity of the
birthing and examination rooms in the licensed facility.
(C) Fire lanes shall be provided and kept clear to provide
immediate access for fire fighting equipment.
(4) General Birthing Center Design Considerations. The
arrangement of the physical plant for a birthing center
shall provide for separation of administrative/public, prenatal
clinic and birthing suite areas. The birthing suite shall be in
a location in the facility that precludes unnecessary traffic
through the suite.
(5) Administrative/Public Areas. These areas shall include a
business office with a public information center and staff
telephone, administrator’s enclosed office, medical records
storage for at least two (2) years of patient records, public
lobby and waiting room, public telephone, public toilet and a
drinking fountain.
(6) Staff Areas. An area shall be provided to include secure
storage for personal effects, handicapped accessible toilet,
shower, change and lounge area sufficient to accommodate
staff needs as defined by the program.
(7) Prenatal Clinic and Preadmission Screening Area. This area
shall include:
(A) At least one (1) room with a minimum size of two
hundred fifty (250) square feet for group education. In birthing
centers with fewer than four (4) birthing rooms in response to
the program of the facility but in no case shall it be smaller
than one hundred twenty (120) square feet;
(B) At least one (1) examination room of not less than ninety
(90) square feet and a minimum dimension of nine feet (9’).
Each examination room shall be equipped with hand washing
facilities. In birthing facilities with only one (1) birthing room,
the required examination room shall be equipped to serve
as a stand-by birthing room. Examination facilities shall be
separate from, but adjacent to, the waiting room and birthing
suite; and
(C) A laboratory equipped with a counter, sink and refrigerator
which is required if the laboratory performs on-site laboratory
work. This requirement may be met by a contractual provision
for off-premises laboratory services.
(8) Birthing Suite. The birthing suite shall include at least one
(1) birthing room with the following minimum dimensions:
length and width of twelve feet (12'), ceiling height of eight feet
(8'), and a door three feet (3') in width.
(A) Hand washing facilities shall be located in each birthing
room. Lavatories shall be sized for scrubbing and equipped
with faucets which are knee, foot or otherwise designed to
operate without the use of hands.
(B) Each birthing room shall be equipped with a labor/
delivery bed large enough for mother and baby, examination
light, capacity to keep the infant warm, storage facilities for
supplies and sufficient tables to hold an emergency tray and
other necessary equipment.
(C) A toilet with lavatory shall be directly accessible to the
birthing room so patients will not be required to enter the
corridor. One (1) toilet may serve up to two (2) birthing rooms.
No fewer than ten percent (10%) of the birthing rooms shall be
served by handicapped accessible toilets. In birthing centers
with fewer than four (4) birthing rooms, one (1) handicappedaccessible patient toilet may be provided which is conveniently
located to and easily accessible from the birthing rooms
without having patients traverse public areas.
(D) A shower shall be conveniently located to and easily
accessible from the birthing rooms without requiring patients
to traverse public areas. One (1) shower may serve not more
than twelve (12) birthing rooms. At least one (1) patient shower
shall be handicapped-accessible.
(E) Piped-in oxygen and clinical vacuum shall be provided
in each birthing room. Birthing centers with fewer than four
(4) birthing rooms may use portable medical gas and vacuum
services.
(F) Emergency equipment including intravenous fluids and
resuscitation equipment shall be located in near the birthing
rooms.
(9) Service and Staff Support Facilities. The birthing suite shall
include:
(A) A clean work and sterile storage room equipped with
a sterilizer, counter and sink, and storage space for clean
supplies;
(B) A separate soiled/decontamination utility room equipped
with a clinic sink, counter and sink;
(C) A separate staff-only toilet with a constant running
exhaust and a lavatory conveniently located to the birthing
suite;
(D) A staff station providing visual supervision of the birthing
rooms and support facilities;
(E) A medication storage and preparation station equipped
with a sink and refrigerator;
(F) Storage space for emergency equipment; and
(G) Janitor’s closet equipped with a mop sink and having
sufficient space for the cleaning equipment used to maintain
the birthing procedure area. Birthing centers with fewer
than four (4) birthing rooms are required to have only one
(1) janitor’s closet to serve the entire facility. In multi-storied
birthing centers at least one (1) janitor’s closet shall be provided
on each floor.
(10) General Support Facilities. Each birthing center shall
include:
(A) Adequate space for the housing and maintenance of
mechanical, plumbing and electrical equipment;
(B) Oxygen storage facilities which, if located inside the
birthing center, shall be exhausted to prevent the accumulation
of quantities of spilled gases. Medical gas storage and
SENIOR SERVICES
distribution systems shall comply with “NFPA 99, Standard for
Health Care Facilities, 1993 Edition” in 1994 National Fire Codes,
Volume 5;
(C) Housekeeping supply and general storage rooms;
(D) A janitor’s closet, including a mop sink, to serve the
public, business and preadmission clinic areas;
(E) In birthing centers proposing to process laundry on-site,
laundry facility design and laundry equipment of a quality to
be capable of producing sanitized linen; and
(F) At a minimum, provisions for shelf storage and refrigerated
storage of prepackaged nourishments. Provisions shall be made
for serving prepackaged nourishments to birthing patients. In
birthing centers proposing to prepare food on-site, the design
of the dietary facilities must be acceptable to the department
and comply with 19 CSR 20-1.010.
(11) Details and Finishes.
(A) A continuous system of unobstructed corridors and aisles
shall be provided which connects all rooms and space with
each other and all entrances, exits and elevators. Corridors
shall be separated from other areas by walls which resist the
passage of smoke.
(B) Each exit shall discharge to the outside or through an
enclosed stairway or passageway to the outside.
(C) Required exit stairs shall discharge directly to the outside
or into a rated fire corridor which extends from the stair
discharge to the outside. The fire-resistance rating of fire
corridor walls shall be not less than the rating of the stair
enclosure requirement located in section (12) of this rule.
(D) Corridors shall be at least six feet (6') wide. All other
corridors and aisles shall be at least four feet (4') wide.
(E) Exit doors shall swing in the direction of exit travel.
(F) All doors, procedure rooms and exits shall be at least three
feet (3') wide.
(G) All corridor doors shall be of solid wood construction or
its equivalent.
(H) Each birthing room shall have an operable window in the
outside wall. The window sill shall be not more than three feet
(3') above the floor. Easily washable window treatments, such
as vertical hanging vinyl blinds, shall be installed to control
light and glare. All window treatments shall be inherently
flame retardant.
(I) At least one (1) ABC-type fire extinguisher, compliant
with “NFPA 10, Standard for Portable Fire Extinguisher,” 1990
Edition, 1994 National Fire Code, Volume 1, shall be located
near each exit on each floor of the birthing center and at the
birthing suite’s staff station.
(J) A paper towel dispenser and soap dispenser shall be
provided at all lavatories used for hand washing.
(K) Finish materials installed on the walls, floors and ceilings
in the birthing rooms shall be smooth and washable.
(L) Ceiling, wall and floor finishes shall be smooth and easily
cleanable in toilets and bath facilities. Utility and storage
rooms used for washing, sterilization and supplies shall have
smooth and easily cleanable ceiling, wall and floor finishes.
(M) Floor and wall penetrations by pipes, ducts, and conduits
shall be tightly sealed to minimize entry of rodents and insects.
Joints of structural elements shall be similarly sealed.
(12) Construction, Including Fire-Resistive Requirements.
(A) Construction of freestanding birthing centers shall
comply with “NFPA 101 Section 12-6, New/Ambulatory Health
Care Centers, 1994 Edition”, 1994 National Fire Codes, Volume 5
and this rule.
(B) Multistoried buildings rated combustible Type V shall
be protected throughout by an approved automatic sprinkler
system. The number of stories in a building housing a birthing
center shall be determined by counting all occupiable levels in
the building.
(C) Birthing centers shall be separated from other tenants
and occupancies by walls having at least a one (1)-hour fireresistance rating. These walls shall extend from the floor slab
below to the floor or roof slab above.
(D) Every stairway, elevator shaft, light and ventilation shaft,
chute and other openings between stories shall be enclosed or
protected to prevent the spread of fire or smoke from one (1)
floor to another. The fire-resistance rating of the enclosure or
protection shall be not less than the structural floor separation
requirements of “NFPA 220, Standard on Types of Building
Construction, 1992 Edition,” 1994 National Fire Code, Volume
5 for the fire-resistive building type classification required by
subsection (12)(A).
(13) Elevators.
(A) Multistoried buildings shall have at least one (1) elevator
if birthing room services are located on any floor other than
the grade level (main entrance) floor.
(B) The elevator cab shall be at least five feet by seven feet (5'
x 7') clear inside. The car door shall have a clear opening of not
less than three feet (3').
(C) Elevators shall be equipped with a two (2)-way special
service switch to permit cars to bypass all landing button calls
and be dispatched directly to any floor.
(D) Elevators shall be equipped with an automatic leveling
device of the two (2)-way automatic maintaining type with an
accuracy of plus or minus one-half inch (±1/2").
(E) Elevator call buttons, controls and door safety stops shall
be of a type that will not be activated by heat or smoke.
(14) Mechanical Requirements.
(A) Heating, ventilating and air conditioning (HVAC)
equipment shall be mandated to operate at an ambient
temperature of sixty-eight to eighty-five degrees Fahrenheit
(68–85°F).
(B) Air supplied to all areas shall be filtered through a filter
with at least a twenty-five percent (25%) efficiency rate. Filter
efficiencies shall be average atmospheric dust spot efficiencies.
(C) Required exhaust fans shall be nonswitched and constant
running. All exhaust fans shall be installed at the discharge
end of the duct.
(D) The HVAC systems shall be designed and balanced to
provide pressure relationships and air change rates shown in
the following table:
(15) Plumbing and Other Piping Systems.
(A) Systems shall be designed to supply water to the fixtures
and equipment on every floor at a minimum pressure of fifteen
pounds per square inch (15 psi) during maximum demand
periods.
(B) Each water service main, branch main, riser and branch
to a group of fixtures shall be valved. Stop valves shall be
provided at each fixture.
(C) Cold and chilled water piping and waste piping shall
be insulated. Insulation of cold and chilled water lines shall
include an exterior vapor barrier.
(D) Reduced pressure backflow preventers shall be installed
where the water service enters the building and on hose bibbs
and on all fixtures to which hoses or tubing can be attached
such as janitors’ sinks and laboratory fixtures.
(E) Hot water distribution systems shall provide one hundred
ten degree Fahrenheit (110°F) water at each fixture at all times.
(F) Sinks in patient service areas shall have the water supply
spout mounted so that its discharge point is a minimum
distance of five inches (5") above the rim of the fixture. All
lavatories used by medical and nursing staff shall have valves
which can be operated without the use of hands.
(16) Electrical Requirements.
(A) Every room, including storage rooms, corridor and all
other areas shall be sufficiently illuminated.
(B) Trickle charge battery pack units, complying with the
standards of “Article 700, Emergency Systems, NFPA 70, National
Electrical Code, 1994 Edition,” in National Fire Code, Volume 3,
shall be located to provide emergency lighting in the birthing
rooms, exit corridors, exit signs, electrical branch panel rooms
and exit stairs to point of discharge at grade. These fixtures
shall be tested at least quarterly with the tests documented in
writing. An emergency stand-by power system is not required
in birthing centers.
(C) There shall be one (1) electrical outlet in each birthing
room for the trickle charge emergency light and at least one (1)
duplex outlet on each wall.
(D) Electrical outlets installed in wet locations, such as the
patient toilet areas, shall be ground fault interrupter types.
(E) In birthing center of four (4) or more birthing rooms, an
electrically powered fire alarm system shall be installed which
will alert all areas of the facility when activated. A fire alarm
manual pull station shall be located near each exit and at the
staff station. The initiation of this fire alarm system shall be
by manual means and by automatic means of any required
detection devices.
(F) Birthing centers shall have smoke detectors interconnected
with the fire alarm system in all rooms and at thirty-foot (30')
intervals in corridors. Birthing centers located in completely
sprinklered buildings require only the corridor detectors. In
birthing centers of fewer than four (4) birthing rooms, the fire
alarm system may consist of the individual required smoke
detectors, provided the local alarm may be heard throughout
the occupied areas of the birthing center.
AUTHORITY: section 197.225, RSMo 1994.* Emergency rule filed
May 1, 1995, effective May 10, 1995, expired Sept. 7, 1995.
Original rule filed May 1, 1995, effective Nov. 30, 1995. Emergency
amendment filed June 19, 1998, effective July 1, 1998, expired Feb.
25, 1999. Amended: Filed June 19, 1998, effective Jan. 30, 1999.
*Original authority 1975, amended 1986.