19 CSR 30-90.070
Fire Safety and Facility Physical Requirements
PURPOSE: This rule establishes the minimum physical and maintenance requirements
for facilities in which adult day care programs are operated.
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule
would be unduly cumbersome or expensive.
This material as incorporated by reference in
this rule shall be maintained by the agency at
its headquarters and shall be made available
to the public for inspection and copying at no
more than the actual cost of reproduction.
This note applies only to the reference material. The entire text of the rule is printed
here.
(1) Facility Physical Requirements.
(A) The adult day care program building
shall be safe and suitable for participants.
The building in which the program is located
shall be clean, of sound construction and
maintained in good repair.
(B) Minimum space requirements shall be
eighty (80) square feet per participant, for up
to twenty (20) participants and an additional
fifty (50) square feet per each additional participant. Space requirements do not include
office space, bathrooms, storage, examining
rooms or dining rooms, unless the latter is
also used for activities. For associated adult
day care programs, the required space shall
be designated and in excess of the particular
facility’s required licensed space for providing long-term care or medical care. For adult
day health care programs, the required space,
regardless of the number of participants, shall
not be less than three hundred twenty (320)
square feet of space.
(C) The facility shall have a room of sufficient size to meet the needs of the participants
based on minimum standards where all of the
participants can gather as well as rooms or
divided areas for small group activities,
including a quiet area for rest, which contains
at least one (1) bed for temporary use by participants when needed.
(D) Furniture shall be of a size and design
so that it is easily used by persons with limited agility. It shall be sturdy and secure so
that it cannot easily tip when used for support
while walking or sitting. At a minimum, the
following shall be provided:
1. One (1) chair for each participant and
staff person;
2. Table space adequate for all participants to be served a meal at a table at the
same time;
3. Reclining lounge chairs or other sturdy comfortable furniture, the number to be
determined by the needs of the participants;
and
4. At least one (1) bed with adequate
privacy in a quiet area to be available for temporary use by participants as needed.
(E) Equipment and supplies shall be adequate to meet the needs of participants
including items necessary for personal care
and materials to encourage activities among
participants. The activity materials shall be
geared to the interests and backgrounds of the
participants.
(F) Ventilation by natural or mechanical
means shall be provided. All screen doors
shall be equipped with self-closing devices
and shall fit tightly. Doors and windows and
other openings to the outside shall be
screened when necessary to prevent entrance
of insects and vermin.
(G) The heating system for adult day care
facilities initially licensed prior to December
1, 2004 shall be in compliance with the applicable provisions of the 2000 Life Safety Code
for existing occupancies (NFPA 101), incorporated by reference in this rule, as published
by the National Fire Protection Agency, 1
Batterymarch Park, PO Box 9101, Quincy,
MA 02269-9101 and all state and local codes.
This rule does not incorporate any subsequent amendments or additions. Heating systems for adult day care facilities initially
licensed on or after December 1, 2004 shall
be in compliance with the applicable provisions of the 2000 Life Safety Code for New
Day Care Occupancies, incorporated by reference in this rule, as published by the
National Fire Protection Agency, 1 Batterymarch Park, PO Box 9101, Quincy, MA
02269-9101 and all state and local codes.
This rule does not incorporate any subsequent amendments or additions. Exposed
heating pipes, hot water pipes or radiators in
rooms and areas used by participants shall be
covered or protected, and insulated when
appropriate. Portable space heaters shall not
be used. Room temperatures shall be maintained between sixty-eight degrees Fahrenheit
(68°F) and eighty-five degrees Fahrenheit
(85°F) in all seasons. The reasonable comfort
needs of individual participants shall be met.
(H) Illumination shall be adequate in all
areas and commensurate with the type of
activity. Glare shall be kept at a minimum by
providing window coverings at all windows
exposed to direct sunlight and using shaded
light fixtures.
(I) All plumbing and plumbing fixtures
shall conform to applicable local codes.
There shall be no cross-connection between
the potable water supply and any source of
pollution through which the potable water
supply might become contaminated.
(J) An adequate supply of water, the source
of which is approved by the state water control authority, under sufficient pressure to
properly serve the facility shall be provided.
The potable water system shall be installed to
preclude the possibility of backflow.
(K) Drinking water shall be easily accessible to the participants and provided by either
an angle jet drinking fountain with mouth
guard or by a running water supply with individual service drinking cups. Drinking facilities shall not be located in a toilet room.
(L) At least one (1) toilet and handwashing
sink shall be provided for each ten (10) participants or any additional fraction thereof.
The handwashing sink shall be in close proximity to each toilet and shall have hot and
cold running water. The water temperature
shall be maintained between one hundred
degrees Fahrenheit (100°F) and one hundred
fifteen degrees Fahrenheit (115°F). The toilet
room shall be within easy access of the activity areas and afford the participants privacy.
Each toilet room shall be equipped with
approved natural or mechanical ventilation.
All toilets shall have grab-rails. Individual
paper towels, a trash receptacle, soap and toilet paper shall be provided at all times and
shall be within reach of the participants.
(M) If persons using wheelchairs or persons with other physical disabilities are
accepted, or the building in which the facility
is located is otherwise required to comply
with the Americans with Disabilities Act
(ADA), the facility shall have ramps or other
means of accessibility to the adult day care
facility for persons with disabilities, and shall
meet the standards of the ADA Standards for
Accessible Design which are available at
www.usdoj.gov/crt/ada/adastd94.pdf.
(N) Stairways and hallways shall be kept
free of obstructions and shall be well lighted.
All stairways and ramps shall have nonslip
surface or treads. All inside and outside stairs
and ramps shall have handrails.
(O) All rugs and floor coverings shall be
secured to the floor. Throw rugs shall not be
used. All equipment and furnishings shall be
safe and maintained in good condition.
(P) The adult day care program shall provide necessary services to maintain the building or portion of the building in which the
adult day care program is located in good
repair and in a safe, clean, orderly and sanitary manner.
(Q) Drugs, cleaning agents, pesticides and
poisonous products shall be stored apart from
food, out of the reach of the participants, and
shall be used in a manner which assures the
safety of participants and staff.
(R) Wastebaskets and trash containers shall
be made of noncombustible or fire-resistant
material. Garbage and other waste shall be
stored and disposed of in an appropriate manner.
(S) The facility shall be maintained free of
insects and rodents. Control measures shall
be implemented to prevent rodent and insect
infestation.
(2) Fire Safety Requirements.
(A) Adult day care programs shall obtain
annual written approval from the appropriate
local fire safety officials, certifying that the
facility complies with local fire codes. If
there are no applicable codes, or if the
department or division determines that such
codes are not adequate, the department or
division shall determine the adequacy of the
means of egress and other measures for life
safety from fire in accordance with the provisions of the Life Safety Code (NFPA 101), in
order to ensure the safety of frail persons or
persons with disabilities. All adult day care
programs initially licensed prior to December
1, 2004 shall comply with the provisions of
the 2000 Life Safety Code for existing occupancies (NFPA 101), incorporated by reference in this rule. Adult day care programs
licensed on or after December 1, 2004 shall
comply with the provisions of the 2000 Life
Safety Code for New Day Care Occupancies
(NFPA 101).
(B) The facility shall have a minimum of
two (2) exits remote from each other. Exits
shall be clearly marked with exit signs and
shall provide egress at ground level.
(C) Each adult day care provider shall
locate, install and maintain in operable condition an adequate number of smoke detectors
and fire extinguishers of the appropriate type
as determined in consultation with the local
fire authorities or the division. Fire extinguishers shall comply with the requirements
of the 1998 Standard for Portable Fire Extinguishers (NFPA 10), incorporated by reference in this rule.
(D) A written plan for assuring the safety
of participants, staff and volunteers in case of
fire or other disaster shall be developed in
consultation with state or local fire authorities and shall include, at a minimum, the following:
1. A written assessment of potential
fire or safety hazards present on the premises
and actions and procedures to follow to minimize potential danger;
2. A written schedule for periodic
checks for battery strength of smoke detectors
and adequate pressure of fire extinguishers;
3. A written training plan and schedule
for staff and volunteers on safety responsibilities and actions to be taken if an emergency
situation occurs and documentation of the
type of training provided; and
4. A written plan for conducting fire
drills and other emergency preparedness procedures, including staff responsibilities and
assignments to ensure orderly evacuations
and participants’ safety.
(E) Fire drills shall be coordinated with
local fire safety authorities and conducted at
least one (1) time per month and with sufficient frequency to familiarize staff and participants with the proper evacuation procedures.
Drills may be held at unexpected times and
under varying conditions to simulate the
unusual conditions that occur in the case of
fire. The actual evacuation of participants
and staff is not necessary providing everyone
involved is able to carry out actual evacuation
procedures if required. Fire drills shall
include suitable procedures to ensure that all
affected persons actually participate in the
drill exercises.
(F) The program director or other staff
qualified to exercise leadership shall be
responsible for planning and conducting fire
drills and other emergency preparedness procedures. The program director shall ensure
that staff are assigned to assist participants
with disabilities or other special needs to
ensure the health and safety of participants
when implementing the fire and emergency
preparedness procedures in evacuating the
facility, or complying with written plan procedures.
AUTHORITY: sections 660.050, RSMo Supp.
2003 and 660.418, RSMo 2000.* This rule
was originally filed as 13 CSR 15-8.070.
Original rule filed Oct. 15, 1984, effective
Jan. 11, 1985. Moved to 19 CSR 30-90.070,
effective Aug. 28, 2001. Amended: Filed
Sept. 14, 2004, effective March 30, 2005. **
*Original authority: 660.050, RSMo 1984, amended
1988,
1992,
1993,
1994,
1995,
2001
and
660.418, RSMo 1984, amended 1993, 1994.