Water damaged electrical equipment wiring and equipment exposed to water damage must comply
with the following:
1.
All breaker panel boards, breakers, fuses, disconnect switches, controllers, receptacles,
switches, light fixtures, and electric heaters that have been submerged or exposed to water
damage must be replaced or all electrical equipment, switchgear, motor control centers,
boilers and boiler controls, electric motors, transformers, and other similar equipment, such as
appliances, water heaters, dishwashers, ovens, and ranges that have been submerged must
be reconditioned by the original manufacturer or by its approved representative or replaced.
2.
Electrical wiring may require replacement depending on the type of wire or cable and what
application it was listed for.
3.
Splices and terminations must be checked to ensure compliance with article 110.14, 2026
edition, National Electrical Code (first version, printed in 2025).
4.
Energized electrical panels that have been submerged must be de-energized to prevent loss
of life and property.
Other recommendations can be found in "Guidelines for Handling Water Damaged Electrical