15 MAC Pt. 10, R. 3.4.15
Air and Ventilation Requirements: A permanent source of outside air shall be
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.4.15
Air and Ventilation Requirements: A permanent source of outside air shall be
provided for each boiler room to permit satisfactory combustion of fuel as well as
proper ventilation of the boiler room under normal operating conditions.
1.
The total requirements of the burners for all fired pressure vessels in the boiler
room must be used to determine the louver sizes whether fired by coal, oil or
gas; however, the minimum net free louvered area must not be less than one
square foot. The following table or formula shall be used to determine the net
louvered area in square feet:
Input BTU/Hour Required Air
Cu.Ft./Min.
Min. Net Louvered
Area Sq. Ft.
500,000
1.0
1,000,000
1.0
2,000,000
1.6
3,000,000
2.5
4,000,000
3.3
5,000,000
4.1
6,000,000
5.0
7,000,000
5.8
8,000,000
6.6
9,000,000
7.5
10,000,000
8.3
(BTU/HR ÷ 100) X 1.5
60 ÷ 300 = Min. Net Area Req. Sq. Ft.
2.
When mechanical ventilation is used in lieu of (a) the supply of combustion
and ventilation air to the boiler room and the firing device shall be interlocked
with the fan so the firing device will not operate with the fan off. The velocity
of the air through the ventilating fan shall not exceed 500 feet per minute, and
the total air delivered shall be equal to or greater than shown in (1.).