NDAC 24.1-06-02-50
(NEC 250) Grounding and bonding
Cite as N.D. Admin. Code ยง 24.1-06-02-50
Grounding and bonding must conform to article 250, 2026 edition, National Electrical Code (first
version, printed in 2025).
1.
At motor connections, a bonding jumper sized in accordance with table 250.122, 2026 edition,
National Electrical Code (first version, printed in 2025), must be provided around all flexible
conduit. The bonding jumper is not required if a separate grounding conductor is included.
2.
Grounding of metal outdoor lighting standards.
a.
Definition of lighting standard is a pole exceeding twelve feet [3.66 meters] in height
measured from the bottom of the base or from the intended grade level of poles.
b.
The metal lighting standard must be connected to a one-half inch [12.70-millimeter] by
ten-foot [3.05-meter] copperweld ground rod, or twenty feet [6.10 meters] of one or more
bare or zinc galvanized or other electrically conductive coated steel reinforcing bars or
rods (rebar) of not less than one-half inch [1.27 centimeters] in diameter, by the means of
a bonding jumper. The ten-foot [3.05-meter] ground rod must be driven in the center of
the metal standard base and project slightly above the base. Both ground rod and
equipment grounding conductor must be connected to the metal standards. The bonding
jumper must be in accordance with 2026 edition, National Electrical Code (first version,
printed in 2025), and in no case smaller than no. 8 copper or no. 6 aluminum.
3.
The grounding electrode conductor must be connected to the grounded service conductor in
the enclosure for the service disconnect.