ARM 37.115.903. NUMBER OF FIXTURES REQUIRED
Cite as Mont. Admin. R. 37.115.903
(1) In facilities built or extensively remodeled after March 1, 2010, showers, toilets, urinals, and hand washing facilities shall, at a minimum, meet the number required by Table 4.
(2) A facility may substitute urinals for up to 50 percent of the toilets in the men's room.
(3) All fixtures shall be properly protected as required by the appropriate plumbing code.
(4) All fixtures must be so designed that they may be readily cleaned, disinfected, and maintained.
(5) Hand washing facilities must provide liquid, foam, or powdered soap and either disposable towels with adjacent waste receptacles or hand blowers.
(6) One drinking fountain is required for every 1000 bathers.
(7) A service sink is required for each facility. It shall be located somewhere other than the dressing rooms.
Table 4. Fixture Ratio Required.
First 1500
Males
First 1500
Females
Additional Males
Over 1500
Additional
Females over
1500
Toilets water closet)
1:75 for first
1500
1:40
1:120
1:60
Hand sinks
1:200
1:150
1:200
1:150
Showers
1:50
1:50
1:50
1:50