MAC Pt. 18, R. 5.2.4
Inlet and Outlet
Cite as Miss. Admin. Code Pt. 18, R. 5.2.4
Inlet and Outlet.
1.
The inlet and outlet must be Schedule Forty (40) pipe four (4) inches in diameter. A three
(3) inch house sewer stubout, when used, shall be connected to the four (4) inch pipe
from the septic tank inlet using manufactured fittings designed for that purpose.
2.
The inlet and outlet pipe (Schedule 40, four (4) inch) must extend a minimum of three (3)
feet onto undisturbed soil before entering and after exiting the Advanced Treatment
System.