15 MAC Pt. 10, R. 3.2.11
Steam Gauges
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.2.11
Steam Gauges
1.
Each steam boiler shall have a steam gauge connected to its steam space, its water
column, or its steam connection, by means of a siphon or equivalent device
exterior to the boiler. The siphon shall be of sufficient capacity to keep the gauge
tube filled with water and so arranged that the gauge cannot be shot off from the
boiler except by a cock with a tee or lever handle placed in the pipe near the
gauge. The handle of the cock shall be parallel to the pipe in which it is located
when the cock is open.
2.
The range of the scale on the dial of a steam boiler steam gauge shall be not less
than 30 psi. The gauge shall be provided with effective stops for the indicating
pointer at the zero point and at the maximum pressure point. The travel of the
pointer from zero to full scale shall be at least three inches.