2 CSR 90-10.014
Storage
PURPOSE: This rule sets out minimum general standards for the
storage of liquefied petroleum gas and promotes safety for life
and property. These requirements do not apply to public utility
facilities regulated by the Missouri Public Service Commission.
PUBLISHER’S NOTE: The secretary of state has determined that the
publication of the entire text of the material which is incorporated
by reference as a portion of this rule would be unduly cumbersome
or expensive. This material as incorporated by reference in this
rule shall be maintained by the agency at its headquarters and
shall be made available to the public for inspection and copying
at no more than the actual cost of reproduction. This note applies
only to the reference material. The entire text of the rule is printed
here.
(1) All liquefied petroleum gas (LP gas) storage containers or
storage systems where one (1) tank is used having a water
capacity of one hundred (100) gallons or more, or where two
(2) or more tanks are used having a total combined capacity
of more than one hundred (100) gallons, and all related
equipment located at or near containers which are installed
within twenty-five feet (25') of a playground where children
in age groups of preschool through grade twelve (12) have
access shall be fenced with industrial type fence a minimum
of six feet (6') high as to prevent tampering with the gas piping
system.
(2) Where LP gas storage of five hundred (500) gallons or less is
in use or where a hazard exists in connection with any size of
underground storage system, reasonable protective methods,
other than fencing, which are deemed necessary may be
required.
(3) Containers of any size shall not be used for storage other
than manufacturer’s design and specifications; i.e., railcars,
converted railcars, bulk delivery truck tanks both transport
and bobtail cannot be utilized for fixed storage. A variance
for bobtail delivery truck tanks may be requested. A written
request must be submitted to the commission on form MPSC0417 included herein.
(4) All aboveground LP gas storage containers shall be kept
properly painted with a light reflective paint such as white or
aluminum.
(5) All aboveground LP gas storage containers, two thousand
(2,000) water capacity (WC) or more, and all dispensers shall
be clearly marked PROPANE, FLAMMABLE, NO SMOKING on
two (2) sides in a conspicuous location of the dispenser
housing, fencing, or a combination thereof. All wording shall
be in block-style letters with a minimum height of two inches
(2") and a minimum width of one-fourth inch (1/4") on a
contrasting background.
(6) Each LP gas bulk plant or system of two thousand (2,000)
gallons WC or more and all dispensers engaged in retail shall
have a sign displayed in a conspicuous location stating the
name and telephone number of the nearest representative,
agent, or owner of the system. All wording shall be in blockstyle letters with a minimum height of one inch (1") and on a
contrasting background.
(7) Any LP gas storage container, including any container used
for motor fuel, which has been damaged in any manner shall
be repaired according to the requirements of the code it was
manufactured under and shall be hydrostatically tested prior
to placing in service.
(8) Repair of any LP gas container shell, excluding valves,
fittings, regulators, and attachments, shall be in conformance
with the code under which the container was manufactured,
and all repairs shall be performed only by a person certified
under the code by which the container was manufactured.
(9) A copy of all container data information and repairs to the
container shall be submitted to the inspection authority for
review prior to installation of the container.
(10) LP gas storage containers supplying mobile home parks,
schools, hospitals, domestic systems, or other public or
institutional facilities shall not be utilized as a bulk storage
plant for loading LP gas into any fuel delivery vessel or vehicle.
(11) At a bulk storage facility that the owner declares out-ofservice, the tank or tanks shall be empty, only contain residual
pressure, and be capped or plugged as close as practical to the
positive shut-off valve just outside the tank or tanks. Before
placing the tank or plant back into operation, form MPSC-0910
including detailed plans shall be furnished to the inspection
authority for approval and approval must be granted by the
inspection authority. Form MPSC-0910, January 1, 2016, is
published by the Missouri Propane Safety Commission, 4110
Country Club Dr., Ste. 200, Jefferson City, MO 65109-0302 and
is incorporated by reference. This rule does not incorporate
any subsequent amendments or additions to the referenced
material.
MPSC-04 17 (06/2012)
Page 1 of 1
MISSOURI PROPANE
SAFETY COMMISSION
LP GAS INSPECTION AUTHORITY
APPLICATION FOR VARIANCE
NOTE: ONE APPLICATION/FORM MUST BE SUBMITTED FOR
EACH UNIT OF EQUIPMENT.
FOR MP S C OFFICE USE ONLY
DATE
VARIANCE #
MPGC APPROVAL
YES NO
THIS FORM MUST BE COMPLETED IN ITS ENTIRETY OR IT WILL BE RETURNED
OWNER NAME
OWNER ADDRESS
OWNER CITY, STATE, ZIP
NAME (IF DIFFERENT FROM OWNER)
MAILING ADDRESS
MAILING CITY, STATE, ZIP
LOCATION NAME
LOCATION ADDRESS
LOCATION CITY, STATE, ZIP
LOCATION COUNTY
LOCATION PHONE
NUMBER OF UNITS AT LOCATION
ACTIVITY
TYPE OF EQUIPMENT
USAGE
NEW INSTALLATION
CARGO TANK
OFFICE/GOVT BUILDING
OTHER
OTHER
HOSPITAL/INSTITUTIONAL
CHURCH/RELIGIOUS
COMMERCIAL/INDUSTRIAL
RETAIL
SCHOOL/LIBRARY/EDUCATIONAL
DISPENSER
RESIDENCE
MOTEL/HOTEL
AGICULTURE
NURSING/RETIREMENT HOME
OTHER
MANUFACTURER
DATE OF MANUFACTURER
SERIAL NUMBER
CAPACITY
WORKING PRESSURE
SPECIFIC LOCATION
LAST INSPECTION DATE
COMMENTS AND DESCRIPTION DETAIL OF INSTALLATION
Draw plan here, or attach plan in duplicate.
North ↑
WRITTEN RESPONSE REQUIRED BEFORE INSTALLATION.
SIGNATURE OF CONTACT PERSON AT LOCATION
INSPECTOR SIGNATURE
PRINTED NAME AND TITLE OF CONTACT PERSON AT LOCATION
Return to: MISSOURI PROPANE SAFETY COMMISSION, 4110 COUNTRY CLUB DR., STE. 200, JEFFERSON CITY, MO 65109-0302
OR FAX TO: 573-893-1074
(01-16)
AUTHORITY: section 323.020, RSMo 2016.* Original rule filed
July 13, 1977, effective Nov. 11, 1977. Amended: Filed May 2, 1985,
effective Sept. 27, 1985. Amended: Filed March 3, 1989, effective
June 29, 1989. Amended: Filed Nov. 13, 1997, effective June 30, 1998.
Amended: Filed Oct. 15, 2008, effective March 30, 2009. Amended:
Filed June 13, 2011, effective Jan. 30, 2012. Amended: Filed June
26, 2012, effective Jan. 30, 2013. Non-substantive change filed July
1, 2016, published Aug. 31, 2016. Amended: Filed March 30, 2017,
effective Oct. 30, 2017.
*Original authority: 323.020, RSMo 1947, amended 1994, 1998, 2005, 2007.