NDAC 24.1-06-01-10
Requirement for electrical installations
Cite as N.D. Admin. Code ยง 24.1-06-01-10
Electrical installations shall be planned to provide adequate capacity for the load.
1.
Wiring systems shall have conductors of sufficient capacity to furnish each outlet without
excessive line loss or voltage drop. The voltage drop shall not exceed five percent at the
farthest outlet of power, heating and lighting loads, or combinations of such loads. (See
appendix for example.)
2.
All wiring materials and equipment shall be listed by nationally recognized testing laboratories
to safeguard life and property. It is the duty of the electrical installer to secure permission from
the executive director to use materials, devices, and methods of installation not specifically
covered by these standards. Equipment not approved under a testing laboratory category
shall be evaluated by a registered professional engineer and recorded on evaluation forms
accepted by the board.
Exception: Manufacturing firms that install industrial machinery for use by the firm itself and
employ professional engineers may evaluate the industrial machinery according to NFPA 79 or
UL 508 Standards. This evaluation shall be maintained with the equipment at all times and a
copy submitted to the board.
3.
When wiring public school buildings, approval shall be received from the department of public
instruction and the board.
4.
Overhead conductors shall not cross over water wells or known sites where water wells may
be drilled. A minimum distance of twenty feet [6.10 meters] in all directions shall be maintained
for overhead conductors.
5.
In the wiring of nursing homes and hospitals, reference shall be made to the state department
of health for special requirements pertaining to operating rooms, delivery rooms, and
emergency lighting.
6.
Aluminum or copper-clad aluminum conductors in sizes smaller than no. 6 must be used only
for class II and class III circuits.
7.
All new construction shall follow the energy-efficient related requirements for design and
construction of buildings in accordance with the locally adopted codes or the State Building
Code.
8.
In any room of an existing building where the sheetrock or wall covering has been removed
from all walls, the electrical wiring requirements must comply with the 2026 edition, National
Electrical Code (first version, printed in 2025).
9.
If the occupancy of an existing building or part of an existing building is changed, the electrical
wiring and equipment of the building or portion thereof that contains the proposed occupancy
must comply with the 2026 edition, National Electrical Code (first version, printed in 2025).