33 MAC Pt. 208, R. 5.7
Critical Facilities
Cite as 33 Miss. Admin. Code Pt. 208, R. 5.7
Critical Facilities. Construction of new and substantially improved critical facilities
shall be located outside the limits of the special flood hazard area (one percent chance
floodplain). Construction of new critical facilities shall be permissible within the SFHA only if
no feasible alternative site is available and access to the facilities remains available during a 0.2
percent chance flood. Critical facilities constructed within the SFHA shall have the lowest floor
elevated three feet six inches above the base flood elevation at the site (or to the 0.2 percent
chance flood elevation whichever is greater). Floodproofing and sealing measures must be
implemented to ensure that toxic substances will not be displaced by or released into
floodwaters. Multiple access routes, elevated to or above the 0.2 percent flood elevation, shall be
provided to all critical facilities to the maximum extent possible. Critical facilities must not only
be protected to or above the 0.2 percent chance flood but must remain operable during such an
event. The community’s flood response plan must list facilities considered critical in a flood,
since loss of access can cause a critical situation. Other facilities in low risk flood zones that may
also be needed to support flood response efforts must be included on the critical facility list. The
use of any structure shall not be changed to a critical facility, where such a change in use will
render the new critical facility out of conformance with this section. The list of the operators of
the critical facilities affected by flooding must be updated at least annually, as part of the
community critical facility planning procedures.