19 CSR 30-86.022
Fire Safety and Emergency Preparedness Standards for Residential Care Facilities and Assisted Living Facilities
PURPOSE: This rule establishes fire safety and emergency
preparedness standards for residential care facilities and assisted
living facilities.
PUBLISHER’S NOTE: The secretary of state has determined that the
publication of the entire text of the material which is incorporated
by reference as a portion of this rule would be unduly cumbersome
or expensive. This material as incorporated by reference in this
rule shall be maintained by the agency at its headquarters and
shall be made available to the public for inspection and copying
at no more than the actual cost of reproduction. This note applies
only to the reference material. The entire text of the rule is printed
here.
AGENCY NOTE: All rules relating to long-term care facilities
licensed by the Department of Health and Senior Services are
followed by a Roman Numeral notation which refers to the class
(either class I, II, or III) of standard as designated in section
198.085, RSMo 2000.
(1) Definitions. For the purpose of this rule, the following
definitions shall apply:
(A) Accessible spaces—shall include all rooms, halls, storage
areas, basements, attics, lofts, closets, elevator shafts, enclosed
stairways, dumbwaiter shafts, and chutes;
(B) Area of refuge—a space located in or immediately
adjacent to a path of travel leading to an exit that is protected
from the effects of fire, either by means of separation from
other spaces in the same building or its location, permitting
a delay in evacuation. An area of refuge may be temporarily
used as a staging area that provides some relative safety to its
occupants while potential emergencies are assessed, decisions
are made, and, if applicable, evacuation has begun;
(C) Major renovation—shall include the following:
1. Addition of any room(s), accessible by residents, that
either exceeds fifty percent (50%) of the total square footage
of the facility or exceeds four thousand five hundred (4,500)
square feet;
2. Repairs, remodeling, or renovations that involve
structural changes to more than fifty percent (50%) of the
building;
3. Repairs, remodeling, or renovations that involve
structural changes to more than four thousand five hundred
(4,500) square feet of a smoke section; or
4. If the addition is separated by two- (2-) hour fireresistant construction, only the addition portion shall meet the
requirements for NFPA 13, 1999 edition, sprinkler system, unless
the facility is otherwise required to meet NFPA 13, 1999 edition;
(D) Fire-resistant construction—type of construction in
residential care and assisted living facilities in which bearing
walls, columns, and floors are of noncombustible material in
accordance with NFPA 101, 2000 edition. All load-bearing walls,
floors, and roofs shall have a minimum of a one- (1-) hour fireresistant rating; and
(E) Concealed spaces—shall include areas within the building
that cannot be occupied or used for storage.
(2) General Requirements.
(A) All National Fire Protection Association (NFPA) codes and
standards cited in this rule: NFPA 10, Standard for Portable Fire
Extinguishers, 1998 edition; NFPA 13R, Installation of Sprinkler
Systems, 1996 edition; NFPA 13, Installation of Sprinkler Systems,
1976 edition; NFPA 13 or NFPA 13R, Standard for the Installation of
Sprinkler Systems in Residential Occupancies Up to and Including
Four Stories in Height, 1999 edition; NFPA 13, Standard for the
Installation of Sprinkler Systems, 1999 edition; NFPA 96, Standard
for Ventilation Control and Fire Protection of Commercial Cooking
Operations, 1998 edition; NFPA 101, The Life Safety Code, 2000
edition; NFPA 72, National Fire Alarm Code, 1999 edition; NFPA
72A, Local Protective Signaling Systems, 1975 edition; NFPA 25,
Standard for the Inspection, Testing, and Maintenance of WaterBased Fire Protection Systems, 1998 edition; and NFPA 101A,
Guide to Alternative Approaches to Life Safety, 2001 edition, with
regard to the minimum fire safety standards for residential
care facilities and assisted living facilities are incorporated
by reference in this rule and available for purchase from the
National Fire Protection Agency, 1 Batterymarch Park, Quincy,
MA 02269-9101; www.nfpa.org; by telephone at (617) 770-3000 or
1-800-344-3555. This rule does not incorporate any subsequent
amendments or additions to the materials listed above. This
rule does not prohibit facilities from complying with the
standards set forth in newer editions of the incorporated
by reference material listed in this subsection of this rule, if
approved by the department.
(B) Facilities that were complying prior to the effective date of
this rule with prior editions of the NFPA provisions referenced
in this rule shall be permitted to continue to comply with the
earlier editions, as long as there is not an imminent danger to
the health, safety, or welfare of any resident or a substantial
probability that death or serious physical harm would result as
determined by the department.
(C) All facilities shall notify the department immediately
after the emergency is addressed if there is a fire in the facility
or premises and shall submit a complete written fire report to
the department within seven (7) days of the fire, regardless of
the size of the fire or the loss involved. II/III
(D) The department shall have the right of inspection of any
portion of a building in which a licensed facility is located
unless the unlicensed portion is separated by two- (2-) hour
fire-resistant construction. No section of the building shall
present a fire hazard. I/II
(E) Following the discovery of any fire, the facility shall
monitor the area and/or the source of the fire for a twenty-four-
(24-) hour period. This monitoring shall include, at a minimum,
hourly visual checks of the area. These hourly visual checks
shall be documented. I/II
(F) The facility shall maintain the exterior premises in a
manner as to provide for fire safety. II
(G) Residential care facilities that accept deaf residents shall
have appropriate assistive devices to enable each deaf person
to negotiate a path to safety, including, but not limited to,
visual or tactile alarm systems. II/III
(H) Facilities shall not use space under stairways to store
combustible materials. I/II
(3) Fire Extinguishers.
(A) Fire extinguishers shall be provided at a minimum of one
(1) per floor, so that there is no more than seventy-five feet (75')
travel distance from any point on that floor to an extinguisher.
I/II
(B) All new or replacement portable fire extinguishers shall
be ABC-rated extinguishers, in accordance with the provisions
of NFPA 10, 1998 edition. A K-rated extinguisher or its equivalent
shall be used in lieu of an ABC-rated extinguisher in the kitchen
cooking areas. II
(C) Fire extinguishers shall have a rating of at least:
1. Ten pounds (10 lbs.), ABC-rated or the equivalent, in or
within fifteen feet (15') of hazardous areas as defined in 19 CSR
30-83.010; and
2. Five pounds (5 lbs.), ABC-rated or the equivalent, in other
areas. II
(D) All fire extinguishers shall bear the label of the
Underwriters’ Laboratories (UL) or the Factory Mutual (FM)
Laboratories and shall be installed and maintained in
accordance with NFPA 10, 1998 edition. This includes the
documentation and dating of a monthly pressure check. II/III
(4) Range Hood Extinguishing Systems.
(A) In facilities licensed on or before July 11, 1980, or in any
facility with fewer than twenty-one (21) beds, the kitchen shall
provide either:
1. An approved automatic range hood extinguishing
system properly installed and maintained in accordance with
NFPA 96, 1998 edition; or
SENIOR SERVICES
2. A portable fire extinguisher of at least ten pounds
(10 lbs.) ABC-rated, or the equivalent, in the kitchen area in
accordance with NFPA 10, 1998 edition. II/III
(B) In licensed facilities with a total of twenty-one (21) or
more licensed beds and whose application was filed after July
11, 1980, and prior to October 1, 2000:
1. The kitchen shall be provided with a range hood and an
approved automatic range hood extinguishing system unless
the facility has an approved sprinkler system. Facilities with
range hood systems shall continue to maintain and test these
systems; and
2. The extinguishing system shall be installed, tested, and
maintained in accordance with NFPA 96, 1998 edition. II/III
(C) The range hood and its extinguishing system shall be
certified at least twice annually in accordance with NFPA 96,
1998 edition. II/III
(5) Fire Drills and Emergency Preparedness.
(A) All facilities shall have a written plan to meet potential
emergencies or disasters and shall request consultation and
assistance annually from a local fire unit for review of fire
and evacuation plans. If the consultation cannot be obtained,
the facility shall inform the state fire marshal in writing and
request assistance in review of the plan. An up-to-date copy
of the facility’s entire plan shall be provided to the local
jurisdiction’s emergency management director. II/III
(B) The plan shall include, but is not limited to, the following:
1. A phased response ranging from relocation of residents
to an immediate area within the facility; relocation to an
area of refuge, if applicable; or to total building evacuation.
This phased response part of the plan shall be consistent with
the direction of the local fire unit or state fire marshal and
appropriate for the fire or emergency;
2. Written instructions for evacuation of each floor
including evacuation to areas of refuge, if applicable, and a
floor plan showing the location of exits, fire alarm pull stations,
fire extinguishers, and any areas of refuge;
3. Evacuating residents, if necessary, from an area of
refuge to a point of safety outside the building;
4. The location of any additional water sources on the
property such as cisterns, wells, lagoons, ponds, or creeks;
5. Procedures for the safety and comfort of residents
evacuated;
6. Staffing assignments;
7. Instructions for staff to call the fire department or other
outside emergency services;
8. Instructions for staff to call alternative resource(s) for
housing residents, if necessary;
9. Administrative staff responsibilities; and
10. Designation of a staff member to be responsible for
accounting for all residents’ whereabouts. II/III
(C) The written plan shall be accessible at all times and
an evacuation diagram shall be posted on each floor in
a conspicuous place so that employees and residents can
become familiar with the plan and routes to safety. II/III
(D) A minimum of twelve (12) fire drills shall be conducted
annually with at least one (1) every three (3) months on
each shift. At least four (4) of the required fire drills must be
unannounced to residents and staff, excluding staff who are
assigned to evaluate staff and resident response to the fire drill.
The fire drills shall include a resident evacuation at least once
a year. II/III
(E) The facility shall keep a record of all fire drills. The record
shall include the time, date, personnel participating, length of
time to complete the fire drill, and a narrative notation of any
special problems. III
(F) The fire alarm shall be activated during all fire drills
unless the drill is conducted between 9 p.m. and 6 a.m., when a
facility-generated predetermined message is acceptable in lieu
of the audible and visual components of the fire alarm. II/III
(6) Fire Safety Training Requirements.
(A) The facility shall ensure that fire safety training is
provided to all employees:
1. During employee orientation;
2. At least every six (6) months; and
3. When training needs are identified as a result of fire drill
evaluations. II/III
(B) The training shall include, but is not limited to, the
following:
1. Prevention of fire ignition, detection of fire, and control
of fire development;
2. Confinement of the effects of fire;
3. Procedures for moving residents to an area of refuge, if
applicable;
4. Use of alarms;
5. Transmission of alarms to the fire department;
6. Response to alarms;
7. Isolation of fire;
8. Evacuation of immediate area and building;
9. Preparation of floors and facility for evacuation; and
10. Use of the evacuation plan as required by section (5) of
this rule. II/III
(7) Exits, Stairways, and Fire Escapes.
(A) Each floor of a facility shall have at least two (2)
unobstructed exits remote from each other. I/II
1. For a facility whose plans were approved on or before
December 31, 1987, or a facility licensed for twenty (20) or
fewer beds, one (1) of the required exits from a multi-story
facility shall be an outside stairway or an enclosed stairway
that is separated by one- (1-) hour rated construction from
each floor with an exit leading directly to the outside at grade
level. Existing plaster or gypsum board of at least one-half
inch (1/2") thickness may be considered equivalent to one- (1-)
hour rated construction. The other required exit may be an
interior stairway leading through corridors or passageways to
outside or to a two- (2-) hour rated horizontal exit as defined
by paragraph 3.3.61 of the 2000 edition NFPA 101. Neither of
the required exits shall lead through a furnace or boiler room.
Neither of the required exits shall be through a resident’s
bedroom, unless the bedroom door cannot be locked. I/II
2. For a facility whose plans were approved after December
31, 1987, for more than twenty (20) beds, the required exits
shall be doors leading directly outside, one- (1-) hour enclosed
stairs or outside stairs or a two- (2-) hour rated horizontal exit
as defined by paragraph 3.3.61 of 2000 edition NFPA 101. The
one- (1-) hour enclosed stairs shall exit directly outside at grade.
Access to these shall not be through a resident bedroom or a
hazardous area. I/II
3. Only one (1) of the required exits may be a two- (2-) hour
rated horizontal exit. I/II
(B) In facilities with plans approved after December 31,
1987, doors to resident use rooms shall not be more than one
hundred feet (100') from an exit. In facilities equipped with a
complete sprinkler system in accordance with NFPA 13 or NFPA
13R, 1999 edition, the exit distance may be increased to one
hundred fifty feet (150'). Dead-end corridors shall not exceed
thirty feet (30') in length. II
(C) In residential care facilities and facilities formerly
licensed as residential care facilities II, floors housing residents
who require the use of a walker, wheelchair, or other assistive
devices or aids, or who are blind, must have two (2) accessible
exits to grade or such residents must be housed near accessible
exits as specified in 19 CSR 30-86.042(33) for residential care
facilities and 19 CSR 30-86.043(31) for facilities formerly licensed
as residential care facilities II unless otherwise prohibited by
19 CSR 30-86.045 or 19 CSR 30-86.047, facilities equipped with
a complete sprinkler system, in accordance with NFPA 13 or
NFPA 13R, 1999 edition, with sprinkler coverage in attics, and
smoke partitions, as defined by subsection (10)(I) of this rule,
may house such residents on floors that do not have accessible
exits to grade if each required exit is equipped with an area of
refuge as defined and described in subsections (1)(B) and (7)(D)
of this rule. I/II
(D) An “area of refuge” shall have—
1. An area separated by one- (1-) hour rated smoke walls,
from the remainder of the building. This area must have direct
access to the exit stairway or access the stair through a section
of the corridor that is separated by smoke walls from the
remainder of the building. This area may include no more than
two (2) resident rooms;
2. A two- (2-) way communication or intercom system with
both visible and audible signals between the area of refuge
and the bottom landing of the exit stairway, attendants’ work
area, or other primary location as designated in the written
plan for fire drills and evacuation;
3. Instructions on the use of the area during emergency
conditions that are located in the area of refuge and
conspicuously posted adjoining the communication or
intercom system;
4. A sign at the entrance to the room that states “AREA
OF REFUGE IN CASE OF FIRE” and displays the international
symbol of accessibility;
5. An entry or exit door that is at least a one and threefourths inch (1 3/4") solid core wood door or has a fire
protection rating of not less than twenty (20) minutes with
smoke seals and positive latching hardware. These doors shall
not be lockable;
6. A sign conspicuously posted at the bottom of the exit
stairway with a diagram showing each location of the areas
of refuge;
7. Emergency lighting for the area of refuge; and
8. The total area of the areas of refuge on a floor shall
equal at least twenty (20) square feet for each resident who is
blind or requires the use of a wheelchair or walker housed on
the floor. II
(E) If it is necessary to lock exit doors, the locks shall not
require the use of a key, tool, special knowledge, or effort to
unlock the door from inside the building. Only one (1) lock shall
be permitted on each door. Delayed egress locks complying
with section 7.2.1.6.1 of the 2000 edition NFPA 101 shall be
permitted, provided that not more than one (1) such device
is located in any egress path. Self-locking exit doors shall be
equipped with a hold-open device to permit staff to reenter the
building during the evacuation. I/II
(F) If it is necessary to lock resident room doors, the locks
shall not require the use of a key, tool, special knowledge, or
effort to unlock the door from inside the room. Only one (1) lock
shall be permitted on each door. Every resident room door shall
be designed to allow the door to be opened from the outside
during an emergency when locked. The facility shall ensure
that facility staff have the means or mechanisms necessary to
open resident room doors in case of an emergency. I/II
(G) All stairways and corridors shall be easily negotiable and
shall be maintained free of obstructions. II
(H) Outside stairways shall be constructed to support
residents during evacuation and shall be continuous to the
ground level. Outside stairways shall not be equipped with
a counter-balanced device. They shall be protected from or
cleared of ice or snow. II/III
(I) Facilities with three (3) or more floors shall comply with
the provisions of Chapter 320, RSMo which requires outside
stairways to be constructed of iron or steel. II
(J) Fire escapes constructed on or after November 13, 1980,
whether interior or exterior, shall be thirty-six inches (36")
wide, shall have eight-inch (8") maximum risers, nine-inch
(9") minimum tread, no winders, maximum height between
landings of twelve feet (12'), minimum dimensions of landings
of forty-four inches (44"), landings at each exit door, and
handrails on both sides and be of sturdy construction, using at
least two-inch (2") lumber. Exit doors to these fire escapes shall
be at least thirty-six inches (36") wide and the door shall swing
outward. II/III
(K) If a ramp is required to meet residents’ needs under 19
CSR 30-86.042, the ramp shall have a maximum slope of one to
twelve (1:12) leading to grade. II/III
(8) Exit Signs.
(A) Signs bearing the word EXIT in plain, legible letters shall
be placed at each required exit, except at doors directly from
rooms to exit passageways or corridors. Letters of all exit signs
shall be at least six inches (6") high and principle strokes threefourths of an inch (3/4") wide, except that letters of internally
illuminated exit signs shall not be less than four inches (4")
high. II
(B) Directional indicators showing the direction of travel
shall be placed in corridors, passageways, or other locations
where the direction of travel to reach the nearest exit is not
apparent. II/III
(C) All required exit signs and directional indicators shall
be positioned so that both normal and emergency lighting
illuminates them. II/III
(9) Complete Fire Alarm Systems.
(A) All facilities shall have a complete fire alarm system
installed in accordance with NFPA 101, Section 18.3.4, 2000
edition. The complete fire alarm shall automatically transmit to
the fire department, dispatching agency, or central monitoring
company. The complete fire alarm system shall include visual
signals and audible alarms that can be heard throughout
the building and a main panel that interconnects all alarmactivating devices and audible signals. Manual pull stations
shall be installed at or near each required attendant’s station
and each required exit. I/II
1. For facilities with a sprinkler system in accordance with
NFPA 13, 1999 edition, smoke detectors interconnected to the
complete fire alarm system shall be installed in all corridors
and spaces open to corridors. Smoke detectors shall be no more
than thirty feet (30') apart with no point on the ceiling more
than twenty-one feet (21') from a smoke detector. I/II
A. In facilities licensed prior to November 13, 1980,
smoke detectors located every fifty feet (50') will be acceptable
if the distance is within the manufacturer’s specifications. I/II
2. For facilities with a sprinkler system in accordance with
NFPA 13R, 1999 edition, smoke detectors interconnected to the
complete fire alarm system shall be installed in all corridors,
spaces open to corridors, and in accessible spaces not protected
by the sprinkler system, as required by NFPA 72, 1999 edition.
Smoke detectors shall be no more than thirty feet (30') apart
SENIOR SERVICES
with no point on the ceiling more than twenty-one feet (21')
from a smoke detector. Smoke detectors shall not be installed
in areas where environmental influences may cause nuisance
alarms. Such areas include, but are not limited to, kitchens,
laundries, bathrooms, mechanical air handling rooms, and
attic spaces. In these areas, heat detectors interconnected to
the complete fire alarm system shall be installed. Bathrooms
not exceeding fifty-five (55) square feet and clothes closets,
linen closets, and pantries not exceeding twenty-four (24)
square feet are exempt from having any detection device if the
walls and ceilings are surfaced with limited-combustible or
non-combustible material as defined in NFPA 101, 2000 edition.
Concealed spaces of noncombustible or limited combustible
construction are not required to have detection devices. These
spaces may have limited access but cannot be occupied or used
for storage. I/II
A. In facilities licensed prior to November 13, 1980,
smoke detectors located every fifty feet (50') will be acceptable
if the distance is within the manufacturer’s specifications. I/II
3. For facilities that are not required to have a sprinkler
system, smoke detectors interconnected to the complete fire
alarm system shall be installed in all accessible spaces, as
required by NFPA 72, 1999 edition, within the facility. Smoke
detectors shall be no more than thirty feet (30') apart with no
point on the ceiling more than twenty-one feet (21') from a
smoke detector. Smoke detectors shall not be installed in areas
where environmental influences may cause nuisance alarms.
Such areas include, but are not limited to, kitchens, laundries,
bathrooms, mechanical air handling rooms, and attic spaces.
In these areas, heat detectors interconnected to the fire alarm
system shall be installed. Bathrooms not exceeding fifty-five
(55) square feet and clothes closets, linen closets, and pantries
not exceeding twenty-four (24) square feet are exempt from
having any detection device if the walls and ceilings are
surfaced with limited-combustible or noncombustible material
as defined in NFPA 101, 2000 edition. Concealed spaces of
noncombustible or limited-combustible construction are not
required to have detection devices. These spaces may have
limited access but cannot be occupied or used for storage. I/II
A. In facilities licensed prior to November 13, 1980,
smoke detectors located every fifty feet (50') will be acceptable
if the distance is within the manufacturer’s specifications. I/II
(B) Facilities that are required to install a sprinkler system in
accordance with section (11) of this rule shall comply with the
following requirements:
1. Until the required sprinkler system is installed, each
resident room or any room designated for sleeping shall
be equipped with at least one (1) battery-powered smoke
alarm installed, tested, and maintained in accordance with
manufacturer’s specifications. In addition, the facility shall be
equipped with interconnected heat detectors installed, tested,
and maintained in accordance with NFPA 72, 1999 edition, with
detectors in all areas subject to nuisance alarms, including, but
not limited to, kitchens, laundries, bathrooms, mechanical air
handling rooms, and attic spaces. I/II
A. The facility shall maintain a written record of the
monthly testing and battery changes. The written records shall
be retained for one (1) year. I/II
B. Upon discovery of a fault with any detector or alarm,
the facility shall correct the fault. I/II
(C) All facilities shall test and maintain the complete fire
alarm system in accordance with NFPA 72, 1999 edition. I/II
(D) All facilities shall have inspections and written
certifications of the complete fire alarm system completed by
an approved qualified service representative in accordance
with NFPA 72, 1999 edition, at least annually. I/II
(E) Facilities shall test by activating the complete fire alarm
system at least once a month. I/II
(F) Facilities shall maintain a record of the complete fire alarm
tests, inspections, and certifications required by subsections (9)
(C) and (D) of this rule. III
(G) Upon discovery of a fault with the complete fire alarm
system, the facility shall correct the fault. I/II
(H) When a complete fire alarm system is to be out-of-service
for more than four (4) hours in a twenty-four- (24-) hour period,
the facility shall immediately notify the department and the
local fire authority and implement an approved fire watch in
accordance with NFPA 101, 2000 edition, until the complete fire
alarm system has returned to full service. I/II
(I) The complete fire alarm system shall be activated by all
of the following: sprinkler system flow alarm, smoke detectors,
heat detectors, manual pull stations, and activation of the
rangehood extinguishment system. II/III
(10) Protection from Hazards.
(A) In assisted living facilities and residential care facilities
licensed on or after November 13, 1980, for more than twelve
(12) beds, hazardous areas shall be separated by construction
of at least a one- (1-) hour fire-resistant rating. In facilities
equipped with a complete fire alarm system, the one- (1-) hour
fire separation is required only for furnace or boiler rooms.
Hazardous areas equipped with a complete sprinkler system
are not required to have this one- (1-) hour fire separation.
Doors to hazardous areas shall be self-closing and shall be kept
closed unless an electromagnetic hold-open device is used
which is interconnected with the fire alarm system. When the
sprinkler option is chosen, the areas shall be separated from
other spaces by smoke-resistant partitions and doors. The doors
shall be self-closing or automatic-closing. Facilities formerly
licensed as residential care facility I or II, and existing prior to
November 13, 1980, shall be exempt from this requirement. II
(B) The storage of unnecessary combustible materials in
any part of a building in which a licensed facility is located is
prohibited. I/II
(C) Electric or gas clothes dryers shall be vented to the
outside. Lint traps shall be cleaned regularly to protect against
fire hazard. II/III
(D) In facilities that are required to comply with the
requirements of 19 CSR 30-86.043 and were formerly licensed as
residential care facilities II on or after November 13, 1980, each
floor shall be separated by construction of at least a one- (1-)
hour fire-resistant rating. Buildings equipped with a complete
sprinkler system may have a nonrated smoke separation barrier
between floors. Doors between floors shall be a minimum of
one and three-fourths inches (1 3/4") thick and be solid core
wood doors or metal doors with an equivalent fire rating. II
(E) In facilities licensed prior to November 13, 1980, and
multi-storied residential care facilities formerly licensed as
residential care facilities I licensed on or after November 13,
1980, there shall be a smoke separation barrier between the
floors of resident-use areas and any floor below the residentuse area. This shall consist of a solid core wood door or metal
door with an equivalent fire rating at the top or the bottom
of the stairs. There shall not be a transom above the door that
would permit the passage of smoke. II
(F) Atriums open between floors will be permitted if resident
room corridors are separated from the atrium by one- (1-) hour
rated smoke walls. These corridors must have access to at
least one (1) of the required exits without traversing any space
opened to the atrium. II
(G) All doors providing separation between floors shall have
a self-closing device attached. If the doors are to be held open,
electromagnetic hold-open devices shall be used that are
interconnected with either an individual smoke detector or a
complete fire alarm system. II
(H) All facilities shall be divided into at least two (2) smoke
sections with each section not exceeding one hundred fifty feet
(150') in length or width. If the floor’s dimensions do not exceed
seventy-five feet (75') in length or width, a division of the floor
into two (2) smoke sections will not be required. II
(I) In facilities whose plans were approved or which were
initially licensed after December 31, 1987, for more than twenty
(20) beds and all facilities licensed after August 28, 2007, each
smoke section shall be separated by one- (1-) hour fire-rated
smoke partitions. The smoke partitions shall be continuous
from outside wall-to-outside wall and from floor-to-floor or
floor-to-roof deck. All doors in this wall shall be at least twenty-
(20-) minute fire-rated or its equivalent, self-closing, and
may be held open only if the door closes automatically upon
activation of the complete fire alarm system. II
(J) In all facilities that were initially licensed on or prior to
December 31, 1987, and all facilities licensed for twenty (20)
or fewer beds prior to August 28, 2007, each smoke section
shall be separated by a one- (1-) hour fire-rated smoke partition
that extends from the inside portion of an exterior wall to
the inside portion of an exterior wall and from the floor to
the underside of the floor or roof deck above, through any
concealed spaces, such as those above suspended ceilings, and
through interstitial structural and mechanical spaces. Smoke
partitions shall be permitted to terminate at the underside of a
monolithic or suspending ceiling system where the following
conditions are met: The ceiling system forms a continuous
membrane, a smoketight joint is provided between the top of
the smoke partition and the bottom of the suspended ceiling
and the space above the ceiling is not used as a plenum. Smoke
partition doors shall be at least twenty- (20-) minute fire-rated
or its equivalent, self-closing, and may be held open only if the
door closes automatically upon activation of the complete fire
alarm system. II
(K) Facilities whose plans were approved or which were
initially licensed after December 31, 1987, for more than twenty
(20) beds which do not have a sprinkler system, shall have one-
(1-) hour rated corridor walls with one and three-quarters inch
(1 3/4") solid core wood doors or metal doors with an equivalent
fire rating. II
(L) If two (2) or more levels of long-term care or two (2)
different businesses are located in the same building, the entire
building shall meet either the most strict construction and fire
safety standards for the combined facility or the facilities shall
be separated from the other(s) by two- (2-) hour fire-resistant
construction. In buildings equipped with a complete sprinkler
system in accordance with NFPA 13 or NFPA 13R, 1999 edition,
this separation may be rated at one (1) hour. II
(11) Sprinkler Systems.
(A) Facilities licensed on or after August 28, 2007, or any
section of a facility in which a major renovation has been
completed on or after August 28, 2007, shall install and
maintain a complete sprinkler system in accordance with NFPA
13, 1999 edition. I/II
(B) Facilities that have a sprinkler system installed prior to
August 28, 2007, shall inspect, maintain, and test these systems
in accordance with the requirements that were in effect for
such facilities on August 27, 2007. I/II
(C) All residential care facilities, and assisted living facilities
that do not admit or retain a resident with a physical,
cognitive, or other impairment that prevents the individual
from safely evacuating the facility with minimal assistance,
that were licensed prior to August 28, 2007, with more than
twenty (20) residents, and do not have an approved sprinkler
system in accordance with NFPA 13, 1999 edition, or NFPA 13R,
1999 edition, shall have until December 31, 2012, to install an
approved sprinkler system in accordance with NFPA 13 or 13R,
1999 edition. I/II
1. The department shall grant exceptions to this
requirement if the facility meets Chapter 33 of NFPA 101, 2000
edition, and the evacuation capability of the facility meets
the standards required in NFPA 101A, Guide to Alternative
Approaches to Life Safety, 2001 edition. I/II
(D) Single-story assisted living facilities that provide care
to one (1) or more residents with a physical, cognitive, or
other impairment that prevents the individual from safely
evacuating the facility with minimal assistance shall install
and maintain an approved sprinkler system in accordance with
NFPA 13R, 1999 edition. I/II
(E) Multi-level assisted living facilities that provide care
to one (1) or more residents with a physical, cognitive, or
other impairment that prevents the individual from safely
evacuating the facility with minimal assistance shall install
and maintain an approved sprinkler system in accordance with
NFPA 13, 1999 edition. I/II
(F) All facilities shall have inspections and written
certifications of the approved sprinkler system completed by an
approved qualified service representative in accordance with
NFPA 25, 1998 edition. The inspections shall be in accordance
with the provisions of NFPA 25, 1998 edition, with certification
at least annually by a qualified service representative. I/II
(G) When a sprinkler system is to be out-of-service for
more than four (4) hours in a twenty-four- (24-) hour period,
the facility shall immediately notify the department and
implement an approved fire watch in accordance with NFPA
101, 2000 edition, until the sprinkler system has been returned
to full service. I/II
(12) Emergency Lighting.
(A) Emergency lighting of sufficient intensity shall be
provided for exits, stairs, resident corridors, and required
attendants’ station. II
(B) The lighting shall be supplied by an emergency service, an
automatic emergency generator, or battery-operated lighting
system. This emergency lighting system shall be equipped with
an automatic transfer switch. II
(C) If battery-powered lights are used, they shall be capable
of operating the light for at least one and one-half (1 1/2) hours.
II
(13) Interior Finish and Furnishings.
(A) In a facility licensed on or after November 13, 1980, for
more than twelve (12) beds, wall and ceiling surfaces of all
occupied rooms and all exitways shall be classified either Class
A or B interior finish as defined in NFPA 101, 2000 edition. II
(B) In facilities licensed prior to November 13, 1980, all
wall and ceiling surfaces shall be smooth and free of highly
combustible materials. II
(C) In facilities licensed for more than twelve (12) beds,
the new or replacement floor covering and carpeting in
buildings that do not have a sprinkler system shall be Class I in
accordance with NFPA 253, 2000 edition. II/III
(D) All curtains and drapes in a licensed facility shall be
certified or treated to be flame-resistant as defined in NFPA 101,
SENIOR SERVICES
2000 edition. II
(14) Smoking.
(A) Smoking shall be permitted in designated areas only.
Areas where smoking is permitted shall be designated as
such and shall be supervised either directly or by a resident
informing an employee of the facility that the area is being
used for smoking. II/III
(B) Ashtrays shall be made of noncombustible material and
safe design and shall be provided in all areas where smoking
is permitted. II/III
(C) The contents of ashtrays shall be disposed of properly in
receptacles made of noncombustible material. II/III
(15) Trash and Rubbish Disposal.
(A) Only metal or UL- or FM-fire-resistant rated wastebaskets
shall be used for trash. II
(B) Trash shall be removed from the premises as often as
necessary to prevent fire hazards and public health nuisance. II
(C) No trash shall be burned within fifty feet (50') of any
facility except in an approved incinerator. I/II
(D) Trash may be burned only in a masonry or metal
container. II
(E) The container shall be equipped with a metal cover with
openings no larger than one-half inch (1/2") in size. III
(16) Standards for Designated Separated Areas.
(A) When a resident resides among the entire general
population of the facility, the facility shall take necessary
measures to provide such residents with the opportunity to
explore the facility and, if appropriate, its grounds. When a
resident resides within a designated, separated area that is
secured by limited access, the facility shall take necessary
measures to provide such residents with the opportunity to
explore the separated area and, if appropriate, its grounds. If
enclosed or fenced courtyards are provided, residents shall
have reasonable access to such courtyards. Enclosed or fenced
courtyards that are accessible through a required exit door
shall be large enough to provide an area of refuge for fire safety
at least thirty feet (30') from the building. Enclosed or fenced
courtyards that are accessible through a door other than a
required exit shall have no size requirements. II
(B) The facility shall provide freedom of movement for the
residents to common areas and to their personal spaces. The
facility shall not lock residents out of or inside their rooms. I/II
(C) The facility may allow resident room doors to be locked
providing the residents request to lock their doors. Any lock
on a resident room door shall not require the use of a key, tool,
special knowledge, or effort to lock or unlock the door from
inside the resident’s room. Only one (1) lock shall be permitted
on each door. The facility shall ensure that facility staff has the
means or mechanisms necessary to open resident room doors
in case of an emergency. I/II
(D) The facility may provide a designated, separated area
where residents, who are mentally incapable of negotiating
a pathway to safety, reside and receive services and which is
secured by limited access if the following conditions are met:
1. Dining rooms, living rooms, activity rooms, and other
such common areas shall be provided within the designated,
separated area. The total area for common areas within the
designated, separated area shall be equal to at least forty (40)
square feet per resident; II/III
2. Doors separating the designated, separated area from
the remainder of the facility or building shall not be equipped
with locks that require a key to open; I/II
3. If locking devices are used on exit doors egressing the
facility or on doors accessing the designated, separated area,
delayed egress magnetic locks shall be used. These delayed
egress devices shall comply with the following:
A. The lock must unlock when the fire alarm is activated;
B. The lock must unlock when the power fails;
C. The lock must unlock within thirty (30) seconds
after the release device has been pushed for at least three (3)
seconds, and an alarm must sound adjacent to the door;
D. The lock must be manually reset and cannot
automatically reset; and
E. A sign shall be posted on the door that reads: PUSH
UNTIL ALARM SOUNDS, DOOR CAN BE OPENED IN 30 SECONDS;
and I/II
4. The delayed egress magnetic locks may also be released
by a key pad located adjacent to the door for routine use by
staff. I/II
(17) Oxygen storage shall be in accordance with NFPA 99, 1999
Edition. II/III
AUTHORITY: sections 198.073, 198.074, and 198.076, RSMo Supp.
2011.* This rule originally filed as 13 CSR 15-15.022. Original rule
filed July 13, 1983, effective Oct. 13, 1983. Emergency amendment
filed Aug. 1, 1984, effective Aug. 13, 1984, expired Dec. 10, 1984.
Amended: Filed Sept. 12, 1984, effective Dec. 13, 1984. Amended:
Filed May 13, 1987, effective Aug. 13, 1987. Amended: Filed Aug. 1,
1988, effective Nov. 10, 1988. Amended: Filed Feb. 28, 2000, effective
Sept. 30, 2000. Moved to 19 CSR 30-86.022, effective Aug. 28, 2001.
Amended: Filed Aug. 16, 2004, effective Feb. 28, 2005. Amended:
Filed Aug. 1, 2005, effective Jan. 30, 2006. Amended: Filed Aug. 23,
2006, effective April 30, 2007. Emergency amendment filed Nov.
24, 2008, effective Dec. 4, 2008, expired June 1, 2009. Amended:
Filed Nov. 24, 2008, effective May 30, 2009. Amended: Filed March
15, 2012, effective Oct. 30, 2012. **
*Original authority: 198.073, RSMo 1979, amended 1984, 1992, 1999, 2006; 198.074,
RSMo 2007; and 198.076, RSMo 1979, amended 1984, 2007.
**Pursuant to Executive Order 21-07, 19 CSR 30-86.022, section (3), subsections (4)(A), (4)(C), (9)(C),
(9)(D), (11)(D), (11)(E), and (11)(F) was suspended from April 23, 2020 through May 1, 2021. Pursuant
to Executive Order 21-09, 19 CSR 30-86.022, subsection (5)(D) and section 198.074.2-4, RSMo was
suspended from April 23, 2020 through December 31, 2021.