10 CSR 60-4.094
Disinfectant Residuals, Disinfection Byproduct Precursors and the Stage 2 Disinfectants/Disinfection Byproducts Rule
PURPOSE: This rule establishes monitoring
and other requirements for achieving compliance with maximum contaminant levels based
on locational running annual averages for
certain disinfection byproducts and for
achieving compliance with maximum residual
disinfectant levels for chlorine and chloramine for certain consecutive systems. This
rule incorporates the requirements of subparts L and V of 40 CFR part 141, Stage 2
Disinfectants/Disinfection Byproducts, published in the January 4, 2006, Federal
Register.
(1) Stage
2
Disinfectants/Disinfection
Byproducts
(D/DBP)
Rule
General
Requirements.
(A) The requirements of this rule constitute
national primary drinking water regulations.
This rule establishes monitoring and other
requirements for achieving compliance with
maximum contaminant levels based on locational running annual averages (LRAA) for
total trihalomethanes (TTHM) and haloacetic
acids five (HAA5), and for achieving compliance with maximum residual disinfectant
residuals for chlorine and chloramine for certain consecutive systems.
(B) Applicability. This rule applies to
community water systems and nontransient
noncommunity water systems that use a primary or residual disinfectant other than ultraviolet light or deliver water that has been
treated with a primary or residual disinfectant
other than ultraviolet light.
(C) Community water systems and nontransient noncommunity water systems must
comply with maximum residual disinfectant
levels (MRDLs), monitoring and compliance
requirements of this rule, and the MCLs of
0.080 mg/L for total triahalomethanes
(TTHM), 0.060 mg/L for haloacetic acids
(five) (HAA5), 0.010 mg/L for bromate, and
1.0 mg/L for chlorite.
(2) Monitoring Requirements.
(A) Disinfectant Residuals, Chlorite, and
Bromate Monitoring Requirements.
1. Chlorine and chloramines.
A. Routine monitoring. Community
and nontransient noncommunity water systems must measure the residual disinfectant
level at the same points in the distribution
system and at the same time as total coliforms
are sampled, as specified in 10 CSR 604.022. Systems using surface water or ground
water under the direct influence of surface
water may use the results of residual disinfectant concentration sampling conducted
under 10 CSR 60-4.080(3) and 10 CSR 604.055(4), in lieu of taking separate samples.
B. Reduced monitoring. Monitoring
may not be reduced.
2. Chlorine dioxide.
A. Routine monitoring. Community,
nontransient noncommunity, and transient
noncommunity water systems that use chlorine dioxide for disinfection or oxidation
must take daily samples at the entrance to the
distribution system. For any daily sample that
detects chlorine dioxide, the system must take
additional samples in the distribution system
the following day in addition to the sample
required at the entrance to the distribution
system.
B. Additional monitoring. On each
day following a routine sample monitoring
result that detects chlorine dioxide, the system is required to take three (3) chlorine
dioxide distribution system samples as close
to the first customer as possible, at intervals
of at least six (6) hours. If chloramines are
used to maintain a disinfectant residual in the
distribution system, or if chlorine is used to
maintain a disinfectant residual in the distribution system and there are no disinfection
addition points after the entrance to the distribution system (that is, no booster chlorination), the system must take three (3) samples
as close to the first customer as possible, at
intervals of at least six (6) hours. If chlorine
is used to maintain a disinfectant residual in
the distribution system and there are one (1)
or more disinfection addition points after the
entrance to the distribution system (that is,
booster chlorination), the system must take
one (1) sample at each of the following locations: as close to the first customer as possible; in a location representative of average
residence time; and as close to the end of the
distribution system as possible (reflecting
maximum residence time in the distribution
system).
C. Reduced monitoring. Chlorine
dioxide monitoring may not be reduced.
3. Chlorite.
A. Routine monitoring. Community
and nontransient noncommunity water systems using chlorine dioxide, for disinfection
or oxidation, must conduct monitoring for
chlorite.
(I) Daily Monitoring. Systems must
take daily samples at the entrance to the distribution system. For any daily sample that
exceeds the chlorite MCL, the system must
take additional samples in the distribution
system the following day at the following
locations: near the first customer; at a location representative of average residence time;
and at a location reflecting maximum residence time in the distribution system, in addition to the sample required at the entrance to
the distribution system.
(II) Monthly monitoring. Systems
must take a three (3)-sample set each month
in the distribution system. The system must
take one (1) sample at each of the following
locations: near the first customer; at a location representative of average residence time;
and at a location reflecting maximum residence time in the distribution system. Any
additional routine sampling must be conducted in the same manner (as three (3)-sample
sets, at the specified locations). The system
may use the results of additional monitoring
conducted under the following subparagraph
(2)(A)3.B. to meet the requirement for
monthly monitoring.
B. Additional monitoring. On each
day following a routine sample monitoring
result that exceeds the chlorite MCL at the
entrance to the distribution system, the system is required to take three (3) chlorite distribution system samples at the following
locations: as close to the first customer as
possible, in a location representative of average residence time, and as close to the end of
the distribution system as possible (reflecting
maximum residence time in the distribution
system).
C. Reduced monitoring.
(I) Chlorite monitoring at the
entrance to the distribution system required
by part (2)(A)3.A.(I) of this rule may not be
reduced.
(II) Chlorite monitoring in the distribution
system
required
by
part
(2)(A)3.A.(II) of this rule may be reduced to
one (1) three (3)-sample set per quarter after
one (1) year of monitoring where no individual chlorite sample taken in the distribution
system under part (2)(A)3.A.(II) of this rule
has exceeded the chlorite MCL and the system has not been required to conduct monitoring under subparagraph (2)(A)3.B. of this
rule. The system may remain on the reduced
monitoring schedule until either any of the
three (3) individual chlorite samples taken
quarterly in the distribution system under
part (2)(A)3.A.(II) of this rule exceeds the
chlorite MCL or the system is required to
conduct monitoring under subparagraph
(2)(A)3.B. of this rule, at which time the system must revert to routine monitoring.
4. Bromate.
A. Routine monitoring. Community
and nontransient noncommunity systems
using ozone for disinfection or oxidation
must take one (1) sample per month for each
treatment plant in the system using ozone.
Systems must take samples monthly at the
entrance to the distribution system while the
ozonation system is operating under normal
conditions.
B. Reduced monitoring. A system
required to analyze for bromate may reduce
monitoring from monthly to quarterly, if the
system’s running annual average bromate
concentration is less than or equal to 0.0025
mg/L based on monthly bromate measurements for the most recent four (4) quarters,
with samples analyzed using Method 317.0
Revision 2.0, 326.0, or 321.8. If a system has
qualified for reduced bromate monitoring,
that system may remain on reduced monitoring as long as the running annual average of
quarterly bromate samples is ≤0.0025 mg/L
based on samples analyzed using Method
317.0 Revision 2.0, 326.0, or 321.8. If the
running annual average bromate concentration is >0.0025 mg/L, the system must
resume routine monitoring required by subparagraph (2)(A)4.A. of this rule.
(B) Disinfection Byproduct Precursors
(DBPP) Monitoring Requirements.
1. Total Organic Carbon (TOC).
A. Routine Monitoring. Systems
using surface water or ground water under
the direct influence of surface water and
using conventional filtration treatment must
monitor each treatment plant for total organic carbon (TOC) no later than the point of
combined filter effluent turbidity monitoring
and representative of the treated water. These
systems must also monitor for TOC in the
source water prior to any treatment at the
same time as monitoring for TOC in the treated water. These samples (source water and
treated water) are referred to as paired samples. At the same time as the source water
sample is taken, all systems must monitor for
alkalinity in the source water prior to any
treatment. Systems must take one (1) paired
sample and one (1) source water alkalinity
sample per month per plant at a time representative of normal operating conditions and
influent water quality.
B. Reduced monitoring. Systems
using surface water or ground water under
the direct influence of surface water with an
average treated water TOC of less than 2.0
mg/L for two (2) consecutive years, or less
than 1.0 mg/L for one (1) year, may reduce
monitoring for both TOC and alkalinity to
one (1) paired sample and one (1) source
water alkalinity sample per plant per quarter.
The system must revert to routine monitoring
in the month following the quarter when the
annual average treated water TOC greater
than or equal to 2.0 mg/L.
2. Bromide. Systems required to analyze
for bromate may reduce bromate monitoring
from monthly to once per quarter, if the system demonstrates that the average source
water bromide concentration is less than 0.05
mg/L based upon representative monthly
measurements for one (1) year. The system
must continue bromide monitoring to remain
on reduced bromate monitoring.
(C) Total Trihalomethane and Haloacetic
Acid Monitoring Requirements.
1. General Requirements.
A. Undisinfected systems that begins
using a disinfectant other than ultraviolet
(UV) light must consult with the department
to identify compliance monitoring locations
for this rule. Systems must then develop a
monitoring plan that includes those monitoring locations.
B. Stage 2 D/DBP Compliance
Monitoring Plan.
(I) Developing and implementing a
monitoring plan. The system must develop
and implement a monitoring plan to be kept
on file for department and public review.
Unless otherwise directed by the department,
the monitoring plan must contain the following elements and be complete no later than
the date initial monitoring under this rule is
conducted:
(a) Monitoring locations;
(b) Monitoring dates;
(c) Compliance calculation procedures; and
(d) Monitoring plans for any
other systems in the combined distribution
system if the department has reduced monitoring requirements.
(II) The system must identify which
locations to use for Stage 2 D/DBP rule compliance monitoring by alternating selection of
locations representing high TTHM levels and
high HAA5 levels until the required number
of Stage 2 D/DBP rule compliance monitoring locations have been identified.
(III) The system must submit a
copy of the monitoring plan to the department
prior to the date the system conducts the initial monitoring under this rule.
(IV) A system may revise the monitoring plan to reflect changes in treatment,
distribution system operations and layout
(including new service areas), or other factors that may affect TTHM or HAA5 formation, or for department-approved reasons,
after consultation with the department
regarding the need for changes and the appropriateness of changes. If the system changes
monitoring locations, the system must replace
existing compliance monitoring locations
with the lowest LRAA with new locations
that reflect the current distribution system
locations with expected high TTHM or
HAA5 levels. The department may also
require modifications in the system’s monitoring plan. The system must submit a copy
of the modified monitoring plan to the department prior to the date the system is required
to comply with the revised monitoring plan.
C. Monitoring must begin at the locations and months the system has recommended in the Stage 2 D/DBP Compliance
Monitoring Plan unless the department
requires other locations or additional locations after its review.
D. Analytical methods. The system
must use an approved method listed in 10
CSR 60-5.010 for TTHM and HAA5 analyses. Analyses must be conducted by laboratories that have received certification by
Environmental Protection Agency (EPA) or
the department as specified in 10 CSR 605.020.
E. Additional
Requirements
for
Consecutive Systems. If the system is a consecutive system that does not add a disinfectant but delivers water that has been treated
with a primary or residual disinfectant other
than ultraviolet light, the system must comply
with analytical and monitoring requirements
for chlorine and chloramines in 10 CSR 605.010 and 10 CSR 60-4.055(4)(E), the compliance requirements in 10 CSR 604.094(3)(B.)1. and report monitoring results
under 10 CSR 60-7.010(5)(B).
2. Reduced Monitoring.
A. Monitoring requirements for
source water TOC. In order to qualify for
reduced monitoring for TTHM and HAA5,
surface water and ground water under the
direct influence of surface water (GWUDISW) systems not monitoring under the TOC
reduced monitoring provisions, must take
monthly TOC samples every thirty (30) days
at a location prior to any treatment. Once
qualified for reduced monitoring for TTHM
and HAA5, a system may reduce source
water TOC monitoring to quarterly TOC
samples taken every ninety (90) days at a
location prior to any treatment.
B. The system may reduce monitoring
any time the LRAA is ≤0.040 mg/L for
TTHM and ≤0.030 mg/L for HAA5 at all
monitoring locations. In addition, the source
water annual average TOC level, before any
treatment, must be ≤4.0 mg/L at each treatment plant treating surface water or ground
water under the direct influence of surface
water.
6WDJH''%35RXWLQH0RQLWRULQJ
6RXUFHZDWHUW\SH
3RSXODWLRQVL]HFDWHJRU\
0RQLWRULQJ
)UHTXHQF\
'LVWULEXWLRQ
V\VWHP
PRQLWRULQJ
ORFDWLRQWRWDOSHU
PRQLWRULQJ
SHULRG
6XUIDFHZDWHUV\VWHPRUJURXQGZDWHU
XQGHUWKHGLUHFWLQIOXHQFHRIVXUIDFH
ZDWHU
*URXQGZDWHU
±
±
±
±
±
±
±
±
±
3HU\HDU
3HUTXDUWHU
3HUTXDUWHU
3HUTXDUWHU
3HUTXDUWHU
3HUTXDUWHU
3HUTXDUWHU
3HUTXDUWHU
3HU\HDU
3HU\HDU
3HUTXDUWHU
3HUTXDUWHU
3HUTXDUWHU
$OOV\VWHPVPXVWPRQLWRUGXULQJPRQWKRIKLJKHVW'%3FRQFHQWUDWLRQV
6\VWHPVRQTXDUWHUO\PRQLWRULQJPXVWWDNHGXDOVDPSOHVHWVHYHU\GD\VDWHDFKPRQLWRULQJORFDWLRQH[FHSWIRUVXUIDFHZDWHU
V\VWHPVRUJURXQGZDWHUXQGHUWKHGLUHFWLQIOXHQFHRIVXUIDFHZDWHUVHUYLQJ±*URXQGZDWHUV\VWHPVVHUYLQJ
RQDQQXDOPRQLWRULQJPXVWWDNHGXDOVDPSOHVHWVDWHDFKPRQLWRULQJORFDWLRQ$OORWKHUV\VWHPVRQDQQXDOPRQLWRULQJDQGVXUIDFH
ZDWHUV\VWHPVRUJURXQGZDWHUXQGHUWKHGLUHFWLQIOXHQFHRIVXUIDFHZDWHUVHUYLQJ±DUHUHTXLUHGWRWDNHLQGLYLGXDO77+0
DQG+$$VDPSOHVLQVWHDGRIDGXDOVDPSOHVHWDWWKHORFDWLRQZLWKWKHKLJKHVW77+0DQG+$$FRQFHQWUDWLRQVUHVSHFWLYHO\
)RUV\VWHPVVHUYLQJIHZHUWKDQILYHKXQGUHGSHRSOHRQHORFDWLRQZLWKDGXDOVDPSOHVHWSHUPRQLWRULQJSHULRGLVQHHGHG
LIWKHKLJKHVW77+0DQG+$$FRQFHQWUDWLRQVRFFXUDWWKHVDPHORFDWLRQ
Source water type
Population size category
Monitoring
Frequency1
Distribution system monitoring location
per monitoring period
Surface water system
or ground water under
the direct influence of
surface water:
Ground water:
<500
500–3,300
3,301–9,999
10,000–49,999
50,000–249,999
250,000–999,999
1,000,000–4,999,999
•5,000,000
<500
500-9,999
10,000-99,999
100,000-499,999
•500,000
Per year
Per year
Per quarter
Per quarter
Per quarter
Per quarter
Per quarter
Every third year
Per year
Per year
Per quarter
Per quarter
Monitoring may not be reduced.
1 TTHM and 1 HAA5 sample: one at the location
and during the quarter with the highest TTHM single
measurement; one at the location and during the
quarter with the highest HAA5 single measurement;
and 1 dual sample set per year if the highest TTHM
and HAA5 measurements occurred at the same
location and quarter.
2 dual sample sets: one at the location and during
the quarter with the highest TTHM single
measurement; and one at the location and during the
quarter with the highest HAA5 single measurement.
2 dual sample sets at the locations with the highest
TTHM and highest HAA5 LRAAs.
4 dual sample sets—at the locations with the two
highest TTHM and two highest HAA5 LRAAs.
6 dual sample sets—at the locations with the three
highest TTHM and three highest HAA5 LRAAs.
8 dual sample sets—at the locations with the four
highest TTHM and four highest HAA5 LRAAs.
10 dual sample sets—at the locations with the five
highest TTHM and five highest HAA5 LRAAs.
1 TTHM and 1 HAA5 sample: one at the location
and during the quarter with the highest TTHM single
measurement; one at the location and during the
quarter with the highest HAA5 single measurement;
and 1 dual sample set per year if the highest TTHM
and HAA5 measurements occurred at the same
location and quarter.
1 TTHM and 1 HAA5 sample: one at the location
and during the quarter with the highest TTHM single
measurement; one at the location and during the
quarter with the highest HAA5 single measurement;
and 1 dual sample set per year if the highest TTHM
and HAA5 measurements occurred at the same
location and quarter.
2 dual sample sets: one at the location and during the
quarter with the highest TTHM single measurement;
and one at the location and during the quarter with
the highest HAA5 single measurement.
2 dual sample sets; at the locations with the highest
TTHM and highest HAA5 LRAAs.
4 dual sample sets at the locations with the two
highest TTHM and two highest HAA5 LRAAs.
Stage 2 D/DBP Reduced Monitoring
1 Systems on quarterly monitoring must take dual sample sets every 90 days.
C. The system may remain on
reduced monitoring as long as the TTHM
LRAA ≤0.040 mg/L and the HAA5 LRAA
≤0.030 mg/L at each monitoring location
(for systems with quarterly reduced monitoring) or each TTHM sample ≤0.060 mg/L
and each HAA5 sample ≤0.045 mg/L (for
systems with annual or less frequent monitoring). In addition, the source water annual
average TOC level, before any treatment,
must be ≤4.0 mg/L at each treatment plant
treating surface water or ground water under
the direct influence of surface water.
D. If the LRAA based on quarterly
monitoring at any monitoring location
exceeds either 0.040 mg/L for TTHM or
0.030 mg/L for HAA5 or if the annual (or
less frequent) sample at any location exceeds
either 0.060 mg/L for TTHM or 0.045 mg/L
for HAA5, or if the source water annual average TOC level, before any treatment, >4.0
mg/L at any treatment plant treating surface
water or ground water under the direct influence of surface water, the system must
resume routine monitoring under section 10
CSR 60-4.094(2)(C)2. or begin increased
monitoring if paragraph 10 CSR 604.094(2)(C)4. applies.
E. The department may return the
system to routine monitoring at the department’s discretion.
3. Increased Monitoring.
A. If the system is required to monitor at a particular location annually or less
frequently than annually under routine or
reduced monitoring of this rule, the system
must increase monitoring to dual sample sets
once per quarter (taken every ninety (90)
days) at all locations if a TTHM sample is
>0.080 mg/L or an HAA5 sample is
>0.060 mg/L at any location.
B. The system is in violation of the
MCL when the LRAA exceeds the Stage 2
D/DBP rule MCLs in subparagraph 10 CSR
60-4.094(3)(D)3.A., calculated based on
four (4) consecutive quarters of monitoring
(or the LRAA calculated based on fewer than
four (4) quarters of data if the MCL would be
exceeded regardless of the monitoring results
of subsequent quarters). The system is in violation of the monitoring requirements for
each quarter that a monitoring result would
be used in calculating an LRAA if the system
fails to monitor.
C. The system may return to routine
monitoring once the system has conducted
increased monitoring for at least four (4) consecutive quarters and the LRAA for every
monitoring location is ≤0.060 mg/L for
TTHM and ≤0.045 mg/L for HAA5.
(3) Compliance Requirements.
(A) General Requirements.
1. Where compliance is based on a locational running annual average (LRAA) or
running annual average (RAA) of monthly or
quarterly samples or averages and the system
fails to monitor for TTHM, HAA5, or bromate, this failure to monitor will be treated as
a monitoring violation for the entire period
covered by the annual average.
2. Where compliance is based on a running annual average of monthly or quarterly
samples or averages and the system’s failure
to monitor makes it impossible to determine
compliance with MRDLs for chlorine and
chloramines, this failure to monitor will be
treated as a monitoring violation for the
entire period covered by the annual average.
3. All samples taken and analyzed under
the provisions of this rule must be included in
determining compliance, even if that number
is greater than the minimum required.
4. If, during the first year of monitoring,
any individual quarter’s average will cause
the running annual average of that system to
exceed the MCL, the system is out of compliance at the end of that quarter.
5. Systems required to monitor quarterly. To comply with MCLs in paragraph 10
CSR 60-4.094(2)(C)1.the system must calculate LRAAs for TTHM and HAA5 using
monitoring results collected under this rule
and determine that each LRAA does not
exceed the MCL. If the system fails to complete four (4) consecutive quarters of monitoring, the system must calculate compliance
with the MCL based on the average of the
available data from the most recent four (4)
quarters. If the system takes more than one
(1) sample per quarter at a monitoring location, the system must average all samples
taken in the quarter at that location to determine a quarterly average to be used in the
LRAA calculation.
6. Systems required to monitor yearly or
less frequently. To determine compliance
with the Stage 2 D/DBP MCLs in subparagraph 10 CSR 60-4.094(3)(D)3.A., the system must determine that each sample taken is
less than the MCL. If any sample exceeds the
MCL, the system must comply with the
requirements of increased monitoring of this
rule. If no sample exceeds the MCL, the
sample result for each monitoring location is
considered the LRAA for that monitoring
location.
7. Violation. If a system fails to monitor,
the system is in violation of the monitoring
requirements for each quarter or monitoring
period that a monitoring result would be used
in calculating a LRAA for TTHM and HAA5
or RAA for bromate or chlorite.
(B) Disinfectant Residuals, Chlorite, and
Bromate.
1. Chlorine and chloramines.
A. Compliance must be based on a
running annual arithmetic average, computed
quarterly, of monthly averages of all samples
collected by the system under paragraph
(2)(A)1. of this rule. If the average covering
any consecutive four (4)-quarter period
exceeds the MRDL, the system is in violation
of the MRDL and must notify the public pursuant to 10 CSR 60-8.010, in addition to
reporting to the department pursuant to 10
CSR 60-7.010.
B. In cases where systems switch
between the use of chlorine and chloramines
for residual disinfection during the year,
compliance must be determined by including
together all monitoring results of both chlorine and chloramines in calculating compliance. Reports submitted pursuant to 10 CSR
60-7.010(5) must clearly indicate which
residual disinfectant was analyzed for each
sample.
2. Chlorine dioxide.
A. Acute violations. Compliance
must be based on consecutive daily samples
collected by the system under subparagraph
(2)(A)2.A. of this rule. If any daily sample
taken at the entrance to the distribution system exceeds the MRDL, and on the following
day one (1) (or more) of the three (3) samples
taken in the distribution system exceed the
MRDL, the system is in violation of the
MRDL and must take immediate corrective
action to lower the level of chlorine dioxide
below the MRDL and must notify the public
pursuant to the procedures for acute health
risks in 10 CSR 60-8.010(2), in addition to
reporting to the department pursuant to 10
CSR 60-7.010. Failure to take samples in the
distribution system the day following an
exceedance of the chlorine dioxide MRDL at
the entrance to the distribution system will
also be considered an MRDL violation and
the system must notify the public of the violation in accordance with the provisions for
acute violations under 10 CSR 60-8.010(2), in
addition to reporting to the department pursuant to 10 CSR 60-7.010.
B. Nonacute violations. Compliance
must be based on consecutive daily samples
collected by the system in compliance with
this rule.
(I) If any two (2) consecutive daily
samples taken at the entrance to the distribution system detect chlorine dioxide, the system must take corrective action to lower the
chlorine dioxide level.
(II) If any two (2) consecutive daily
samples taken at the entrance to the distribution system exceed the MRDL and all distribution system samples taken are below the
MRDL, the system is in violation of the
MRDL and must take corrective action to
lower the level of chlorine dioxide below the
MRDL at the point of sampling and notify
the public pursuant to the procedures for
nonacute health risks in 10 CSR 60-8.010(3),
in addition to reporting to the department
pursuant to 10 CSR 60-7.010. Failure to monitor at the entrance to the distribution system
the day following an exceedance of the chlorine dioxide MRDL at the entrance to the distribution system is also an MRDL violation
and the system must notify the public of the
violation in accordance with the provisions
for nonacute violations in 10 CSR 608.010(3), in addition to reporting to the
department pursuant to 10 CSR 60-7.010.
(C) Disinfection Byproduct Precursors
(DBPP).
1. Systems using surface water or
ground water under the direct influence of
surface water and using conventional filtration treatment must operate with enhanced
coagulation or enhanced softening to achieve
the TOC percent removal levels specified in
this rule unless the system meets at least one
(1) of the alternative compliance criteria listed here. These systems must still comply
with monitoring and compliance requirements of this rule. The alternative compliance
criteria for enhanced coagulation and
enhanced softening are:
A. The system’s source water TOC
level, measured according to 10 CSR 605.010, is less than 2.0 mg/L, calculated quarterly as a running annual average;
B. The system’s treated water TOC
level, measured according to 10 CSR 605.010, is less than 2.0 mg/L, calculated quarterly as a running annual average;
C. The system’s source water TOC
level, measured according to 10 CSR 605.010, is less than 4.0 mg/L, calculated quarterly as a running annual average; the source
water alkalinity, measured according to 10
CSR 60-5.010, is greater than sixty (60)
mg/L (as CaCO3), calculated quarterly as a
running annual average; and either the
TTHM and HAA5 running annual averages
are no greater than 0.040 mg/L and 0.030
mg/L, respectively; or prior to the effective
date for compliance with this rule, the system
has made a clear and irrevocable financial
commitment not later than the effective date
for compliance with this rule to use technologies that will limit the levels of TTHMs and
HAA5 to no more than 0.040 mg/L and
0.030 mg/L, respectively. Systems must submit evidence of a clear and irrevocable financial commitment, in addition to a schedule
containing milestones and periodic progress
reports for installation and operation of
appropriate technologies, to the department
for approval not later than the effective date
for compliance with this rule. These technologies must be installed and operating not
later than June 30, 2005. Failure to install
and operate these technologies by the date in
the approved schedule will constitute a violation;
D. The TTHM and HAA5 running
annual averages are no greater than 0.040
mg/L and 0.030 mg/L, respectively, and the
system uses only chlorine for primary disinfection and maintenance of a residual in the
distribution system;
E. The system’s source water SUVA,
prior to any treatment and measured monthly
according to 10 CSR 60-5.010, is less than or
equal to 2.0 L/mg-m, calculated quarterly as
a running annual average. SUVA refers to
Specific Ultraviolet Absorption at two hundred fifty-four nanometers (254 nm), an indicator of the humic content of water. It is a
calculated parameter obtained by dividing a
sample’s ultraviolet absorption at a wavelength of 254 nm (UV254) (in m=1) by its concentration of dissolved organic carbon (DOC)
(in mg/L); and
F. The system’s finished water SUVA,
measured monthly according to 10 CSR 605.010, is less than or equal to 2.0 L/mg-m,
calculated quarterly as a running annual average.
2. Additional alternative compliance criteria for softening systems. Systems practicing enhanced softening that cannot achieve
the Step 1 TOC removals may use the alternative compliance criteria listed here in lieu
of complying with paragraph (3)(C)3. of this
rule. Systems must still comply with monitoring and compliance requirements of this
rule.
A. Softening that results in lowering
the treated water alkalinity to less than sixty
(60) mg/L (as CaCO3), measured monthly
according to 10 CSR 60-5.010 and calculated
quarterly as a running annual average.
B. Softening that results in removing
at least ten (10) mg/L of magnesium hardness
(as CaCO3), measured monthly according to
10 CSR 60-5.010 and calculated quarterly as
an annual running average.
3. Enhanced coagulation and enhanced
softening performance requirements.
A. Systems must achieve the percent
reduction of TOC specified in Table 1
between the source water and the combined
filter effluent, unless the department
approves a system’s request for alternate minimum TOC removal (Step 2) requirements.
Systems may begin monitoring to determine
whether Step 1 TOC removals can be met
twelve (12) months prior to the compliance
date for the system. This monitoring is not
required and failure to monitor during this
period is not a violation. However, any system that does not monitor during this period,
and then determines in the first twelve (12)
months after the compliance date that it is not
able to meet the Step 1 requirements and
must therefore apply for alternate minimum
TOC removal (Step 2) requirements, is not
eligible for retroactive approval of alternate
minimum TOC removal (Step 2) requirements and is in violation. Systems may apply
for alternate minimum TOC removal (Step 2)
requirements any time after the compliance
date. For systems required to meet Step 1
TOC removals, if the value calculated under
part (3)(C)4.A.(IV) of this rule is less than
1.00, the system is in violation of the treatment technique requirements and must notify
the public pursuant to 10 CSR 60-8.010 in
addition to reporting to the department pursuant to 10 CSR 60-7.010.
B. Required Step 1 TOC reductions,
indicated in the following table, are based
upon specified source water parameters measured in accordance with 10 CSR 60-5.010.
Systems practicing softening are required to
meet the Step 1 TOC reductions in the far
right column (Source water alkalinity >120
mg/L) for the specified source water TOC.
1Systems meeting at least one (1) of the conditions in paragraph (3)(C)1. of this rule are
not required to operate with enhanced coagulation.
2Softening systems meeting one (1) of the
alternative compliance criteria in paragraph
(3)(C)1. of this rule are not required to operate with enhanced softening.
3Systems practicing softening must meet the
TOC removal requirements in this column.
C. Conventional treatment systems
using surface water or ground water under the
direct influence of surface water that cannot
achieve the Step 1 TOC removals due to water
quality parameters or operational constraints
must apply to the department, within three (3)
months of failure to achieve the Step 1 TOC
removals, for approval of alternative minimum
TOC removal (Step 2) requirements submitted
by the system. If the department approves the
alternative minimum TOC removal (Step 2)
requirements, the department may make those
requirements retroactive for the purposes of
7DEOH5HTXLUHG6WHS72&5HGXFWLRQ
6WHS5HTXLUHG5HPRYDORI72&E\(QKDQFHG&RDJXODWLRQDQG
(QKDQFHG6RIWHQLQJIRU6XUIDFH:DWHUDQG*:8',6:6\VWHPV
8VLQJ&RQYHQWLRQDO7UHDWPHQW
6RXUFHZDWHU72&PJ/
6RXUFHZDWHUDONDOLQLW\PJ/DV&D&2
±
!±
!
!±
!±
!
determining compliance. Until the department approves the alternate minimum TOC
removal (Step 2) requirements, the system
must meet the Step 1 TOC removals.
D. Alternate minimum TOC removal
(Step 2) requirements. Applications made to
the department by enhanced coagulation systems for approval of alternative minimum
TOC removal (Step 2) requirements under
subparagraph (3)(C)3.C. of this rule must
include, as a minimum, results of bench- or
pilot-scale testing conducted under this subparagraph (3)(C)3.D. and used to determine
the alternate enhanced coagulation level.
(I) Alternate enhanced coagulation
level is defined as coagulation at a coagulant
dose and pH as determined by the method
described here such that an incremental addition of ten (10) mg/L of alum (or equivalent
amount of ferric salt) results in a TOC
removal of less than or equal to 0.3 mg/L.
The percent removal of TOC at this point on
the “TOC removal versus coagulant dose”
curve is then defined as the minimum TOC
removal required for the system. Once
approved by the department, this minimum
requirement supersedes the minimum TOC
removal required by Table 1 of this rule. This
requirement will be effective until such time
as the department approves a new value based
on the results of a new bench- and pilot-scale
test. Failure to achieve department-set alternative minimum TOC removal levels is a violation.
(II) Bench- or pilot-scale testing of
enhanced coagulation must be conducted by
using representative water samples and
adding 10 mg/L increments of alum (or
equivalent amounts of ferric salt) until the pH
is reduced to a level less than or equal to the
enhanced coagulation Step 2 target pH shown
in Table 2.
(III) For waters with alkalinities of
less than sixty (60) mg/L for which addition
of small amounts of alum or equivalent addition of iron coagulant drives the pH below
5.5 before significant TOC removal occurs,
the system must add necessary chemicals to
maintain the pH between 5.3 and 5.7 in samples until the TOC removal of 0.3 mg/L per
10 mg/L alum added (or equivalent addition
of iron coagulant) is reached.
(IV) The system may operate at any
coagulant dose or pH necessary (consistent
with other regulatory requirements) to
achieve the minimum TOC percent removal
approved under subparagraph (3)(C)3.C. of
this rule.
(V) If the TOC removal is consistently less than 0.3 mg/L of TOC per 10
mg/L of incremental alum dose at all dosages
of alum (or equivalent addition of iron coagulant), the water is deemed to contain TOC
not amenable to enhanced coagulation. The
system may then apply to the department for
a waiver of enhanced coagulation requirements.
4. Compliance calculations.
A. Systems using surface water or
ground water under the direct influence of
surface water, other than those identified in
paragraphs (3)(C)1. or (3)(C)2. of this rule,
must comply with requirements contained in
subparagraphs (3)(C)3.B. or (3)(C)3.C. of
this rule. Systems must calculate compliance
quarterly, beginning after the system has collected twelve (12) months of data, by determining an annual average using the following
method:
(I) Determine actual monthly TOC
percent removal, equal to: (1 – (treated water
TOC/source water TOC)) Ă— 100;
(II) Determine the required monthly TOC percent removal;
(III) Divide the value in part
(3)(C)4.A.(I)
by
the
value
in
part
(3)(C)4.A.(II); and
(IV) Add together the results of
part (3)(C)4.A.(III) for the last twelve (12)
months and divide by twelve (12). If the value
calculated is less than 1.00, the system is not
in compliance with the TOC percent removal
requirements.
B. Systems may use the following provisions in lieu of the calculations in subparagraph (3)(C)4.A. of this rule to determine
compliance with TOC percent removal
requirements:
(I) In any month that the system’s
treated or source water TOC level, measured
according to 10 CSR 60-5.010, is less than
2.0 mg/L, the system may assign a monthly
value of 1.0 (in lieu of the value calculated in
part (3)(C)4.A.(III) of this rule);
(II) In any month that a system
practicing softening removes at least 10 mg/L
of magnesium hardness (as CaCO3), the system may assign a monthly value of 1.0 (in
lieu of the value calculated in part
(3)(C)4.A.(III) of this rule);
(III) In any month that the system’s
source water SUVA, prior to any treatment
and measured according to 10 CSR 60-5.010,
is less than or equal to 2.0 L/mg-m, the system may assign a monthly value of 1.0 (in
lieu of the value calculated in part
(3)(C)4.A.(III) of this rule);
(IV) In any month that the system’s
finished water SUVA, measured according to
10 CSR 60-5.010, is less than or equal to 2.0
L/mg-m, the system may assign a monthly
value of 1.0 (in lieu of the value calculated in
part (3)(C)4.A.(III) of this rule); and
(V) In any month that a system
practicing enhanced softening lowers alkalinity below sixty (60) mg/L (as CaCO3), the
system may assign a monthly value of 1.0 (in
lieu of the value calculated in part
(3)(C)4.A.(III) of this rule).
C. Systems using conventional treatment and surface water or ground water
under the direct influence of surface water
may also comply with the requirements of
this rule by meeting the criteria in paragraphs
(3)(C)1. or (3)(C)2. of this rule.
(D) Disinfection Byproducts.
1. Bromate. Compliance must be based
on a running annual arithmetic average, computed quarterly, of monthly samples (or, for
months in which the system takes more than
one sample, the average of all samples taken
during the month) collected by the system as
prescribed by paragraph (2)(A)4. of this rule.
If the average of samples covering any consecutive four-quarter period exceeds the
MCL, the system is in violation of the MCL
and must notify the public pursuant to 10
CSR 60-8.010, in addition to reporting to the
department pursuant to 10 CSR 60-7.010. If a
PWS fails to complete twelve (12) consecutive months’ monitoring, compliance with the
MCL for the last four (4)-quarter compliance
period must be based on an average of the
available data.
2. Chlorite. Compliance must be based
on an arithmetic average of each three (3)
sample set taken in the distribution system as
prescribed by item (2)(A)3.C.(II) and subparagraph (2)(A)3.B. of this rule. If the arithmetic average of any three (3) sample set
exceeds the MCL, the system is in violation
of the MCL and must notify the public pursuant to 10 CSR 60-8.010, in addition to
reporting to the department pursuant to 10
CSR 60-7.010.
3. Total Trihalomethane (TTHM) and
Haloacetic Acid (HAA).
A. Stage 2 Disinfectants/Disinfection
Byproducts—Locational Running Annual
Average (LRAA) Compliance. The MCLs of
0.080 mg/L for TTHM and 0.060 mg/L for
HAA5 must be complied with as a locational
running annual average at each monitoring
location.
B. If the system is required to conduct
quarterly monitoring, the system must make
7DEOH(QKDQFHG&RDJXODWLRQ
6WHS7DUJHWS+
$ONDOLQLW\PJ/DV&D&2
7DUJHWS+
!
!
!
compliance calculations at the end of the
fourth calendar quarter that follows the compliance date and at the end of each subsequent quarter (or earlier if the LRAA calculated based on fewer than four (4) quarters of
data would cause the MCL to be exceeded
regardless of the monitoring results of subsequent quarters). If the system is required to
conduct monitoring at a frequency that is less
than quarterly, the system must make compliance calculations beginning with the first
compliance sample taken after the compliance date.
C. The department may determine
that the combined distribution system does
not include certain consecutive systems based
on factors such as receiving water from a
wholesale system only on an emergency basis
or receiving only a small percentage and
small volume of water from a wholesale system. The department may also determine that
the combined distribution system does not
include certain wholesale systems based on
factors such as delivering water to a consecutive system only on an emergency basis or
delivering only a small percentage and small
volume of water to a consecutive system.
(E) Operational Evaluation Levels.
1. The system has exceeded the operational evaluation level at any monitoring location where the sum of the two (2) previous
quarters of TTHM results plus twice the current quarter’s TTHM result, divided by four
(4) to determine an average, exceeds 0.080
mg/L, or where the sum of the two (2) previous quarters of HAA5 results plus twice the
current quarter’s HAA5 result, divided by
four (4) to determine an average, exceeds
0.060 mg/L.
2. If Operational Evaluation Levels are
Exceeded.
A. If the system exceeds the operational evaluation level, the system must conduct an operational evaluation and submit a
written report of the evaluation to the department no later than ninety (90) days after
being notified of the analytical result that
causes the system to exceed the operational
evaluation level. The written report must be
made available to the public upon request.
B. The system’s operational evaluation must include an examination of system
treatment and distribution operational practices, including storage tank operations,
excess storage capacity, distribution system
flushing, changes in sources or source water
quality, and treatment changes or problems
that may contribute to TTHM and HAA5 formation and what steps could be considered to
minimize future exceedences.
(I) The system may request and the
department may allow a limit to the scope of
the evaluation if the system is able to identify
the cause of the operational evaluation level
exceedance.
(II) The system’s request to limit
the scope of the evaluation does not extend
the schedule in subparagraph (3)(E)2.A. of
this rule for submitting the written report.
The department must approve this limited
scope of evaluation in writing, and the system
must keep that approval with the completed
report.
(F) Stage 2 D/DBP Reporting and RecordKeeping Requirements.
1. Reporting requirements are found in
10 CSR 60-7.010, Reporting Requirements.
2. Record-keeping requirements are
found in 10 CSR 60-9.010, Requirements for
Maintaining Public Water System Records.
AUTHORITY: section 640.100, RSMo 2016.*
Original rule filed Feb. 27, 2009, effective
Oct. 30, 2009. Amended: Filed June 13,
2018, effective Feb. 28, 2019.
*Original authority: 640.100, RSMo 1939, amended 1978,
1981, 1982, 1988, 1989, 1992, 1993, 1995, 1996, 1998,
1999, 2002, 2006, 2012, 2014.