MAC Pt. 18, R. 5.3.2
General Requirements
Cite as Miss. Admin. Code Pt. 18, R. 5.3.2
General Requirements.
1.
Pump chambers shall have a storage volume as required per each system type; for
subsurface drip, overland disposal and spray systems. Pump chambers for septic tank
systems shall be a minimum of 400 gallons.
2.
The pump chamber shall be constructed to withstand normally encountered earth
pressures and manufactured with approved materials resistant to the corrosive effects of
wastewater, common household chemicals and chemicals used for disinfection.
3.
The pump chamber shall be equipped with an audible high water alarm.
4.
The pump chamber shall have a grade level access large enough to allow servicing and/or
removal of the largest component in the chamber. Access ports shall be protected against
unauthorized entrance.
5.
The pump chamber shall be vented through the grade level access or by means of a
separate vent. In either case the vent shall be a minimum of one inch in diameter.
6.
All openings shall be sealed with a mastic, butyl rubber or other pliable sealant that is
waterproof, corrosion resistant and approved for use in contact with wastewater and
chemicals used for disinfection, in a manner to prevent the entrance of surface and
groundwater.
7.
When pumping to normally gravity fed systems the use of a stilling chamber (baffled
distribution box) shall be required. The stilling chamber must be sized larger than the
maximum volume pumped in a single dose so as not to flood the chamber.
8.
The stilling chamber shall be constructed and placed so it will drain between doses into
the treatment and/or disposal site.