MAC Pt. 18, R. 5.1.4
Design
Cite as Miss. Admin. Code Pt. 18, R. 5.1.4
Design.
All septic tanks (prefabricated concrete, steel, fiberglass or polyethylene) must be designed
according to minimum standards as follows:
1.
General:
a.
The septic tank shall be watertight, structurally sound and not subject to excessive
corrosion or decay. The outlet of the septic tank should be placed so as not to be
located below the Seasonal High Water Table.
b.
The minimum hydraulic detention time of the septic tank must be two (2) days
(48 hours) based on daily sewage flows. In no case shall the septic tank have a
minimum effective liquid capacity of less than seven hundred fifty (750) gallons.
c.
All tanks manufactured in two (2) sections must have an interlocking type joint.
Tanks manufactured in two sections must be sealed and joined with an approved
sealant such as butyl rubber or other approved pliable sealant that is waterproof,
corrosion-resistant and is warranted by the manufacturer for sealing concrete
septic tanks.
d.
All septic tanks with a capacity of greater than fifteen hundred (1,500) gallons
shall be deemed structurally sound by a licensed Professional Engineer via
stamped letter.
2.
Tank Dimensions:
a.
The inside length of a rectangular septic tank shall be a minimum of 1.5 times the
width. The minimum inside width of a septic tank shall not be less than 3.5 feet.
b.
The minimum liquid depth of all septic tanks shall be thirty (30) inches.
c.
A minimum air space of seventeen (17) percent of the liquid depth must be
provided.
3.
Tank Inlet and Outlet:
a.
The inlet and outlet of the septic tank must be large enough to accommodate a
four (4) inch Schedule Forty (40) pipe and be equipped with a sanitary tee or
baffle.
b.
The inlet and outlet pipes must extend a minimum of three (3) feet onto
undisturbed soil before entering and after exiting the septic tank.
c.
The inlet invert shall enter the septic tank a minimum of two (2) inches above the
liquid level of the tank. The inlet tee or baffle shall be provided to divert the
incoming sewage downward and extend a minimum of six (6) inches below the
liquid level of the tank.
d.
The outlet tee or baffle shall extend eighteen (18) inches below the liquid depth of
the tank.
4.
Baffle Walls and Two Compartment Tanks:
a.
The first compartment shall be between sixty (60) and sixty-seven (67) percent of
the total capacity of the tank.
b.
The baffle forming the two (2) compartments shall have an opening four (4) to six
(6) inches wide, located in the center of the baffle and at fifty (50) percent of the
liquid depth of the tank.
c.
If the tank is to be made of concrete, the baffle wall shall be constructed of
concrete and be structurally sound. This shall be interpreted as a minimum of
three thousand (3,000) pound concrete containing six (6) inch by six (6) inch
number ten (10) concrete wire and having a minimum thickness of two and one-
half inches.
d.
Baffle walls shall be securely and permanently fastened to the septic tank. All
fasteners shall be of sound and durable material not subject to corrosion or decay.
5.
Access Openings:
a.
A resealable opening above each tee and baffle must be provided in each tank top.
These openings provide for cleaning or rodding out of the inlet or outlet pipe and
access for pumping.
b.
Openings covering the inlet and outlet shall be accessible and visible at finished
grade once the septic tank is covered.
c.
Rectangular openings shall be a minimum of fifteen (15) inches by fifteen (15)
inches as measured from the bottom side of the lid of the septic tank.
d.
Circular openings shall be a minimum diameter of seventeen (17) inches as
measured from the bottom side of the lid of the septic tank.
e.
Multi-slab tank lids and one-piece lids that can be removed manually to include
but not limited to steel and fiberglass require the slab or lid over the inlet and
outlet tee or baffle to have a minimum access opening of 6 inches by 6 inches if
rectangular or 8 inches in diameter if round.
f.
All concrete covers, access openings and slabs must have a handle of 3/8 inch
steel rebar or other corrosion resistant material of the size necessary to facilitate
the removal of the cover, opening or slab.