NDAC 24.1-06-03-01
(NEC 300) Wiring methods
Cite as N.D. Admin. Code ยง 24.1-06-03-01
1.
Agricultural buildings. This section covers all buildings housing livestock, poultry, and other
areas of similar or like nature. All electrical panel boards, wiring devices, and equipment must
be installed in accordance with the provisions of article 547, 2026 edition, National Electrical
Code (first version, printed in 2025).
A site-isolating device must be permitted to be installed at the distribution point where two or
more agricultural building structures are supplied from the distribution point.
2.
Electric metallic tubing may not be used in concrete below grade, in concrete slab or masonry
in direct contact with earth. A vapor barrier, if used, has no effect on the requirements of the
section. Electric metallic tubing may not be embedded in earth or fill.
3.
Aluminum conduit may not be installed in contact with earth or embedded in concrete.
4.
The installation of rigid nonmetallic conduit shall comply with the provision of article 352, 2026
edition, National Electrical Code (first version, printed in 2025). Expansion fittings for rigid
nonmetallic conduit shall be provided to compensate for thermal expansion and contraction in
accordance with article 352.44, 2026 edition, National Electrical Code (first version, printed in
2025). When installed outdoors and above grade, one hundred forty degrees Fahrenheit
[60 degrees Celsius] is considered the minimum change in degrees.
5.
Fertilizer rooms, meatpacking plants, salt processing plants, and similar locations are judged
to be occupancies where severe corrosive conditions are likely to be present. It is
recommended that nonmetallic conduit with nonmetallic boxes and fittings be used as the
wiring method for such occupancies. Ferrous and nonferrous metal raceways must be used
providing the raceway, boxes, and fittings are properly protected against corrosion.
6.
Metal raceways or metal clad cable (type MC) rated for the environment must be installed in
the following occupancies:
a.
Hospitals;
b.
Nursing homes;
c.
Related patient care areas; and
d.
Places of assembly.
Metal raceways or metal clad cable (type MC) must be used in fixed wiring methods including
fire alarms along with metal boxes or nonmetallic raceways encased in not less than two
inches of concrete.
Exception 1: As provided in article 640, 2026 edition, National Electrical Code (first version,
printed in 2025), sound reproduction and similar equipment; in article 800, 2026 edition,
National Electrical Code (first version, printed in 2025), communication circuits; and in article
725, 2026 edition, National Electrical Code (first version, printed in 2025), for class 2 and
class 3 remote control and signaling circuits.
Exception 2: Listed two-hour fire-rated cables as permitted in article 695, and article 760, 2026
edition, National Electrical Code (first version, printed in 2025).
Adjacent areas separated by an approved fire barrier may be wired in any approved wiring
method in chapter 3 of the 2026 edition, National Electrical Code (first version, printed in
2025). For the purpose of this section, a fire barrier is defined as a continuous assembly,
vertical or horizontal, in accordance with locally adopted codes or the State Building Code.