26 MAC Pt. 2, Ch. 1, R. 1.61
FIREWALLS
Cite as 26 Miss. Admin. Code Pt. 2, Ch. 1, R. 1.61
FIREWALLS.
(a) Each permanent oil and/or saltwater tank or battery of oil and/or saltwater tanks now or
hereafter located in the State of Mississippi shall be surrounded by a dike (or firewall) or
retaining wall of sufficient height and size so that the volume enclosed shall be equal to one
hundred fifty percent (150%) of the capacity of the largest tank in said battery OR the total
volume of fluids produced into the said battery during any twenty-four (24) hour period,
whichever is the greater. The dike (or firewall) or retaining wall shall be constructed of
impermeable material approved in advance by the Field Inspector or Energy Resource Director.
If there is more than 150% of the volume of the largest vessel in the tank battery produced into
the battery in a twenty-four (24) hour period, the Operator may, in lieu of extending the size of
the firewall to accommodate the excess of the 150% of the volume of the largest vessel in the
tank battery, install a high level shutdown device or system inside the firewall that would, in the
event of a spill, shut down all production coming to the tank battery at a level that would not
allow the fluid level to reach within six (6) inches of the top of the firewall.
(1)
Each permanent oil tank or battery of oil tanks, or any vessel or tank which
is protected by a dike (or firewall) or retaining wall and which has installed
a drain line for the purpose of discharging rainwater, must have in the drain
line a valve on the outside of the firewall and a bull plug installed downstream
of the valve.
(2)
Firewall drain valves may be open and bull plugs removed only when the
operator or his representative is present to observe the discharge. Discharges
may consist of rainwater only.
(3)
Firewall drain valves being open or bull plugs being removed from firewall
drain lines when no operator personnel are on the location shall be deemed
a violation of Statewide Rule 61.
(4)
The discharge of any fluids or other materials other than rainwater through
a firewall drain may constitute a violation of Statewide Rule 16, Statewide
Rule 17, Statewide Rule 45 or Statewide Rule 61.
(b) In water, swamp or marsh areas where the building of firewalls is impractical or
impossible, and the requirement thereof has been waived by the Supervisor upon proper written
application, permanent tanks shall be placed on an impervious base and surrounded by an
impervious gutter to catch all of the oil and other waste products which, upon escape, may cause
a fire hazard or pollution. A sump shall be provided to catch the runoff from the gutters.
(c) Tanks for the accumulation of liquid hydrocarbons not falling into the above categories
(A and B above) and all facilities for the loading and transportation of liquid hydrocarbons by
truck must be surrounded by a retaining wall or must be suitably ditched to a collecting sump,
either to be of sufficient capacity to contain the potential spillage to prevent the possibility of
pollution of surrounding areas.
(d) The Mississippi State Oil and Gas Board may, following notice and public hearing,
grant appropriate exceptions to any of the provisions of this rule upon a finding by the Board that
alternative construction or operating procedures proposed by the operator will provide an
equivalent level of protection to the public and the environment.
(e) With respect to oil and/or saltwater tanks, tank batteries and loading facilities in
existence on June 17, 2015, the date of approval of amendments to this rule to impose new
construction and operating requirements on such facilities, the operator shall have six (6) months
from that date in which to comply with said new requirements.