MAC Pt. 18, R. 5.7.5
Pump/Dosing Chambers: Spray Irrigation
Cite as Miss. Admin. Code Pt. 18, R. 5.7.5
Pump/Dosing Chambers: Spray Irrigation.
1.
The pump/dosing chamber shall have a minimum working capacity of 1.5 times the
maximum volume produced for timed-dose, or should be sized per the manufacturer’s
specifications for demand-dose systems.
2.
The dosing chamber shall be equipped with an audible high-water alarm.
3.
The pump/dosing chamber shall have a grade level access large enough to allow
servicing and/or removal of the largest component in the chamber. Access ports shall be
protected against unauthorized entrance or removal.
4.
The pump/dosing chamber shall be vented through the grade level access or by means of
a separate vent. In either case the vent shall be a minimum of one (1) inch in diameter.
5.
The pump/dosing chamber shall be made of material resistant to the corrosive effects of
wastewater, chemicals used for disinfection and designed to withstand the lateral and
bearing loads to which it is expected to be subjected.