20 CSR 4240-124.045
Anchoring Standards
PURPOSE: This rule applies to the anchoring of any manufactured home purchased or
relocated on or after the effective date of this
rule. This rule shall not be applicable to any
manufactured home which has previously
been anchored at its existing location and
which has not been relocated subsequent to
the effective date of this rule.
(1) Definitions. The following definitions, as
well as those set out in section 700.010,
RSMo apply to this chapter:
(A) Anchor means any device designed to
transfer wind loads imposed on a manufactured home to the ground;
(B) Anchoring equipment means straps,
seals, cables, turnbuckles, and tensioning
devices, which are used to secure a manufactured home to anchors;
(C) Anchoring systems means a combination of ties, anchoring equipment, and
anchors that will, when properly designed
and installed, resist overturning and lateral
movement of the manufactured home from
wind forces;
(D) Classified soil means soil that has been
evaluated through the use of a standard soil
torque probe or other approved method to
determine anchor-holding capacity;
(E) Installed means the arrangement and
assembly at the occupancy site of all portions
of an anchoring system, in accordance with
the manufacturer’s design, that renders the
anchoring system fit for its intended use;
(F) Stabilizing device means a lateral support device such as a steel plate or a concrete
collar used in connection with an anchor to
limit lateral movement of the anchor;
(G) Tie means straps, cable, or securing
devices used to connect the manufactured
home to the anchor; and
(H) Unclassified soil means soils that have
not been evaluated to determine anchor-holding capacity.
(2) Anchoring System. Each manufactured
home installed after the effective date of the
rule must be anchored in accordance with the
minimum standards specified in the rule. At
a minimum, each anchoring system must also
meet or exceed the design wind load requirements for Wind Zone 1, as defined in
3280.305 in the Federal Manufactured Home
Construction and Safety Standards.
(3) Anchoring Equipment.
(A) Load. Anchoring equipment, when
installed, must be capable of resisting an
allowable working load equal to or exceeding
three thousand one hundred fifty (3,150)
pounds and must be capable of withstanding
a fifty percent (50%) overload (four thousand
seven hundred twenty-five (4,725) pounds
total) without failure of either the anchoring
equipment or the attachment point on the
manufactured home.
(B) Resistance to Weather Deterioration.
Anchoring equipment exposed to weathering
shall have a coating that is resistant to weather deterioration at least equivalent to that provided by a coating of zinc on steel of not less
than 0.30 ounces per square foot of surface
(.0005 inch in thickness), and in accordance
with the following:
1. Slit or cut edges of zinc-coated steel
strapping do not need to be zinc coated;
2. Flat steel strapping shall be Type 1,
Heavy Duty, Finish B, Grade 1, 1 1/4 inches
wide and 0.035 inch in thickness, certified by
a registered professional engineer as conforming with ASTM Standard Specification
D3953-91, Standard Specification for strapping, flat steel, and seals; and
3. Seals shall be Class H, Heavy Duty,
Finish B, Grade 1, for steel strapping, certified by the manufacturer as conforming with
ASTM Standard Specification D3953-91.
(C) Permanency of Connections. Anchoring equipment shall be designed and installed
to prevent self-disconnection when ties are
slack.
(4) Tensioning Devices. Tensioning devices
such as turnbuckles or yoke-type fasteners
shall be ended with clevis or forged or welded eyes.
(5) Ties.
(A) Material.
1. Flat steel strapping and seals or other
approved methods or materials shall be used
for ties. All ties shall be fastened to anchors
and drawn tight with turnbuckles or other
adjustable tensioning devices or devices
approved for use with the anchor.
2. Tie materials shall be either as
described in (3)(B)2. of this standard or other
approved material capable of resisting an
allowable working load of three thousand one
hundred fifty (3,150) pounds with no more
than twelve percent (12%) elongation and
shall withstand a fifty percent (50%) overload
(four thousand seven hundred twenty-five
(4,725) pounds total).
(B) Attachment.
1. Ties shall connect the anchor and the
main structural steel frame that runs lengthwise under the manufactured home. Ties
shall not connect to steel outrigger or cross
beams that fasten to and intersect the main
structural frame. Tie-down straps shall be
routed from the anchor to the top of the main
structural steel frame.
2. Tie-down straps shall be attached to
the anchor in accordance with the anchor
manufacturer’s instructions. A permanently
attached strap that has been cut off may be
spliced, provided an approved splicing device
is used.
(C) Vertical Ties. Vertical ties are not
required in Wind Zone 1, as defined in
3280.305 in the Federal Manufactured Home
Construction and Safety Standards.
(6) Anchors.
(A) Each anchor, when installed in classified soil, must be capable of resisting a minimum allowable working load of three thousand one hundred fifty (3,150) pounds in the
direction of the tie, plus a fifty percent (50%)
overload (four thousand seven hundred twenty-five (4,725) pounds total) without failure.
Failure shall be considered to have occurred
when the head of the anchor moves more than
two inches (2") vertically or three inches horizontally when pulled at an angle of between
forty degrees (40°) and fifty degrees (50°)
under a force of four thousand seven hundred
twenty-five (4,725) pounds.
(B) Each manufactured anchor shall be
tested and installed in accordance with the
terms of its specified testing procedures and
the anchor manufacturer’s instructions. Each
anchor shall be installed and pre-tensioned
until it is flush with the stabilizer plate. The
slotted bolt must have a minimum of four (4)
wraps of the strap after installation.
(C) Spacing and Location.
1. Classified soil.
A. All anchors shall be installed at the
intervals and in the locations specified by the
manufactured home manufacturer’s installation instructions, and in the correct soil class
for which they are approved.
B. In the event that the manufacturer’s
installation instructions are unavailable, all
anchors shall be installed in accordance with
Tables (A) through (C) of this standard
included herein, and in the correct soil class
for which they are approved.
2. Unclassified soil. All anchors
installed in unclassified soil shall be in accordance with Tables (A) through (C) of this
standard, included herein. A thirty-inch (30")
double four-inch (4") helix anchor with a
twelve-inch (12") stabilizer shall be used in
unclassified soil.
3. Spacing.
A. Spacing shall be as even as practicable along the entire length of the home with
the first anchor on each end no more than two
feet (2') from the end of the home.
(D) Soil Testing. A determination for soil
classification should be made at each anchor
location through the use of a standard torque
probe, as described in ASTM Standard
D2573-94, or equivalent method. If no soil
classification test is performed for the anchor
location, then the soil at the location shall be
considered as unclassified.
(7) Diagonal Tie-Down Strap Spacing. Strap
spacing for anchors is illustrated in the following tables.
(A) Tables (A) through (C), included herein, illustrate the strap spacing for single section and multi-section homes with anchors
located in classified and unclassified soils.
1. Note that the maximum vertical distance is measured from the anchor head to
the top of the I-beam (i.e., bottom of the
floor).
2. The maximum distance to the first
tie-down strap at each end of the home shall
be two feet (2'0").
3. Strap spacing calculations are based
on the fact that single disk anchors and double disk anchors have the same holding
capacity if installed in accordance with the
anchor manufacturer’s installation instructions and in the proper soil classification.
4. Anchors shall be installed just inside
the skirting line in order to maintain the
angles identified in each table.
5. Anchor strap attachments to the home
must be in accordance with the anchor manufacturer’s methods.
(B) Tables (D) and (E), included herein,
illustrate the criss-cross strapping system for
elevated single and multi-section homes (or
portion thereof) to be used in lieu of diagonal
tie-down strap spacing tables; and
(C) Table (F), included herein, illustrates
approved methods of ground anchor installation.
(8) Spacing For Federal Manufactured Home
Construction and Safety Standards Wind
Zone 1 Conditions.
(A) If the floor width is one hundred sixtysix inches (166") (typical fourteen (14)-wide),
with I-beam spacing ninety-five inches (95")
or greater center to center and the distance
from the top of the footer to the top of the Ibeam is no higher than sixty-four inches
(64"), anchors shall be spaced eight feet (8')
apart for classified soil, or five feet (5') apart
for unclassified soil.
(B) If the floor width is one hundred fortyone inches (141") (typical twelve (12)-wide),
with I-beam spacing seventy-five and onehalf inches (75.5") or greater center to center
and the distance from the top of the footer to
the top of the I-beam is no higher than fiftytwo inches (52"), anchors shall be spaced six
feet (6') apart for classified soil, or four feet
(4') apart for unclassified soil.
(C) Anchors must be installed just inside
the skirting line, or as close to the skirting
line as possible.
AUTHORITY: section 700.076, RSMo 2000*.
This rule originally filed as 4 CSR 240124.045. Original rule filed June 12, 2001,
effective Jan. 30, 2002. Moved to 20 CSR
4240-124.045, effective Aug. 28, 2019.