19 CSR 30-35.020
Hospice Providing Direct Care in a Hospice Facility
PURPOSE: This rule defines the minimum requirements necessary
for the construction and operation of hospice inpatient facilities in
order to be certified as part of the hospice program.
(1) A hospice that delivers care in a facility operated by the
hospice and not otherwise licensed shall comply with this rule
in addition to 19 CSR 30-35.010 and 19 CSR 30-35.030.
(2) Each patient shall receive treatment, medications and
diet as prescribed and shall be kept comfortable, clean, wellgroomed and protected from accident, injury and infection.
(3) Organization and Management of Hospice Facilities.
(A) 24-Hour Staffing.
1. The hospice shall provide 24-hour staffing which is
sufficient to meet the patients’ total needs in accordance with
the patient plan of care.
2. All hospices shall employ qualified staff at the ratio of no
less than one for every ten (1:10) patients per shift, per patient
unit, 24 hours a day.
3. Staffing personnel shall be on duty at all times on each
patient-occupied floor, with no less than two staff personnel in
a facility at all times.
4. Minimum staff personnel shall be no less qualified
than one home health aide or companion/volunteer and one
licensed practical nurse.
5. A registered nurse shall be available for telephone
consultation or on-site visit as needed, 24 hours a day.
6. Facility personnel shall have a telephone access to
administrative staff, 24 hours a day.
(B) Disaster Preparedness.
1. The hospice shall have a written plan, annually rehearsed
with staff, which includes procedures to be followed in the
event of an internal or external disaster and for the care of
casualties arising from disasters.
2. Each facility shall conduct quarterly fire drills so that
each shift participates at least annually.
(C) Meals Service Menu Planning and Supervision. The
hospice shall:
1. Make available a practical freedom of choice diet
offering at least three meals and snacks, or their equivalent,
that accommodate patient’s needs and preferences each day
at regular times, with not more than 14 hours between a
substantial evening meal and breakfast;
2. Prepare and serve foods using methods that conserve
nutritive value, flavor and appearance;
3. Give special attention to the texture of food served to
patients who have chewing difficulty;
4. Provide assurance that hot food is served hot and cold
food is served cold;
5. Give a minimum of 30 minutes for eating meals.
Patients who eat slowly or who need assistance shall be given
as much time to eat as necessary;
6. Make tray service and dining room service attractive
for patients and ensure that each patient receives appropriate
table service;
7. Provide each patient who is served meals in bed or
in a chair not within the dining area with either a table, an
overbed table or an overbed tray of sturdy construction which
is positioned so that the patient can eat comfortably;
8. Provide assistance upon tray delivery to all patients
requiring assistance at mealtimes, whether it be preparation
of the food items or actual feeding. Dining room supervision
shall be provided during meals;
9. Establish an identification system to assure that each
patient receives the diet as ordered;
10. Provide sufficient equipment and personnel trained in
their duties to assure adequate preparation and serving of food
if meals are prepared on-site;
11. Review menus for special prescribed diets and approve
in writing by either a qualified dietitian, a registered nurse, or
a physician;
12. Keep a current record of purchased food to show the
kind and amount of food purchased each month, if meals are
prepared on-site;
13. Plan menus for all diets at least two weeks in advance
if meals are prepared on-site. If cycle menus are used, the cycle
shall cover a minimum of three weeks and shall be different
each day of the week;
14. Make fresh water readily accessible to all patients at
all times;
15. Procure, store, prepare, distribute and serve all food
under sanitary conditions;
16. Permit family to bring, prepare and serve food to their
loved one; and
17. Permit staff to prepare a single patient snack upon
request.
(D) Patient Areas.
1. The hospice shall design and equip areas for the comfort
and privacy of each patient and family member.
2. The hospice shall have accommodations for family
privacy after a patient’s death that do not infringe on other
patients’ rights and decor which is homelike in design and
function;
3. Patients shall be permitted to receive visitors, including
small children, at any hour;
4. The facility shall have a policy regarding pets; and
5. Smoking may be permitted in the hospice consistent
with the smoking policy of the facility. Smoking may be
permitted in the patient’s room and in designated smoking
areas. Individual patients may be permitted to smoke in their
rooms with the consent of any other patients occupying the
room and with the permission of his/her attending physician.
If a patient is confined to bed or classified as not being
responsible, smoking is permitted only under the direct
supervision of an authorized individual.
(E) Infection Control.
1. The hospice shall make disease-specific provision for
isolating patients with infectious diseases.
2. Infectious waste management control.
A. Every inpatient hospice facility shall write an
infectious waste management plan with an annual review
identifying infectious waste generated on-site, the scope of
the infectious waste program and policies and procedures
to implement the infectious waste program. The plan shall
include at the least the following: administrator’s endorsement
letter; introduction and purpose; objectives; phone number of
responsible individuals; definition of those wastes handled
by the facility; identification of responsible individuals;
procedures for waste identification, segregation, containment,
transport, treatment and disposal; emergency and contingency
procedures and training; and educational procedures.
B. Infectious waste shall be segregated from other
wastes at the point of generation and shall be placed in
distinctive, clearly marked, leakproof containers or plastic bags
appropriate for the characteristics of the infectious waste.
C. Containers for infectious waste shall be identified
with the universal biological waste symbol. All packaging shall
maintain its integrity during storage and transport. Infectious
waste shall not be placed in a gravity disposal chute.
D. Pending disposal, infectious waste shall be stored
separately from other wastes in a room limited to staff access.
E. When transported off the premises of the hospice,
all infectious waste shall be packaged and transported as
provided in sections 260.200–260.245, RSMo.
F. Hospices generating 100 kilograms or less of infectious
waste per month must comply with section 260.203.10, RSMo.
3. Written policies and procedures shall define and
describe the scope and conduct of laundry and linen services.
There shall be a mechanism for the review and evaluation on
an annual basis of the quality of laundry services.
4. Written policies and procedures shall define and
describe the scope and conduct of on-site cleaning of dietary
ware. There shall be a mechanism for the review and evaluation
on an annual basis of the quality of dietary-ware sanitizing
services provided.
(F) Pharmacy Services. The hospice shall comply with all
provisions of 19 CSR 30-35.010 regarding medications.
1. The hospice shall employ or contract with a pharmacist.
A. The pharmacist shall assist in the development
of policies and procedures for medication use, shall advise
the hospice on all other matters pertaining to the use of
medications, shall serve as a member of, or consultant to,
the interdisciplinary team and shall provide medication
information to professional staff as required.
B. A pharmacist shall be available on a twenty-four (24)-
hour basis for emergencies.
2. Medication acquisition and labeling.
A. Prescription medications shall be maintained as
individual patient prescriptions or in an automated dispensing
system.
B. Each facility shall maintain an emergency medication
supply. When the emergency medication supply is separate
from an automated dispensing system and contains controlled
substances the facility shall be registered with the Missouri
Bureau of Narcotics and Dangerous Drugs.
C. Automated dispensing systems may be controlled
by the facility or may be controlled on-site or remotely by a
pharmacy.
(I) When an automated dispensing system is controlled
by the facility:
(a) A pharmacist shall be responsible for the
operation of the automated dispensing system and training of
facility staff in its use;
(b) A pharmacist shall review and confirm each new
medication order prior to administration of the first dose;
(c) The facility shall have a policy and procedure
to allow removal of initial doses of approved emergency
medication supply medications in lieu of maintaining a
separate emergency medication supply;
(d) A pharmacist or pharmacy technician shall place
medications in the automated dispensing system. Medications
to be placed in the automated dispensing system shall be
checked and approved by a pharmacist;
(e) When the automated dispensing system contains
controlled substances, the facility shall be registered with the
Missouri Bureau of Narcotics and Dangerous Drugs and the
Drug Enforcement Administration; and
(f) When the automated dispensing system is for
the purpose of an emergency medication supply only, subparts
(b) and (c) of this part shall not apply and the facility shall
not be required to be registered with the Drug Enforcement
Administration.
(II) When an automated dispensing system is
controlled by a pharmacy:
(a) A pharmacist shall review and confirm each new
medication order prior to releasing the medication from the
system;
(b) The pharmacy and the facility shall have a
policy and procedure to allow removal of initial doses of
approved emergency medication supply medications when the
automated dispensing system is used in lieu of maintaining a
separate emergency medication supply;
(c) A pharmacist or pharmacy technician shall place
medications in the automated dispensing system. Medications
to be placed in the automated dispensing system shall be
checked and approved by a pharmacist;
(d) The pharmacy shall comply with all requirements
of paragraph 3. of this subsection;
(e) The automated dispensing system shall be
licensed by the Board of Pharmacy and shall be used in
compliance with 20 CSR 2220-2.900;
(f) When the automated dispensing system contains
controlled substances it shall be registered with the Missouri
Bureau of Narcotics and Dangerous Drugs and the Drug
Enforcement Administration; and
(g) When the automated dispensing system is for
the purpose of an emergency medication supply only, subparts
(a) and (e) of this part shall not apply and it shall not be required
to be registered with the Drug Enforcement Administration.
(III) A facility employee who registers with the Board of
Pharmacy as a pharmacy technician shall be a nurse, certified
pharmacy technician, or certified medication technician.
The pharmacist shall be responsible for the training of the
employee and shall supervise the employee in compliance
with 20 CSR 2220-2.700 when pharmacy technician functions
are being performed.
D. Patient prescription medications shall be labeled with
at least the patient name, medication name, strength and date
dispensed. They shall also contain accessory information and
the expiration date when applicable.
E. Prescription medication labels shall not be altered
by hospice staff and medications shall not be repackaged by
hospice staff except as allowed by (3)(F)4.E.
F. When the patient’s own medications are used, they
shall be examined prior to use for suitability and positively
identified by a pharmacist or nurse in writing.
G. Non-prescription medications may be obtained
as stock or individual patient supplies. They shall not be
repackaged, except as allowed by (3)(F)4.E., and supplies for
individual patients shall be labeled with the patient’s name.
3. Medication storage and control.
A. All medications shall be stored in locked compartments
under proper temperature controls, separate from food
and other substances. Medications shall be accessible only
to persons authorized to administer them, pharmacists or
pharmacy technicians.
B. Controlled substances shall be stored in locked
compartments separate from other medications.
C. The pharmacist shall inspect medication storage
areas and the emergency medication supply monthly and shall
document this inspection.
D. Records of receipt and disposition of all controlled
substances shall be maintained separate from other records.
(I) Inventories of Schedule II controlled substances
shall be reconciled each shift when they are not maintained in
an automated dispensing system.
(II) Inventories of Schedule III–V controlled substances
shall be reconciled daily when they are not maintained in an
automated dispensing system.
(III) Inventories of controlled substances shall be
reconciled at least every seventy-two (72) hours when they are
maintained in an automated dispensing system.
(IV) Receipt records shall include the date, source
of supply, patient name and prescription number when
applicable, medication name and strength, quantity and
signatures of the supplier and receiver.
(V) Administration records shall include the date,
time, patient name, medication name, dose administered and
signature of the person administering.
(VI) Documentation of waste at the time of
administration shall also include the reason for the waste and
the signature of an authorized employee witness.
E. The pharmacist shall review controlled substance
record keeping monthly.
F. All variances of controlled substance records shall
be reported to the registered nurse coordinator and the
pharmacist for review and investigation.
G. All losses of controlled substances shall be reported to
the Missouri Bureau of Narcotics and Dangerous Drugs and to
other federal, state and local authorities when required.
H. All controlled substance records shall be maintained
for two (2) years.
4. Medication administration.
A. Medication administration by the patient or a family
member shall be ordered by the physician. Instructions for
administration shall be provided.
B. Non-controlled substances may be stored in a locked
compartment in the patient’s room.
C. Single doses of controlled substances may be placed
in the locked compartment or provided directly to the patient
or family member prior to the time of administration.
D. Administration of the patient’s own medications
brought to the facility shall be ordered by the authorized
prescriber.
E. Medications for administration when a patient
temporarily leaves the facility shall be labeled by the pharmacy
with instructions for administration, except that a single
dose of each medication may be provided by the nurse
in containers labeled with the patient’s name, medication
name and strength, instructions for administration, and other
necessary information.
F. Medication administration shall be documented on
a separate record. Administration by the patient or a family
member shall be monitored by nursing staff and documented.
5. Other medication disposition.
A. Medications may be sent with a patient at the time
of discharge only if they have been labeled by the dispensing
pharmacy with instructions for administration and ordered by
the authorized prescriber.
B. Records of this disposition shall include the date,
patient name, prescription number, drug name and strength,
quantity and signatures of the persons releasing and receiving
the medications.
C. Patient prescription medications that have been
discontinued shall be destroyed within sixty (60) days if
they are controlled substances or if they are not in unit-dose
packaging.
D. Patient prescription medications of expired patients
shall be destroyed within five (5) days if they are controlled
substances or if they are not in unit-dose packaging or if they
were brought from home.
E. Other expired or nonusable medications shall be
destroyed within five (5) days.
F. Medications shall be destroyed by a pharmacist
and a nurse or two (2) nurses, and a record of destruction
shall be maintained which includes the date, patient name,
prescription number, medication name and strength, quantity,
method of destruction and signatures of the persons destroying
the medications.
G. Unit-dose packaged medications returnable to the
pharmacy shall be returned within ten (10) days.
H. Medications shall not be transferred to other patients
and shall not be removed from the facility by hospice staff,
except those being returned to the pharmacy.
(4) General Design and Construction Standards for New
Inpatient Hospice Facilities.
(A) Health and Safety Laws. The hospice shall meet all
federal, state and local laws, ordinances, regulations and
codes pertaining to health and safety, including but not
limited to, provisions regulating construction, maintenance
and equipment.
1. General Requirements.
A. After October 30, 1996, a new hospice facility shall
submit plans for approval to the Department of Health for the
construction of a new facility, expansion or renovation of an
existing state certified hospice or the conversion of an existing
facility not previously and continuously state certified and
operated as a hospice facility under section 197.250, RSMo.
B. New hospice facilities shall be designed and
constructed in conformance with this rule.
C. This rule is not intended to restrict innovations
and improvements in design or construction techniques.
Accordingly, the Department of Health may approve plans and
specifications which contain deviations from this rule. Requests
for deviations from requirements on physical facilities shall
be in writing to the Department of Health and shall contain
information which determines that the respective intent or
objectives of this rule have been met. Approvals for deviations
shall be in writing and both requests and approvals shall be
made a part of the permanent Department of Health records
for the hospice.
D. Where renovation or replacement work is done within
an existing licensed facility, all new work, additions, or both,
shall comply with the applicable sections of this rule. Where
existing major structural elements make total compliance
impractical or impossible, alternative proposals which result in
an equivalency may be considered by the department.
E. In renovation projects and additions to existing
state certified hospice facilities, only that portion of the total
facility affected by the project shall comply with the applicable
sections of this rule. However, upon construction completion,
the facility shall satisfy all functional requirements for state
certified hospices.
F. Those existing portions of the facility which are not
included in the renovation but which are essential to the
functioning of the complete facility as well as existing state
certified building areas that receive less than substantial
amounts of new work shall, at a minimum, comply with
the state certification requirements which were in effect at
the time that the existing portion of the building was state
certified.
G. All required fire exits shall be maintained throughout
the construction and the work shall be phased as necessary to
minimize disruption of the existing hospice operation.
2. Planning and Construction Procedures.
A. Any hospice facility constructed or renovated after
October 30, 1996 shall have plans and specifications prepared
in conformance with Chapter 327, RSMo by an architect or
engineer duly registered in Missouri. The owner of each
new facility or the owner of an existing licensed inpatient
hospice being added to or undergoing major alterations shall
provide a program—scope of services—which describes space
requirements, staffing patterns, departmental relationships
and other basic information relating to the objectives of the
facility. The program may be general but it shall include a
description of each function to be performed, approximate
space needed for these functions and the interrelationship
of various functions and spaces. The program shall describe
how essential services can be expanded in the future as the
demand increases. Appropriate modifications or deletions in
space requirements may be made when services are shared or
purchased, provided the program indicates where the services
are available and how they are to be provided. This program
shall be submitted to the Department of Health for review
along with the plans developed for the project. Schematic and
preliminary plans showing the basic layout of the building and
the general types of construction, mechanical and electrical
systems and details may be submitted to the department
before the larger and more complicated working drawings
and specifications so that necessary corrections can be easily
made before final plans are completed. Working drawings and
specifications, complete in all respects, shall be prepared and
submitted to the Department of Health for approval. These plans
shall cover all phases of the construction project, including site
preparation: paving; general construction; mechanical work,
including plumbing, heating, ventilating and air conditioning;
electrical work; and all built-in equipment, including elevators,
kitchen equipment, cabinet work, and the like.
B. The Department of Health shall be notified in writing
within five (5) days after construction begins. Construction
shall be in conformance with plans and specifications approved
by the Department of Health. The department may elect
to inspect the construction of hospice projects at any time
during the development of the project. If construction of the
project is not started within one (1) year or completed within
a period of three (3) years after the date of the approval of the
plans and specifications, the plans and specifications shall be
resubmitted to the Department of Health for its approval and
shall be amended, if necessary, to comply with the then current
rules before construction work is started or continued.
C. References in this rule to National Fire Protection
Association (NFPA) publications are those contained
in the 12-volume 1994 Compilation of NFPA Codes, Standards, Recommended Practices and Guides. Where there are
discrepancies
between
referenced
NFPA
publication
requirements and this rule, the requirements of this rule shall
apply.
D. The design and construction of hospices shall conform
to the most stringent requirements of this rule and the local
governing building code and zoning ordinances.
3. Site.
A. Adequate paved pedestrian access shall be provided
within the lot lines to the main entrance. Loading and
unloading space for delivery vehicles shall be paved.
B. Adequate paved parking shall be provided. Parking
space needs shall be determined by the local zoning
requirement and the operational program but shall not be less
than one (1) space for each of the maximum number of staff
persons on duty at any given time plus one (1) parking space
for each licensed inpatient bed in the facility.
C. Fire lanes shall be provided as required by local
authority and kept clear to provide immediate access for fire
fighting equipment.
D. The site shall provide reasonable access for those
individuals to be served by the facility. The facility shall be
on an all-weather road for easy access by vehicular traffic.
Consideration should be given to locating the hospice to
provide easy access to public transportation services which
may be available in the community.
E. The site shall be located within the service area of a
public fire department.
4. Roads, parking facilities, walks, ramps and entrances
shall be accessible and usable by persons with various physical
handicaps.
A. At least one toilet, telephone and drinking fountain
shall be provided on each floor of a hospice which is accessible
for use by handicapped public and staff.
B. Elevator controls and alarms shall be accessible
to wheelchair occupants and shall be provided with tactile
signage for the visually impaired.
C. Design details for handicapped accessible facilities
should be consistent with the Guidebook to: The Minimum
Federal Guidelines of Requirements for Accessible Design
published January 6, 1981, by the U.S. Architectural and
Transportation Barriers Compliance Board.
D. At least ten percent (10%) of the patient beds shall be
located in handicapped-accessible rooms with accessible toilet
rooms which open directly into the patient room. All other
clinical areas to which patients have common access shall be
handicapped-accessible.
5. Administrative and public areas shall be provided.
A. All hospices shall provide adequate work areas to
support the administrative personnel and governing body.
The facilities shall allow business to be conducted in a setting
which provides confidentiality and privacy as required. The
administrative offices may be located remotely from a hospice
inpatient unit or may be housed within the inpatient facility.
B. Where administration is included within the inpatient
facility, the following shall be provided:
(I) Administrator’s office;
(II) Business office including a work area for quality
assurance;
(III) Storage and work area for archived medical
records;
(IV) Conference room for governing board meetings
and personnel in-service training; and
(V) Office for director of patient-care services.
C. Each inpatient hospice facility shall provide the
following public areas in a location separated from the clinical
and service areas of the facility:
(I) Lobby/waiting room with reception;
(II) Wheelchair accessible public toilet;
(III) Wheelchair accessible public drinking fountain;
and
(IV) Wheelchair accessible public phone.
6. Design of patient-care units.
A. One or more patient-care units shall be provided.
Each unit shall not exceed a maximum of twenty (20) beds.
B. Each patient-care unit shall be a continuous area
which does not require patient-care traffic to traverse other
areas and shall be restricted to only one (1) floor level. If
justified by the program submitted under subparagraph (2)
(A)2.A. of this rule, the department may consider approval of
designs which provide for larger capacity patient-care units.
C. The bed area in a patient room exclusive of toilet
rooms, closets, alcoves or vestibules, shall not be less than one
hundred twenty (120) square feet in a private room and not
less than two hundred (200) square feet in a semi-private room.
Heating units and lavatories may protrude into this space.
D. No dimension for the bed area in any patient room
shall be less than ten (10) feet.
E. No patient room shall house more than two (2)
patients.
F. Each patient-care unit shall have not greater than
fifty percent (50%) of its beds housed in semi-private rooms
and the remaining rooms shall be limited to occupancy by
one (1) patient. If justified by the program submitted under
subparagraph (2)(A)2.A. of this rule, the department may
consider approval of designs which provide other ratios of
semi-private to private patient rooms.
G. Each patient shall have access to a toilet room
without entering the general corridor area.
H. One (1) toilet may serve not more than two (2)
adjacent rooms.
I. The toilet room shall contain a lavatory and water
closet and shall be sized to permit access for the patient and
an assisting member of the staff. The lavatory may be omitted
from the toilet room if a lavatory is provided in the patient
room.
J. At least one (1) patient room per patient-care unit shall
be provided to be used for isolation. This unit shall have a
toilet room equipped with a bathing facility which serves this
room exclusively.
K. Mirrors shall be provided in each patient room or
adjoining toilet room. Mirrors shall be at least three (3) feet
high located with the bottom edge no more than three feet
four inches (3'4") above the floor.
L. Patients shall have separate wardrobes, lockers or
closets located within their respective patient rooms. A clothes
rod and shelf shall be provided.
M. One or more windows shall be provided, with the
sash not more than three (3) feet above the floor and with a
gross area of not less than ten percent (10%) of the floor area
of the room. In each patient room at least one (1) window
to the outside shall be operable. Patient room windows
shall be exposed to an outside area not less than thirty (30)
feet horizontally opposite the window which contains no
construction or grading which would further diminish the
view and the exposure of the window to natural light.
N. Social spaces (dining, recreation, meditation) shall
be provided throughout the facility with a cumulative area of
not less than thirty (30) square feet per patient bed. One social
space may serve more than one patient-care unit provided it is
directly accessible from each unit and is sized proportionate to
the total number of patient beds it serves. No social space shall
be smaller than one hundred fifty (150) square feet in area.
O. Unless bathing facilities are included in the toilets
serving each patient room, central bathing facilities shall be
provided in each patient-care unit at a ratio of not fewer than
one for each ten (1:10) beds.
P. Each bathing facility shall be located in its own room
and shall be directly accessible from the general corridor. The
bathing facility may be either a tub, shower or tub/shower
combination.
Q. However, at least one (1) handicapped accessible
shower shall be provided on each patient unit.
R. A locked cabinet for the storage of cleaning supplies
shall be available in or near each bathroom.
7. Support and services areas. The following staff support
and service areas shall be located directly accessible to each
patient care unit:
A. Clean work and storage facilities shall be equipped
with counter and sink and storage space provided for clean
linen and supplies;
B. A separate soiled/decontamination utility room shall
be equipped with a clinic sink (this fixture is not required
where bedpan-flushing devices have been installed at each
patient toilet), counter and sink and sufficient floor space shall
be provided to accommodate storage containers for soiled
linen, trash and infectious waste;
C. Space shall be provided for secure storage of staff
personal items;
D. A staff station shall be located to provide visual
supervision of the patient-care unit corridors. The station shall
consist of a work counter and secure storage space for charts;
E. A medication storage and preparation station which
has a means of locked storage for all medications shall be
equipped with a work counter, sink, and refrigerator;
F. Separate locked storage facilities shall be provided in
the station for controlled substances;
G. If medications are held in each patient room, the
room shall include separate locked storage facilities for each
patient’s medications;
H. A nourishment station shall be equipped with a work
counter, sink, and refrigerator and shall be provided physically
remote from the medication preparation station;
I. Storage space shall be provided for mobile equipment
used on the unit;
J. A janitor’s closet shall be provided which is equipped
with a mop sink and has sufficient space for the cleaning
equipment and open supplies used to maintain the patientcare unit; and
K. All clean support functions may be located in one
clean workroom provided the room is carefully designed to
provide adequate storage and function separations.
8. Food service facilities shall be designed and equipped
to meet the requirements of the scope of services outlined as
follows:
A. Dietary facilities shall comply with 19 CSR 20-1.010;
B. In hospice facilities where food is prepared on-site, the
dietary facilities shall, as a minimum, have—a storage space
including cold storage for four-day supply, space and equipment
for food preparation to facilitate efficient food preparation and
to provide for a safe and sanitary environment, conveniently
located handwashing facilities, space for preparing food for
distribution to patients, warewashing facilities which are
isolated from the food preparation and serving area, and
storage facilities for waste which is inaccessible for insects and
rodents and accessible to the outside for pickup or disposal.
C. The warewashing processes shall produce dietary
ware which is free of pathogenic organisms; and
D. In hospice facilities where the food service is
provided through a vendor contract, dietary facilities shall, as
a minimum, include space for receiving and holding the food
transport equipment, utility connections for food transport
equipment to maintain appropriate serving temperatures, and
a holding area for soiled dietary ware transport equipment
which is out of the patient area and located near the service
entrance for pick-up.
(B) Service Facilities Shall Meet the Following Standards:
1. Services including linen service.
A. Service facilities shall be provided in each inpatient
hospice facility and located to be out of the normal public and
clinical traffic flow.
B. A weather-protected service entrance shall be
provided separate from entrances used by public and patients.
C. Space and facilities shall be provided for the sanitary
storage and disposal of waste. Exterior dumpsters will suffice
provided they can be accessed under the protection provided
at the service entrance.
D. A general storage room shall be provided with an area
not less than ten (10) square feet per bed for the first fifty (50)
beds, plus eight (8) square feet per bed for the next twentyfive (25) beds, plus five square feet per bed for any additional
beds over seventy-five (75). No storage room shall be less than
one hundred (100) square feet of floor space. Off-site storage
is acceptable, however, one half (1/2) of the required storage
space shall be located in the inpatient hospice facility. General
storage shall be concentrated in one area.
E. Space shall be provided to house mechanical
equipment. The space shall be adequate for initial installation
and ongoing maintenance access for each component of the
systems housed in it. Mechanical equipment shall not be
installed in rooms designated to house other functions.
F. A housekeeping room shall be provided with a
janitor’s sink and space to store opened containers of cleaning
supplies and housekeeping equipment used to maintain the
facility. This room is not required if the hospice is maintained
by a contract cleaning service which transports the necessary
cleaning supplies and equipment to the facility on a daily
basis.
G. An oxygen storage room shall be provided. This room
shall be enclosed with one-hour rated construction and shall
have a powered or gravity vent to the outside. Permanent
racks or fasteners shall be provided and used in the oxygen
storage room to prevent accidental damage or dislocation of
oxygen cylinders. In facilities storing quantities of oxygen less
than one thousand five hundred (1,500) cubic feet in total, a
power ventilated storage cabinet will comply. No ventilated
gas storage facilities are required in hospices which store no
medical gases within the building.
H. Laundry services may be provided by the hospice
operator or may be obtained through contract with a linen
service vendor. If laundry for the facility is done commercially,
either entirely or in part, space shall be provided for the
sorting, processing and storing of both soiled and clean linen.
Storage space shall be located to facilitate convenient pickup
and delivery by commercial laundry personnel. Hospices with
only one patient-care unit may accommodate these functions
within the utility facilities provided in the unit’s staff support
area.
I. Hospice-operated laundry facilities shall be designed
and procedures instituted to prevent cross-contamination of
clean and dirty linen. The laundry room shall be in a separate
room from the kitchen, patients’ rooms, the dining room and
the bathrooms or the nursing utility room. Adequate space
shall be provided in the laundry room for the storing, sorting
and processing of soiled linen. The processes of the laundry
operation shall be appropriate to the production of patient
linens which are free of pathogenic organisms. Space shall be
provided for the storage of clean linen in a separate room from
the laundry.
J. As may be required by the program, laundry facilities
provided for cleaning patients’ clothing exclusively shall
be located in the patient-care unit but in a room separate
from other functions. A residential-style laundry equipment
installation is acceptable.
K. As required by the program, living and sleeping
quarters, separate from patients’ facilities, shall be provided for
the employees and their families who may reside in the facility;
2. Elevators.
A. All inpatient hospice facilities having patient-care
facilities located on any floor other than the main entrance
floor shall have at least one (1) electric or electrohydraulic
elevator. Hospice facilities with more than thirty (30) beds
located on any floor other than the main entrance floor shall
have at least two (2) elevators. Hospice facilities with more
than two hundred (200) beds located on any floor other
than the main entrance floor shall provide passenger and
service elevators in numbers and at locations determined by a
professionally conducted study of the hospice operation and its
estimated vertical transportation needs.
B. Inside dimensions of patient-use elevators shall be
not less than five feet four inches (5'4") by eight feet (8')with a
capacity of 3,500 pounds. Cab and hoistway doors shall be not
less than three feet ten inches (3'10") clear opening.
C. Elevators shall be equipped with an automatic
leveling device of the two-way automatic maintaining type
with an accuracy of plus or minus one-half inch.
D. Elevator call buttons, controls and door safety stops
shall be of a type that will not be activated by heat or smoke.
E. Elevator controls, alarm buttons and telephones shall
be accessible to wheelchair occupants and usable by others
with various physical disabilities.
F. Elevator hoistway doors shall be fire rated to maintain
the integrity of the fire-rated shaft enclosure;
3. Chutes and dumbwaiters.
A. Chutes and dumbwaiters may be installed in hospice
facilities as required by the operational program.
B. Linen and trash chutes shall be of fire-resistant
material and shall be installed with flushing ring, vent to
atmosphere and floor drain at the floor of the chute discharge.
An automatic sprinkler shall be provided at the top of each
linen and trash chute.
C. Service openings to chutes shall not be located in
corridors or passageways but shall be located in a room having
a fire-resistant construction of not less than one hour. Doors
to the rooms shall be not less than 3/4-hour labeled doors
equipped with an automatic closing device.
D. Service openings to chutes and other vertical openings
shall have an approved self-closing labeled fire door rating not
less than the fire-resistant rating of the shaft in which the
chute is installed.
E. Chutes shall discharge directly into collection rooms
separate from the incinerator, laundry or other services.
Separate collection rooms shall be provided for trash and for
linen. These rooms shall have a fire-resistant construction
of not less than one hour. Doors to these rooms shall be not
less than 3/4-hour labeled doors equipped with an automatic
closing device.
F. Dumbwaiters, conveyors and material-handling
systems shall not open directly into a corridor or exitway but
shall open into a room enclosed by construction having a fire
resistance of not less than one hour and provided with a 3/4hour labeled fire door with a self-closing device.
G. Where horizontal conveyors and material-handling
systems penetrate fire-rated walls or smoke walls, the
penetrations shall be protected to maintain the integrity of
the wall;
4. General design, finish and life safety requirements.
A. A continuous system of unobstructed corridors,
referred to as required corridors, shall extend through the
enclosed portion of each story of the building, connecting
all rooms and spaces with each other and with all entrances,
exitways and elevators, with the following exceptions: work
suites such as the administrative suite and dietary area,
which are occupied primarily by employed personnel, may
have within them corridors or aisles as considered advisable,
but are not subject to the regulations applicable to required
corridors. Areas may be open to the required corridor system as
permitted by NFPA 101 (1994), The Life Safety Code.
B. The arrangement of the physical plant shall provide
for separation of the administrative/business, service and
public areas from patient service areas.
C. Ceilings shall be at a height of at least eight feet.
Ceilings in corridors, storage rooms, toilet rooms and other
minor rooms shall not be less than seven feet six inches (7'6").
Suspended fixtures located in the path of normal traffic shall
not be less than six feet eight inches (6'8") above the floor.
D. Handrails may be provided on both sides of all
corridors and aisles used by patients and, if provided, corridor
handrails shall have ends return to the wall.
E. New inpatient hospice facilities shall be designed
and constructed in compliance with Chapters Five through
Seven and Chapter Twelve of NFPA 101 (1994), Life Safety Code
and NFPA 99 (1993) Standard for Health Care Facilities, NFPA 13
(1994) Standard for Installation of Sprinkler Systems and NFPA
90A (1993) Standard for the Installation of Air Conditioning and
Ventilation Systems. Section 12-6 of NFPA 101 shall not apply to
these facilities.
F. Hardware on toilet room doors shall be operable from
both the inside and the outside. All toilet room doors shall
provide a net clear opening of not less than 32 inches.
G. The corridor doors from all patient-use areas as well
as all doors through which patients may need to pass for
emergency exit shall be not less than thirty-six (36) inches
wide.
H. Every window in patient-use areas shall be provided
with shades, curtains or drapes. Curtains and drapes shall be
made of fabric which is treated to be or is inherently flameretardant.
I. The floors of toilets, baths, utility rooms and janitor’s
closets shall have smooth, waterproof surfaces which are wearresistant. The floors of kitchens and food preparation areas
shall be waterproof, greaseproof, smooth and resistant to heavy
wear.
J. The walls of all rooms where food and drink are
prepared, served or stored shall have a smooth surface with
painted or equally washable finish. At the base they shall be
waterproof and free from spaces which may harbor insects.
The walls of kitchens, utility rooms, baths, warewashing rooms,
janitor’s closets and spaces with sinks shall have waterproof,
painted, glazed, or similar finishes to a point above the splash
and spray line.
K. The ceilings of all kitchens, sculleries and other rooms
where food and drink are prepared shall be painted with
washable paint.
L. All casework in the facility shall be finished with
at least a sealer on all interior surfaces. Casework with sinks
installed in the counter shall be caulked to provide a watertight
joint between the backsplash and the wall.
M. All floor covering used in inpatient hospice facilities
shall have either Class A or B fire ratings as required by Chapter
Twelve of NFPA 101 (1994), The Life Safety Code.
N. Stairways, ramps, elevator hoistways, light or
ventilation shafts, chutes and other vertical openings between
stories shall be enclosed with construction which is equal
to or greater than the required floor assembly rating of the
building’s construction type.
O. The number of stories in a building housing a
hospice facility shall be determined by counting the number
of occupiable levels in the building regardless of their location
at, above or below grade.
P. Each room or patient-use area shall be conspicuously
and unmistakably identifiable at its entrance by patients,
visitors and staff.
Q. All signage within six feet (6') of the floor shall be
tactile to be usable by visually impaired persons.
R. Fire-resistant ratings—
(I) Definitions—
(a) Fire-separation distance is the distance in feet
measured from the building face to the closest interior lot line,
to the centerline of a street or public way or to an imaginary
line between two (2) buildings on the same property.
(b) Fire-protection rating is the time in hours, or
fractions of an hour, that an opening protective assembly will
resist fire exposure as determined in accordance with the test
procedures set forth in ASTM E119.
(II) Exterior walls with a fire-separation distance less
than five feet (5') shall have a fire-resistant rating of one (1)
hour.
(III) In exterior walls with a fire-separation distance of
three feet or less, no openings will be allowed, from three feet
(3') to five feet (5') no unprotected openings will be allowed,
and protected openings will be allowed with a total aggregate
area of fifteen percent (15%) of the wall surface.
(IV) Approved fire protective assemblies shall be fixed,
self-closing or equipped with approved automatic-closing
devices, a fire-resistant rating of not less than three-quarters
(3/4) of an hour shall be required.
(V) Fire protective assemblies are not required where
outside automatic sprinklers are installed for the protection
of the exterior openings. The sprinklers shall be installed in
accordance with NFPA 13;
5. Structural design.
A. All new facilities and additions to all areas of existing
licensed facilities which undergo major remodeling, in all
their parts, shall be of sufficient strength to resist all stresses
imposed by dead loads, live loads and lateral or uplift forces
such as wind, without exceeding, in any of the structural
materials, the allowable working stress established for these
materials by generally accepted good engineering practice.
B. Foundations shall rest on solid ground or properly
compacted fill and shall be carried to a depth of not less
than one foot below the estimated frost line or shall rest on
leveled rock or load-bearing piles when solid ground is not
encountered. When engineered fill is used, site preparation
and placement of fill shall be done under the direct full-time
supervision of the soils engineer. The soils engineer shall issue
a final report on the compacted fill operation and certify its
compliance with the job specifications. Reasonable care shall
be taken to establish proper soil-bearing values for soil at the
building site. If the bearing capacity of the soil is in question,
a recognized load test may be used to determine the safe
bearing value. Footings, piers and foundation walls shall be
adequately protected against deterioration from the action of
groundwater;
6. Electrical systems.
A. The entire electrical system shall be designed,
installed and tested in compliance with NFPA 70 (1993) The
National Electrical Code and NFPA 99 (1993) Standard for Health
Care Facilities.
B. Emergency lighting shall be provided for exits,
stairs and exit access corridors which shall be supplied by an
emergency service and automatic electric generator or battery
lighting system. This emergency lighting system shall be
equipped with an automatic transfer switch. If battery lights
are used, they shall be wet cell units or other rechargeable-type
batteries equipped with automatic trickle charger. These units
shall be rated at four (4) hours.
C. Patient rooms shall have a minimum general
illumination of ten foot-candles, a night-light and a patient’s
reading light. The general illumination fixtures and the nightlight shall be switched at the patient room door.
D. Ceiling lighting fixtures, if used, shall be of a type
which are shaded or globed to minimize glare.
E. Each patient room shall have not less than one duplex
receptacle on each wall in the room. The spacing of receptacles
around the perimeter of the room shall not be greater than
twelve (12) feet.
F. All occupied areas shall be adequately lighted as
required by the duties performed in the space.
G. Night-lights shall be provided in corridor, stairways
and patient rooms. Toilets adjacent to patient rooms are not
required to have night-lights.
H. An electrically powered communication system shall
be provided which allows staff to respond to patient calls
regardless of patient location.
I. An electrically powered fire alarm system shall be
provided as required by NFPA 101 (1994) The Life Safety Code.
The fire alarm system shall have an emergency back-up source
of electrical power and a direct connection for notifying the
fire department or fire department dispatch service. Fire alarm
manual pull stations shall be provided at each exit and at each
staff workstation in the patient-care units. Smoke detectors
shall be installed in social space rooms which open directly
to the corridor, in the vicinity of any smoke or fire door which
is permitted to be held open by a magnetic hold-open device,
and in the corridors at intervals not exceeding 30 feet.
J. Portable fire extinguishers shall be provided as required
by NFPA 101 (1994) The Life Safety Code and the local authority;
7. Mechanical systems.
A. The heating, ventilation and air-conditioning systems
shall be capable of providing temperature ranges between
72°F–80°F in all patient-care areas. The heating system shall be
capable of maintaining a winter indoor temperature of not less
than 72°F in all nonpatient areas. The air-conditioning system
shall be capable of maintaining a summer indoor temperature
of not more than 80°F in all nonpatient areas.
B. The heating system shall have automatic controls
adequate to provide comfortable conditions in all portions of
the building at all times.
C. Heating, ventilation and air-conditioning systems
installed in inpatient hospice facilities shall be designed,
installed and balanced in compliance with NFPA 90A (1993)
Standard for the Installation of Air Conditioning and Ventilation
Systems, and shall provide the pressure relationships and at
least the minimum air change rates indicated in Table 1.
TABLE 1—VENTILATION REQUIREMENTS
Minimum
Minimum
Pressure
Air Changes of
Total Air
All Air
Relationship
Outdoor Air Per
Changes Per
Exhausted
Air Returned
to Adjacent
Hour Supplied
Hour Supplied
Directly
From This
Area Designation
Areas
to Room
to Room
to Outdoors
Room
Patient Room
E
2
2
Optional
Optional
Patient Area Corridor
and Patient Living Room
P
2
2
Optional
Optional
Soiled Workroom
and Soiled Linen Holding
N
Optional
6
Yes
No
Clean Staff Work Area
P
2
6
Optional
Optional
Toilet Room
N
Optional
6
Yes
No
Clean Linen Storage
P
Optional
2
Optional
Optional
Designated Smoking Area
N
Optional
10
Yes
No
Food Preparation Area
E
2
6
Yes
No
Warewashing
N
Optional
6
Yes
No
Dietary and General Storage
V
Optional
2
Optional
Optional
Linen and Trash Chute Room
N
Optional
6
Yes
No
Medical Gas Storage and
Manifold Rooms
N
Optional
6
Yes
No
Administrative and
Public Areas
E
2
2
Optional
Optional
P = Positive
N = Negative
V = Variable
E = Equal
D. All air-moving, heating, ventilation and airconditioning equipment shall be equipped with at least
one filter located upstream of the conditioning equipment.
If a pre-filter is employed, the pre-filter shall be upstream
of the conditioning equipment and the main filter shall
be located farther downstream. All filters shall be easily
accessible for maintenance. Filter frames shall be durable and
carefully dimensioned and shall provide an airtight fit with the
enclosing ductwork. All joints between the filter segments and
the enclosing ductwork shall be sealed to preclude air leakage.
E. Outside air intakes shall be located no less than 25
feet from exhaust outlets of ventilation systems, combustion
equipment stacks, clinical suction discharges and plumbing
vent stacks or from areas which may collect vehicular exhaust
and other noxious fumes.
F. Corridors shall not be used to supply air to or exhaust
air from any room, except that air from corridors may be used
to ventilate bathrooms, toilet rooms, janitor’s closets and
small electrical or telephone closets opening directly onto
corridors provided that ventilation can be accomplished by the
undercutting of doors. The installation of louvers in corridor
doors is prohibited. The space above the finished ceiling may
be used as a plenum for return air only.
G. Exhaust hoods in meal preparation areas shall comply
with the requirements of NFPA 96 (1994). All hoods and cooktop
surfaces in meal preparation areas shall be equipped with
automatic fire suppression systems, automatic fan controls and
fuel shutoff;
8. Plumbing systems.
A. The entire plumbing system, its design, operation
and maintenance shall comply with the requirements of all
applicable local and state codes including the requirements
set forth in this rule.
B. Plumbing fixtures.
(I) All plumbing fixtures shall be of nonabsorptive
acid-resistant material.
(II) Clinical sinks shall have a bedpan-flushing device
and shall have an integral trap in which the upper portion of a
visible trap seal provides a water surface.
(III) Showers and tubs shall be provided with nonslip
surfaces.
(IV) Water closets in patient areas shall be quiet
operating types.
(V) Stools in patient toilet facilities shall be the
elongated bowl type with nonreturn stops, backflow preventers
and silencers. Seats shall be the split type and white in color.
(VI) Grab bars or handrails shall be provided adjacent
to all bathtubs.
(VII) All lavatories shall be trimmed with valving
operable without the use of hands.
C. Water supply systems.
(I) A reliable source of potable water shall be provided
at the site to supply water in sufficient quantities to meet the
various use demands of the hospice. The source of water shall
have been tested and approved by the Missouri Department of
Natural Resources.
(II) The water supply systems shall be designed to
supply water at sufficient pressure to operate all fixtures and
equipment during maximum demand periods.
(III) Each water service main, branch main, riser and
branch to a group of fixtures shall be valved. Stop valves shall
be provided at each fixture.
(IV) Reduced pressure backflow preventers shall be
installed on water service entrance, hose bibbs, janitors’ sinks,
bedpan-flushing attachments, and on all other fixtures to
which hoses or tubing can be attached. The installation of
backflow preventors shall provide safeguards against waterline
expansion.
(V) The water supply system shall be designed to
provide hot water at each hot water outlet at all times. The
water-heating equipment shall have sufficient capacity to
supply five gallons of water at 120°F per hour per bed for
hospice fixtures and eight gallons per bed for kitchen and
laundry. Lesser capacities may be accepted upon submission of
the calculation for the anticipated demand of all fixtures and
equipment in the building. Hot water at showers and bathing
facilities shall not exceed 110°F. Hot water at handwashing
facilities shall not exceed 120°F. Hot water circulating mains
and risers shall be run from the hot storage tank to a point
directly below the highest fixture at the end of each branch
main.
D. Drainage systems.
(I) All fixtures and equipment shall be connected
through traps to soil and waste piping and to the sewer and
they shall all be properly vented to the outside.
(II) Courts, yards and drives which do not have natural
drainage from the building shall have catch basins and drains
to low ground, storm-water drainage system or dry wells.
(III) The building sanitary drain system shall be piped
in cast iron, steel, copper or plastic.
(IV) Building sewers shall discharge into a community
sewerage system when available. If such a system is not
available, a facility providing sewage treatment shall conform
to the rules of the Department of Natural Resources.
(V) Drainage piping shall not be installed within the
ceiling or exposed in food preparation centers, food service
facilities, food storage areas and clean linen storage rooms;
special precautions shall be taken to protect any of these
areas from possible leakage or condensation from necessary
overhead drainage piping systems. These special precautions
include requiring noncorrosive drip troughs with a minimum
four-inch outside diameter to be installed under the drainage
pipe in the direction of slope to a point where the pipe leaves
the protected space and terminates at that point—usually
at a wall. The trough shall be supported with noncorrosive
strap hangers and screws from the pipe above. Trough joints
and hanging screw penetrations shall be sealed to maintain
watertight integrity throughout.
E. Natural or liquefied petroleum (LP) gas systems.
(I) Where gas-fire equipment is used, all gas piping,
fittings, tanks and specialties shall be provided and installed
in compliance with NFPA 54 (1992), NFPA 58 (1992), and the
instructions of the gas supplier, except where more strict
requirements are stated. Where liquefied petroleum gas (LPG)
is used, compliance with the rules of the Missouri Department
of Agriculture is also required.
(II) Where gas piping enters the building below grade,
it shall have an outside vent as follows: a concrete box shall be
made 18 inches by 18 inches with three-inch thick walls, of a
height to rest on top of the entering gas pipe, and the top of
the box to coming within six inches of top grade. The box shall
be filled with coarse gravel. A one-inch upright vent line shall
be to 1/2 the depth of the box and extend 12 inches above grade
with a screened U-vent looking down. The vent line shall be
anchored securely to the building wall.
(III) Gas outlets and gas-fired equipment shall not be
installed in any patients’ bedrooms.
F. Where a piped central medical gas distribution
system is installed, the oxygen piping, outlets, manifold rooms,
and storage rooms shall be installed in accordance with the
requirements of Chapter 4 of NFPA 99 (1993); and
9. Fire prevention and general operating requirements.
A. The hospice facility shall be maintained in a manner
which provides a clean safe environment for the delivery of
patient care and shall, until remodeled or renovated with
the approval of the Department of Health, remain compliant
with the codes and regulations under which the facility was
constructed.
B. Exitways shall always be maintained free of
obstructions.
C. Curtains, drapes and cubicle curtains shall be
maintained in a manner which does not compromise their
fire-resistant properties.
D. Smoking may be permitted in the patient’s room
by the patient only, and designated smoking areas by others.
Designated smoking areas shall be ventilated as required by
Table 1 of this rule. Modification of the patient room ventilation
system is not required to permit occasional authorized smoking
by a patient.
E. All waste containers shall be of noncombustible
construction.
F. Electrical systems and medical gas systems shall be
tested according to the provisions of NFPA 99 (1993) and shall
be modified as necessary to comply with the operational
requirements of that standard.
(5) General Design and Construction Standards for Existing
Inpatient Hospice Facilities.
(A) Any inpatient hospice facility existing and in continuous
operation prior to the date of October 30, 1996, will upon
receipt of application for licensure, be inspected by the
Department of Health to determine compliance with this rule.
Where existing physical conditions cause strict compliance to
be difficult to achieve, the department may determine that the
intent of the new construction rules has been satisfied through
the establishment of acceptable equivalency conditions. The
provision of fire alarm and detection systems, automatic
extinguishment systems, building compartmentation and the
presence of staff trained consistent with the facility’s disaster
preparedness plan are factors which will be considered in
determining fire safety compliance equivalency. The ability
of the existing facility to meet the programmatic needs of
the patients, their family, staff and public in an accessible
and sanitary environment will be considered in determining
functional equivalency. Existing inpatient hospice facilities
shall provide the department evidence of compliance with
all local regulations and codes as well as evidence that the
existing operation is in good standing with the health facility
licensure programs administered by Department of Social Services/Division of Aging. Existing inpatient hospice facilities
shall be operated and licensed exclusively under the provisions
of section 197.250, RSMo.
AUTHORITY: section 197.270, RSMo 2000.* Original rule filed
March 8, 1996, effective Oct. 30, 1996. Rescinded and readopted:
Filed Jan. 3, 2001, effective Aug. 30, 2001. Amended: Filed Sept. 11,
2007, effective March 30, 2008.
*Original authority: 197.270, RSMo 1992, amended 1993.