NDAC 24.1-06-01-40
Smoke alarms, heat alarms, fire alarm systems, and carbon monoxide alarm
Cite as N.D. Admin. Code ยง 24.1-06-01-40
requirements for evacuation and life safety.
Alarm systems stated in this section must be installed in accordance with the locally adopted codes
or the State Building Code and state fire code under the supervision of a master or class B electrician.
In new construction, all alarm systems must receive their primary power from the building wiring and
when primary power is interrupted, shall receive power from a battery. Wiring must be permanent and
without a disconnecting switch other than those required for overcurrent protection.
1.
Dwelling units, congregate residences, and hotel or lodging house guest rooms that are used
for sleeping purposes shall be provided with smoke alarms. Alarms must be installed in
accordance with the approved manufacturer's instructions.
a.
When more than one smoke alarm is required to be installed within an individual dwelling
unit the alarm devices must be interconnected in such a manner that the actuation of one
alarm will activate all of the alarms in the individual unit. Smoke alarms must be installed
in the following locations:
(1)
In each sleeping room.
(2)
Outside each separate sleeping area in the immediate vicinity of the sleeping
rooms.
(3)
On each additional story of the dwelling, including basements and habitable attics
but not including crawl spaces and uninhabitable attics. In dwellings or dwelling
units with split levels and without an intervening door between the adjacent levels, a
smoke alarm installed on the upper level shall suffice for the adjacent lower level
provided that the lower level is less than one full story below the upper level.
(4)
In dwelling units where the ceiling height of a room open to the hallway serving the
bedrooms exceeds that of the hallway by twenty-four inches [60.96 centimeters] or
more, smoke alarms shall be installed in the hallway and in the adjacent room.
b.
Heat alarms. For new construction, an approved heat alarm must be installed in the
attached single tenant garage of a residence and interconnected with the smoke alarms
within the residence.
c.
Household fire alarm systems installed in accordance with NFPA 72 that include smoke
alarms, or a combination of smoke detectors and audible notification device installed as
required by this section for smoke alarms, must be permitted. The household fire alarm
system must provide the same level of smoke detection and alarm as required by this
section for smoke alarms. Where a household fire warning system is installed using a
combination of smoke detector and audible notification device, it must become a
permanent fixture of the occupancy and owned by the homeowner. The system must be
monitored by an approved supervising station and be maintained in accordance with
NFPA 72 upper level.
2.
Apartment houses, hotels, and congregate residences must be provided with a manual and
automatic fire alarm system in accordance with the requirements of locally adopted codes or
the State Building Code and state fire codes. For two-family dwellings, a notification device
connected to a smoke alarm system in the other dwelling unit must be provided in each
dwelling unit.
3.
An approved carbon monoxide alarm must be installed in dwelling units within which fuel-fired
appliances are installed and in dwelling units that have attached garages in the following
locations:
a.
Outside each sleeping area in the immediate vicinity of the bedrooms.
b.
On every habitable level.
c.
In each bedroom or its attached bathroom within which a fuel-fired appliance is located.
If more than one carbon monoxide alarm must be installed within an individual dwelling unit,
the alarm devices must be interconnected to activate all alarms in the individual dwelling unit if
one alarm is activated.
4.
Rooms and areas within dwelling units, basements and attached garages in which an energy
storage system is installed must be protected by smoke alarms. The smoke alarm must
receive power from the premise wiring and be interconnected to any existing smoke alarm
system. A heat detector listed and interconnected must be installed if a smoke alarm cannot
based on its listing.
A condensed guide is included in the appendix, and for further information consult the locally
adopted codes or the State Building Code and state fire codes.