10 CSR 60-11.010
Prevention of Backflow
PURPOSE: This rule establishes requirements for protection of public water systems
from introduction of contaminants by backflow.
(1) Applicability, Exemptions and Compliance
Dates.
(A) Applicability. This rule applies to all
community water systems.
(B) Exemptions.
1. This rule does not apply to customer
facilities used solely for residential purposes
unless a cross-connection is specifically identified or the rule indicates otherwise.
2. The department may issue an exemption from the requirements of paragraphs
(3)(A)1. and (3)(B)1. of this rule if the customer can demonstrate to the department, the
local governmental authority (if one exists)
and the supplier of water that the activities
taking place at the customer’s facility and the
materials used in connection with these activities or stored on the premises cannot endanger the health of customers or degrade the
water quality of the public water system
should backflow occur, or that any potential
risk posed by these materials or activities is
isolated from the public water system. Those
customers granted an exemption in accordance with this paragraph shall report to the
supplier of water any proposed change in process, plumbing or materials used or stored at
the exempted facility at least fourteen (14)
days prior to making the change.
3. Any exemption granted under paragraph (1)(B)2. of this rule shall be void if the
supplier of water, local governmental authority (if one exists) or the department determines that the customer facility has become
an actual or potential backflow hazard, or if
the customer fails to provide notice at least
fourteen (14) days prior to making any
change in process, plumbing or materials
used or stored at the facility.
(2) Cross-Connections. No customer shall
cause or allow the construction or maintenance of an unprotected cross-connection.
(3) Backflow Control by Containment.
(A) Class I Backflow Hazards.
1. A Class I backflow hazard presents an
actual or potential health hazard to customers
of the public water system should backflow
occur. The customer or the customer’s authorized representative shall construct a department-approved air-gap separation or install a
reduced pressure principle backflow prevention assembly on the customer service line, in
accordance with section (4) of this rule,
when—
A. The supplier of water or local governmental agency (if one exists) requires protection from an actual or potential Class I
backflow hazard at any facility;
B. Modification is made to the customer water system at an existing facility
which is designated an actual or potential
backflow hazard in paragraph (3)(A)2. of this
rule. If an addition or modification requiring
a separate customer service line is made to an
existing facility, the new service line as well
as the existing customer service line shall be
equipped with department-approved backflow
prevention assemblies;
C. A new customer service line connection is made to a facility listed in paragraph (3)(A)2. of this rule; or
D. A backflow incident occurs which
introduces a contaminant into the public or
customer water system which may create a
health hazard.
2. Following is a list, not all inclusive,
of actual or potential Class I backflow hazards:
A. Aircraft and missile manufacturing
plants;
B. Automotive plants including, but
not limited to, those plants which manufacture motorcycles, automobiles, trucks, recreational vehicles and construction and agricultural equipment;
C. Potable water dispensing stations
which are served by a public water system;
D. Beverage bottling plants including,
but not limited to, dairies, soft drink bottlers,
and breweries;
E. Canneries, packing houses and
reduction plants;
F. Car washes;
G. Chemical, biological and radiological laboratories including, but not limited to,
those in high schools, trade schools, colleges,
universities and research institutions;
H. Hospitals, clinics, medical buildings, autopsy facilities, morgues, mortuaries,
veterinary facilities, dental clinics, and other
medical facilities;
I. Metal or plastic manufacturing,
fabrication, cleaning, plating or processing
facilities;
J. Plants manufacturing paper and
paper products;
K. Plants manufacturing, refining,
compounding or processing fertilizer, film,
herbicides, natural or synthetic rubber, pesticides, petroleum or petroleum products,
pharmaceuticals, radiological materials or
any chemical which would be a contaminant
to the public water system;
L. Commercial facilities that use herbicides, pesticides, fertilizers or any chemical
which would be a contaminant to the public
water system;
M. Plants processing, blending or
refining animal, vegetable or mineral oils;
N. Commercial laundries and dye
works;
O. Sewage, storm water and industrial waste treatment plants and pumping stations;
P. Waterfront facilities including
piers, docks, marinas and shipyards;
Q. Industrial facilities which recycle
water;
R. Restricted or classified facilities or
other facilities closed to the supplier of water
or the department;
S. Fire sprinkler systems using any
chemical additives;
T. Auxiliary water systems, including
but not limited to alternative water sources;
U. Irrigation systems with facilities
for injection of pesticides, herbicides or other
chemicals or with provisions for creating
back pressure. The backflow assembly may
be installed between the customer service line
and the irrigation system;
V. Portable tanks for transporting
water taken from a public water system;
W. Facilities which have pumped or
repressurized cooling or heating systems that
are served by a public water system; and
X. Facilities which contain any boiler
system and are served by a public water system. The backflow assembly may be installed
on the water service line to the boiler.
(B) Class II Backflow Hazards.
1. A Class II backflow hazard threatens
to degrade the water quality of the public
water system should backflow occur. The
customer or the customer’s authorized representative shall install, as minimum protection
for Class II backflow hazards, a departmentapproved double check valve assembly on the
customer service line in accordance with
section (5) of this rule when—
A. The supplier of water or local governmental agency (if one exists) requires protection from an actual or potential Class II
backflow hazard at any facility;
B. Modification is made to the customer water system at an existing facility
which is designated an actual or potential
backflow hazard in paragraph (3)(B)2. If an
addition or modification requiring a separate
customer service line is made to an existing
facility, the new service line, as well as the
existing customer service line, shall be
equipped with department-approved backflow
prevention assemblies;
C. A new customer service line connection is made to a new facility listed in
paragraph (3)(B)2.; or
D. A backflow incident occurs in any
situation described in paragraph (3)(B)2. or
subsection (3)(C).
2. Following is a list, not all inclusive,
of actual or potential Class II backflow hazards:
A. Tanks to store water from the public water system for fire fighting only, unless
the tanks meet the requirements of the department for construction to maintain bacteriological quality of the water;
B. Fire sprinkler systems not using
chemical additives. This only applies to new
fire sprinkler systems or fire sprinkler systems scheduled for modifications;
C. Irrigation systems without facilities for injection of pesticides, herbicides or
other chemicals. The backflow assembly may
be installed between the customer service line
and the irrigation system; and
D. Cross-connections that could permit introduction of contaminants into the
public or customer water system and create a
nuisance, be aesthetically objectionable or
cause minor damage to the public water system or its appurtenances.
(C) Customer facilities not designated a
backflow hazard by subsection (3)(A) or (B)
may be designated a Class I or Class II backflow hazard by written notification from the
supplier of water or the department to the
customer. The notice shall specify the nature
of the customer activity which necessitates
designation of the facility as a backflow hazard, the type of backflow protection required
and the date by which the customer shall
install or construct this assembly on the customer service line to the facility.
(4) Department-Approved Backflow Prevention Assemblies.
(A) Only those models of double check
valve assemblies and reduced pressure principle backflow prevention assemblies which are
approved by the Foundation for Cross
Connection Control and Hydraulic Research
of the University of Southern California
(USC) or the American Society of Sanitary
Engineering (ASSE).
(B) The discharge pipe of an approved airgap shall terminate a minimum of two (2)
pipe diameters of the discharge pipe above
the flood level rim of the receiving vessel; in
no case shall the distance be less than one
inch (1").
(5) Standards of Construction and Installation.
(A) Reduced pressure principle backflow
prevention assemblies shall be installed with
no plug or additional piping affixed to the
pressure differential relief valve port (except
for specifically-designed funnel apparatus
available from the manufacturer) and with the
pressure differential relief valve port a minimum of twelve inches (12") above floor level.
Additionally, the assembly shall be installed
at a location where any leakage from the
pressure differential relief valve port will be
noticed, that allows easy access to the assembly for maintenance and testing, and that will
not subject the assembly to flooding, excessive heat or freezing.
(B) All double check valve assemblies
shall be installed at a location that allows easy
access to the assembly for maintenance and
testing and that will not subject the assembly
to excessive heat or freezing.
(C) Backflow prevention assemblies shall
be installed on the customer water system as
close as possible to the point of service connection and prior to any other connection or
branch line. If it is not possible to install the
backflow prevention assembly as described,
then installation shall be at the approval of the
department.
(D) No bypass piping shall be allowed
around a backflow prevention assembly
unless the bypass is equipped with the same
degree of backflow prevention protection.
(6) Backflow Prevention Assembly Testing
and Inspection.
(A) All backflow prevention assemblies
shall be inspected and tested by testers certified in accordance with the requirements and
procedures in 10 CSR 60-11.030.
(B) Air-gaps shall be inspected each year
by a date which is no later than thirty (30)
days past the anniversary date established by
the supplier of water to ensure that they continue to meet the requirements of subsection
(4)(A).
(C) Reduced pressure principle backflow
prevention assemblies shall be tested by a
certified backflow prevention assembly tester
each year by a date which is no later than
thirty (30) days past the anniversary date
established by the supplier of water to ensure
that—
1. The pressure differential relief valve
operates to maintain the zone between the two
(2) check valves at least two pounds per
square inch (2.0 psi) less than the supply
pressure;
2. The #2 check valve is leak tight
against reverse flow under all pressure differentials; and
3. The static pressure drop across the #1
check valve is at least three pounds per
square inch (3.0 psi) greater than the pressure
differential between the supply pressure and
the pressure in the zone required to open the
pressure differential relief valve.
(D) Double check valve assemblies shall
be tested each year by a certified backflow
prevention assembly tester by a date which is
no later than thirty (30) days past the anniversary date established by the supplier of water
to ensure that both the #1 and #2 check valves
maintain at least one pound per square inch
(1.0 psi) differential in the direction of flow
and are leak tight against reverse flow under
all pressure differentials.
(E) All certified backflow prevention
assembly testers shall report to the appropriate governmental authority (if one exists), the
supplier of water, the customer, and, if
requested, the department the results of
inspections or tests conducted in compliance
with this section (6). Reports of tests shall
contain the signature of the certified backflow
prevention assembly tester attesting to the
compliance (or noncompliance) of the assembly with established operational requirements. Routine reports shall be submitted
within thirty (30) days after making the
inspection or test. Falsification of testing or
inspection information shall be grounds for
removing the tester from the list of testers
authorized to operate in Missouri.
(7) Customer Responsibilities.
(A) The customer shall furnish, install and
maintain in working order at all times any
backflow prevention assembly required by
this rule.
(B) To ensure that each backflow prevention assembly required by this rule is in
working order, the customer shall have each
assembly inspected and tested by a certified
backflow prevention assembly tester at the
time of construction or installation and at the
frequency specified in section (6).
(C) The customer shall permit access to
the premises by the certified backflow prevention assembly tester, supplier of water and
department representatives, at reasonable
times and upon presentation of identification,
for inspection of the customer water system
or testing of backflow prevention assemblies
installed in accordance with this rule.
(8) Responsibilities of the Supplier of Water.
(A) Because backflow may cause a health
hazard through transmission of contaminants
via the public water system, the supplier of
water shall remove the water meter or otherwise sever the public water system from the
customer service line serving a facility when
the supplier of water—
1. Has knowledge that the customer is
causing or maintaining an unprotected crossconnection;
2. Has knowledge that the customer is
failing or refusing to proceed without delay to
correct any violation of the provisions of this
rule after having been notified to do so;
3. Is so ordered by the appropriate local
governmental author ity (if one exists); or
4. Is so ordered by the department
because of violation of any provision of this
rule by the customer.
(B) The supplier of water shall retain
records of the reports of inspections, tests and
repairs on backflow prevention assemblies for
a period of five (5) years.
(C) The supplier of water may develop, for
use within his/her service area, written procedures to implement the provisions of this
rule. In developing the procedures, the supplier of water will be permitted to take into
account existing backflow prevention pro-
grams and incorporate ordinances, regulations or requirements of appropriate local
governmental authorities. However, the written procedures shall be no less stringent than
the provisions of this rule. The department
will prepare and make available on request
the appropriate forms needed to assist the
supplier of water in implementing the provisions of this rule. The supplier of water may
submit the procedures to the department for
approval.
(D) The supplier of water shall record the
date of the initial inspection or test of backflow prevention assemblies required under
subsections (3)(A) and (3)(B) and shall
require that an annual inspection or test
report be submitted by a certified backflow
prevention assembly tester. The supplier of
water shall establish an annual anniversary
date for these inspection or test reports. If
these reports are not received by the supplier
of water on or before sixty (60) days following this anniversary date, the supplier of
water promptly shall notify the customer, the
local governmental agency (if one exists) and
the department.
(E) The supplier of water shall notify the
department within forty-eight (48) hours
whenever a cross-connection problem has
occurred which resulted in contamination of
the public water system.
AUTHORITY: section 640.100, RSMo 2016.*
Original rule filed May 4, 1979, effective
Sept. 14, 1979. Rescinded and readopted:
Filed July 11, 1986, effective Jan. 1, 1987.
Amended: Filed Dec. 4, 1990, effective July
8, 1991. Amended: Filed Jan. 2, 1997, effective Dec. 29, 1997. Amended: Filed June 13,
2018, effective Feb. 28, 2019. **
*Original authority: 640.100, RSMo 1939, amended 1978,
1981, 1982, 1988, 1989, 1992, 1993, 1995, 1996, 1998,
1999, 2002, 2006, 2012, 2014.
**Pursuant to Executive Orders 20-04, 20-10, and 20-12, 10 CSR
60-11.010, subsections (6)(B)-(6)(D) and (8)(D) was suspended from
June 1, 2020 through December 30, 2020.