11 MAC Pt. 5, R. 2.4
Leak Detection
Cite as 11 Miss. Admin. Code Pt. 5, R. 2.4
Leak Detection.
§280.40 General requirements for all UST systems.
(a) Owners and operators of new and existing UST systems must provide a method, or
combination of methods, of leak detection that:
(1) Can detect a leak from any portion of the tank and the connected underground
piping and ancillary equipment that routinely contains product;
(2) Is installed, calibrated, operated, and maintained in accordance with the manufacturer's
instructions and any applicable code of practice listed in §280.13, including routine
maintenance and service checks for operability or running condition;
(3) Beginning on [three years after effective date of rule], is operated and maintained, and
electronic and mechanical components are tested for proper operation. The leak
detection equipment shall be tested for proper operation in accordance with one of the
following: manufacturer’s instructions; a code of practice developed by a nationally
recognized association or independent testing laboratory; or requirements determined
by MDEQ to be no less protective of human health and the environment than the two
options listed above. A test of the proper operation must be performed at least every 12
months and, at a minimum, as applicable to the facility, cover the following
components and criteria:
(i) Automatic tank gauge and other controllers: test alarm; verify system configuration;
test battery backup;
(ii) Probes and sensors: inspect for proper placement; remove any residual buildup;
ensure floats move freely; ensure shaft is not damaged; ensure cables are free of
kinks and breaks; test alarm operability and communication with controller;
(iii)Automatic line leak detector: test operation to meet criteria in § 280.44(a) by
simulating a leak;
(iv) Vacuum pumps and pressure gauges: ensure proper communication with sensors
and controller; and
(v) Hand-held electronic sampling equipment associated with groundwater and vapor
monitoring: ensure proper operation: and
(4) Meets the performance requirements in §280.43, §280.44, §280.45, or Rule 2.10 with any
performance claims and their manner of determination described in writing by the
equipment manufacturer or installer. In addition, methods used must be capable of
detecting the leak rate or quantity specified for that method in the corresponding section
of the rule with a probability of detection of 0.95 and a probability of false alarm of 0.05.
(b) When a leak detection method operated in accordance with the performance standards in
§280.43, §280.44, §280.45, or Rule 2.10 indicates a leak may have occurred, owners and
operators must notify the MDEQ in accordance with Rule 2.5.
(c) Any UST system that can not apply a method of leak detection that complies with the
requirements of this rule must complete the closure procedures in rule 2.7.
§280.41 Requirements for petroleum UST systems.
Owners and operators of petroleum UST systems must provide leak detection for tanks, piping,
and ancillary equipment within secondary containment sumps as follows:
(a) Tanks. Tanks installed on or after October 1, 2008, must be monitored at least every 30 days
for leaks in accordance with §280.43(g). Tanks installed before October 1, 2008, must be
monitored at least every 30 days for leaks using one of the methods listed in §280.43 (d)
through (h) except that:
(1) UST systems that meet the performance standards in §280.20 or §280.21, and the
monthly inventory control requirements in §280.43 (a) or (b), may use tank tightness
testing (conducted in accordance with §280.43(c)) at least every 5 years until December
22, 1998, or until 10 years after the tank is installed or upgraded under §280.21(b),
whichever is later;
(2) Tanks with capacity of 550 gallons or less may use weekly tank gauging (conducted in
accordance with §280.43(b)).
(b) Piping. Underground piping that routinely contains regulated substances must be monitored
for leaks in a manner that meets one of the following requirements:
(1) Pressurized piping. Underground piping that conveys regulated substances under pressure
must be equipped with an automatic line leak detector conducted in accordance with
§280.44(a) except for life safety/critical function UST systems, in which case, an
alternative method of leak detection must be approved by MDEQ; and
(i) Pressurized piping installed before October 1, 2008, must have an annual line tightness
test conducted in accordance with §280.44(b) or have monthly monitoring conducted
in accordance with §280.44(c) or §280.44(d).
(ii) Pressurized piping installed on or after October 1, 2008, must be monitored at least
once every 30 days for leaks in accordance with §280.44(c).
(2) Suction piping. Underground piping that conveys regulated substances under
suction must:
(i) Have a line tightness test conducted at least every 3 years and in
accordance
with §280.44(b), or use a monthly monitoring method conducted in accordance with
§280.44(c) or §280.44(d) if it was installed before October 1, 2008.
No release detection is required for suction piping that is designed and
constructed to meet the following standards:
(A) The below-grade piping operates at less than atmospheric pressure;
(B) The below-grade piping is sloped so that the contents of the pipe will drain
back into the storage tank if the suction is released;
(C) Only one check valve is included in each suction line;
(D) The check valve is located directly below and as close as practical to the
suction pump; and
(E) A method is provided that allows compliance with paragraphs (b)(2)(iii)
(B)-(D) of this rule to be readily determined.
(ii)
Must be monitored at least every 30 days for leaks in accordance with
§280.44(c) if it was installed on or after October 1, 2008.
(c) Ancillary equipment in secondary containment sumps. Ancillary equipment within
secondary containment sumps where the containment sumps were installed on or after
October 1, 2008, must be monitored at least every 30 day for leaks or ingress of water in
accordance with §280.45.
§280.42 Requirements for hazardous substance UST systems.
Owners and operators of hazardous substance UST systems must provide leak detection that
meets the following requirements:
(a) Leak detection at existing UST systems must meet the requirements for petroleum UST
systems in §280.41. By December 22, 1998, all existing hazardous substance UST systems
must meet the leak detection requirements for new systems in paragraph (b) of this rule.
(b) Leak detection at new hazardous substance UST systems must meet the following
requirements:
(1) Secondary containment systems must be designed, constructed and installed to:
(i) Contain regulated substances leaked from the tank system until they are detected
and removed;
(ii) Prevent the release of regulated substances to the environment at any time during
the operational life of the UST system; and
(iii)Be checked for evidence of a leak at least every 30 days.
Note: The provisions of 40 CFR 265.193, Containment and Detection of Releases, may be used to
comply with these requirements.
(2) Double-walled tanks must be designed, constructed, and installed to:
(i) Contain a leak from any portion of the inner tank within the outer wall;
(ii) Detect the failure of the inner wall.
(3) External liners (including vaults) must be designed, constructed, and installed to:
(i) Contain 100 percent of the capacity of the largest tank within its boundary;
(ii) Prevent the interference of precipitation or ground-water intrusion with the ability to
contain or detect a leak of regulated substances; and
(iii)Surround the tank completely (i.e., it is capable of preventing lateral as well as
vertical migration of regulated substances).
(4) Underground piping must be equipped with secondary containment that satisfies the
requirements of paragraph (b)(1) of this rule. In addition, underground piping that
conveys regulated substances under pressure must be equipped with an automatic line
leak detector in accordance with §280.44(a).
(5) Other methods of leak detection may be used if owners and operators:
(i) Demonstrate to the MDEQ that an alternate method can detect a release of the stored
substance as effectively as any of the methods allowed in §280.43(b) through (h)
can detect a release of petroleum;
(ii) Provide information to the MDEQ on effective corrective action technologies, health
risks, and chemical and physical properties of the stored substance, and the
characteristics of the UST site; and,
(iii) Obtain approval from the MDEQ to use the alternate release detection method
before the installation and operation of the new UST system.
§280.43 Methods of leak detection for tanks.
Each method of leak detection for tanks used to meet the requirements of §280.41 must be
conducted in accordance with the following:
(a) Inventory control. Product inventory control (or another test of equivalent performance) must
be conducted monthly to detect a leak of at least 1.0 percent of flow-through plus 130
gallons on a monthly basis in the following manner:
(1) Inventory volume measurements for regulated substance inputs, withdrawals, and the
amount still remaining in the tank are recorded each operating day;
(2) The equipment used is capable of measuring the level of product over the full range of the
tank's height to the nearest one-eighth of an inch;
(3) The regulated substance inputs are reconciled with delivery receipts by measurement of
the tank inventory volume before and after delivery;
(4) Deliveries are made through a drop tube that extends to within one foot of the tank
bottom;
(5) Product dispensing is metered and recorded within the local standards for meter
calibration or an accuracy of 6 cubic inches for every 5 gallons of product withdrawn;
and
(6) The measurement of any water level in the bottom of the tank is made to the nearest one-
eighth of an inch at least once a month.
(b) Manual tank gauging. Manual tank gauging must meet the following requirements:
(1) Tank liquid level measurements are taken at the beginning and ending of a period using
the appropriate minimum duration of test value in the table below during which no liquid is
added to or removed from the tank;
(2) Level measurements are based on an average of two consecutive stick readings at both
the beginning and ending of the period;
(3) The equipment used is capable of measuring the level of product over the full range of the
tank's height to the nearest one-eighth of an inch;
(4) A leak is suspected and subject to the requirements of Rule 2.5 if the variation between
beginning and ending measurements exceeds the weekly or monthly standards in the
following table:
Nominal tank capacity
Minimum Duration
Weekly standard
(one test)
Monthly standard
(average of four tests)
550 gallons or less
36 hours
10 gallons
5 gallons.
551-1,000 gallons
(when tank diameter is 64 inches) 44 hours
9 gallons
551-1,000 gallons
(when tank diameter is 48 inches)
58 hours
12 gallons
551-1,000 gallons
36 hours
13 gallons
7 gallons.
1,001-2,000 gallons
36 hours
26 gallons
13 gallons.
(5) Only tanks of 550 gallons or less nominal capacity may use this as the sole method of leak
detection. Tanks of 551 to 2,000 gallons may use this method in place of manual
inventory control in §280.43(a). Tanks of greater than 2,000 gallons nominal capacity
may not use this method to meet the requirements of this rule.
(c) Tank tightness testing. Tank tightness testing (or another test of equivalent performance) must
be capable of detecting a 0.1 gallon per hour leak rate from any portion of the tank that
routinely contains product while accounting for the effects of thermal expansion or
contraction of the product, vapor pockets, tank deformation, evaporation or condensation,
and the location of the water table.
(d) Automatic tank gauging. Equipment for automatic tank gauging that tests for the loss of
product must meet the following requirements:
(1) The automatic product level monitor test can detect a 0.2 gallon per hour leak rate from
any portion of the tank that routinely contains product. The equipment must be
capable of visual or audible alarms and the equipment must be capable of printing the
completed 0.2 gallon per hour leak rate test; and
(2) The equipment is inspected for proper operation at least once every 12 months. The
inspection must be conducted in accordance with the manufacturer's periodic
maintenance specifications and any applicable code of practice listed in §280.13.
(3) The test must be performed with the system operating in one of the following modes:
(i) In-tank static testing conducted at least once every 30 days; or
(ii) Continuous in-tank leak detection operating on an uninterrupted basis or operating
within a process that allows the system to gather incremental measurements to
determine the leak status of the tank at least once every 30 days.
(e) Vapor monitoring. Testing or monitoring for vapors within the soil gas of the excavation zone
must meet the following requirements:
(1) The materials used as backfill are sufficiently porous (e.g., gravel, sand, crushed rock) to
readily allow diffusion of vapors from releases into the excavation area;
(2) The stored regulated substance, or a tracer compound placed in the tank system, is
sufficiently volatile (e.g., gasoline) to result in a vapor level that is detectable by the
monitoring devices located in the excavation zone in the event of a release from the tank;
(3) The measurement of vapors by the monitoring device is not rendered inoperative by the
ground water, rainfall, or soil moisture or other known interferences so that a release
could go undetected for more than 30 days;
(4) The level of background contamination in the excavation zone will not interfere with the
method used to detect releases from the tank;
(5) The vapor monitors are designed and operated to detect any significant increase in
concentration above background of the regulated substance stored in the tank system, a
component or components of that substance, or a tracer compound placed in the tank
system;
(6) In the UST excavation zone, the site is assessed to ensure compliance with the
requirements in paragraphs (e) (1) through (4) of this rule and to establish the number and
positioning of monitoring wells that will detect releases within the excavation zone from
any portion of the tank that routinely contains product and
(7) Monitoring wells are clearly marked and secured to avoid unauthorized access and
tampering.
(f) Ground-water monitoring. Testing or monitoring for liquids on the ground water must meet
the following requirements:
(1) The regulated substance stored is immiscible in water and has a specific gravity of less
than one;
(2) Ground water is never more than 20 feet from the ground surface and the hydraulic
conductivity of the soil(s) between the UST system and the monitoring wells or devices is
not less than 0.01 cm/sec (e.g., the soil should consist of
gravels, coarse to medium
sands, coarse silts or other permeable materials);
(3) The slotted portion of the monitoring well casing must be designed to prevent
migration of natural soils or filter pack into the well and to allow entry of regulated
substance on the water table into the well under both high and low ground-water
conditions;
(4) Monitoring wells shall be sealed from the ground surface to the top of the filter pack;
(5) Monitoring wells or devices intercept the excavation zone or are as close to it as is
technically feasible;
(6) The continuous monitoring devices or manual methods used can detect the presence of at
least one-eighth of an inch of free product on top of the ground water in the monitoring
wells;
(7) Within and immediately below the UST system excavation zone, the site is assessed to
ensure compliance with the requirements in paragraphs (f) (1) through (5) of this rule
and to establish the number and positioning of monitoring wells or devices that will
detect releases from any portion of the tank that routinely contains product; and
(8) Monitoring wells are clearly marked and secured to avoid unauthorized access and
tampering.
(g) Interstitial monitoring. Monitoring of the space between the inner (primary) and the outer
(secondary) tank walls may be used, but only if the system is designed, constructed and
installed to meet the following requirements:
(1) The sampling or testing method can detect a release from any portion of the tank that
routinely contains product;
(2) The sampling or testing method can detect ingress of external fluids (groundwater or other
fluids not intended as monitoring fluids) into the interstice;
(3) Records must be maintained that show the interstice has been checked at least every 30
days for evidence of a leak or ingress of external fluids;
(i) If the interstice is monitored continuously, records must document that the electronic
device monitoring the interstice is in communication with
the control console at
least monthly;
(ii) If the interstice is monitored continuously, records must document the alarm history and
provide the response action taken, appropriate reporting (if applicable) and
reconciliation of each alarm;
(iii)Any electronic device that monitors the interstice must be tested at least once every 12
months for proper function. The functionality test must simulate a leak and be in
accordance with the manufacturer's
specifications and any applicable industry
code or recommended practice listed in §280.13; and
(4) Any regulated substance that enters the interstice must be removed within 24 hours of
discovery or another time frame determined by the MDEQ to be reasonable.
(h) Other methods. Any other type of leak detection method, or combination of methods, can be
used if:
(1) It can detect a 0.2 gallon per hour leak rate or a release of 150 gallons within a
month
with a probability of detection of 0.95 and a probability of false alarm of 0.05; or
(2) The MDEQ may approve another method if the owner and operator can demonstrate that
the method can detect a release as effectively as any of the methods
allowed
in
paragraphs (c) through (h) of this rule. In comparing
methods, the MDEQ shall
consider the size of leak that the method can detect and the frequency and reliability with
which it can be detected. If the method is approved, the owner and operator must comply
with any conditions imposed by the MDEQ on its use to ensure the protection of human
health and the environment.
§280.44 Methods of leak detection for piping.
Each method of leak detection for piping used to meet the requirements of §280.41 must be
conducted in accordance with the following:
(a) Automatic line leak detectors. Methods which alert the operator to the presence of a leak by
restricting or shutting off the flow of regulated substances through piping or triggering an
audible or visual alarm may be used only if they detect leaks of 3 gallons per hour at 10
pounds per square inch line pressure within 1 hour. Testing must be performed in
accordance with the following requirements:
(1) Frequency.
(i) Automatic line leak detectors installed on or after October 1, 2008, must be tested in
accordance with the requirements of this rule at startup to verify proper operation
and at least once every 12 months thereafter.
(ii) Automatic line leak detectors installed before October I, 2008, must be tested in
accordance with the requirements of this rule by no later than October 1, 2009, and at
least once every 12 months thereafter.
(2) Criteria. All testing of automatic line leak detectors must be conducted in accordance with
the manufacturer's specifications and any applicable code of practice listed in §280.13
and
(i) Involve the simulation of a leak in the piping at the dispenser that is at the highest
elevation above the submersible pump. If there is no change in elevation, the test must
be conducted at the dispenser that is the furthest away from the submersible pump;
(ii) Be conducted with the leak detector installed in the system as it normally would be
during operation;
(iii)Verify that the leak detector is capable of detecting a leak equivalent to 3 gallons per
hour at 10 pounds per square inch line pressure within 1 hour; and
(iv) Be conducted finitely and the test results reported quantitatively.
(3) Records. A written record documenting the testing of automatic line leak detectors must
be maintained (in accordance with §280.35) to demonstrate compliance with this section.
These records must provide the results of the last two (2) tests required in this section.
(b) Line tightness testing. A periodic test of piping may be conducted only if it can detect a 0.1
gallon per hour leak rate at one and one-half times the operating pressure and the test is
conducted in accordance with manufacturer specifications or other recommended code of
practice.
(c) Interstitial monitoring. Monitoring of the space between the inner (primary) and the outer
(secondary) pipe walls may be used, but only if the system is designed, constructed and
installed to meet the following requirements:
(1) The sampling or testing method can detect a leak from any portion of the pipe that
routinely contains product;
(2) The sampling or testing method can detect ingress of water or other external fluids into
the interstice;
(3) Records must be maintained that show the interstice has been checked at least every 30
days for evidence of a leak or ingress of external fluids;
(i) If the interstice is monitored continuously, records must document that the electronic
device monitoring the interstice is in communication with the control console at least
monthly;
(ii) If the interstice is monitored continuously, records must document the alarm history and
provide the appropriate reporting (if applicable) and reconciliation of each alarm;
(iii)Any electronic device that monitors the interstice must be tested at least once every 12
months for proper function. The functionality test must be in accordance with the
manufacturer's specifications and any applicable industry code or recommended
practice listed in §280.13. The functionality test must simulate a leak; and
(4) Any regulated substance that enters the interstice must be removed within 24 hours of
discovery or another time frame determined by the MDEQ to be reasonable.
(d) Applicable tank methods. Any of the methods in §280.43 (e), (0 or (h) may be used if they
are designed to detect a leak from any portion of the underground piping that routinely
contains regulated substances.
§ 280.45 Methods of leak detection for ancillary equipment within secondary containment
sumps
Each method of leak detection for ancillary equipment within secondary containment sumps used to
meet the requirements of §280.31 and §280.41 must be conducted in accordance with the following:
(a) Visual Monitoring. Testing or monitoring for liquids in the containment sump or in the
interstice of a double walled containment sump must meet the following requirements:
(1) Records must be maintained that show the containment sump or the interstice of a double
walled containment sump has been checked at least every 30 days for evidence of a leak
or ingress of external fluids
(2) Once measurements have been recorded, any fluids in the containment sumps shall be
removed and properly dispose
(b) Electronic Monitoring. Testing or monitoring for liquids in the containment sump must meet
the following requirements:
(1) The electronic sensors must be securely mounted permanently within the sump to prevent
tampering, removal, or adjustment of the sensor
(2) The electronic sensors must be placed no more than 1 inch off the bottom of the
containment sump
§ 280.46 Leak detection recordkeeping.
All UST system owners and operators must maintain records in accordance with §280.35
demonstrating compliance with all applicable requirements of this rule. These records must include
the following:
(a) All written performance claims pertaining to any leak detection system used, and the manner
in which these claims have been justified or tested by the equipment manufacturer or
installer, must be maintained for 5 years, or for another reasonable period of time
determined by the MDEQ, from the date of installation;
(b) The results of any sampling, testing, or monitoring must be maintained for at least 1 year, or
for another reasonable period of time determined by the MDEQ, except that the results of
tank tightness testing conducted in accordance with §280.43(c) must be retained until the next
test is conducted; and
(c) The results of annual operation tests conducted in accordance with §280.40(a)(3) must be
maintained for three years. At a minimum, the results must list each component tested, indicate
whether each component tested meets criteria in § 280.40(a)(3) or needs to have action taken, and
describe any action taken to correct an issue;
(d) Written documentation of all calibration, maintenance, and repair of leak detection equipment
permanently located on-site must be maintained for at least one year after the servicing work
is completed, or for another reasonable time period determined by the MDEQ. Any schedules
of required calibration and maintenance provided by the leak detection equipment
manufacturer must be retained for 5 years from the date of installation.