NDAC 89-14-01-05
Allowable headwater
Cite as N.D. Admin. Code ยง 89-14-01-05
The allowable maximum headwater when passing the design discharge must be measured from
the bottom of the channel. For arch pipes, the maximum allowable headwater must be based on the
rise of the pipe, and the pipe size category must be the equivalent round pipe size. For multiple pipe
installations, the pipe diameter used to calculate the allowable headwater must be the diameter of the
largest pipe. Tailwater resulting from downstream conditions, either natural or manmade, must be
accounted for in the determination of the crossing's capacity and the resulting headwater. Additional
guidance is provided in the North Dakota department of transportation design manual. If a crossing
results in less than one-half foot [15.24 centimeters] of headloss when passing the appropriate design
discharge, this section does not apply.
Streambed Slope
(feet/mile)
Pipe Size
Allowable Headwater
<5
24" - 54"
pipe diameter + 2 feet
โฅ 60"
1.5 pipe diameters
5 to 10
24" - 36"
pipe diameter + 2 feet
42" - 54"
1.5 pipe diameters
โฅ 60"
2 pipe diameters
>10
โฅ 24"
2 pipe diameters