Classification of Systems During Connection-Event Inspections by Certified
Cite as Miss. Admin. Code Pt. 18, R. 1.6.8
Classification of Systems During Connection-Event Inspections by Certified
Installers.
An IOWDS inspected under Rule 1.6.6 shall be classified as one of the following:
1.
Operational – A system functioning as intended with no evidence of treated or partially-
treated effluent leaving the property and no evidence of surfacing effluent. The Certified
Installer shall submit proper certifying documents confirming operational status.
2.
Non-operational – A system not in daily use on the day of inspection. The Certified
Installer shall notify the Property Owner to contact the Division for repair/replacement
recommendations for use should the existing system fail once in use.
3.
Failed Inspection – Any IOWDS which has evidence of treated effluent leaving the
property, or partially-treated effluent seeping to the surface. The Certified Installer shall
notify the Property Owner to contact the Division for acceptable system repair or system
replacement options compliant with the law and regulations.