NDAC 33-03-36-07
General building requirements
Cite as N.D. Admin. Code ยง 33-03-36-07
1.
The facility shall design and equip areas for the comfort and privacy of each patient. Each
patient room must have:
a.
A bed, a mattress, appropriate bedding, a bedside stand, and a chair appropriate to the
needs and comfort of the patient. All furniture and furnishings must be well-constructed,
comfortable, in good repair, kept clean and maintained in a serviceable condition.
b.
Physical space for private visiting.
c.
Physical space to ensure visual privacy for personal care.
d.
If a hardwired communication system is used in patient rooms, each patient must be
provided with a call device. Calls must be initiated by a patient activating a device that
sends a call signal to the staff call station or a hand-held mobile device carried by a staff
member.
e.
A window with a shade.
f.
Patient toilet room with a handwashing station. Each patient shall have access to a toilet
room without having to enter a corridor. Toilets used by patients must allow sufficient
clearance on both sides to enable physical access and maneuvering by caregivers who
may have to assist patients in wheelchair-to-toilet transfers and returns.
2.
The facility shall provide space for storage of clean linen, clean supplies, patient care
equipment, housekeeping, and cleaning supplies.
3.
Grab bars must be installed in all patient toilet rooms, showers, and bathing facilities. Grab
bars must comply with all local, state, and federal requirements.
4.
Ground fault circuit interrupters must be provided for outlets within six feet [1.83 meters] of the
outside edge of a sink.
5.
A convenience portable space heater, portable halogen lamp, household-type electric blanket,
or household-type heating pad may not be used in a facility.
6.
The storage and transfilling of oxygen cylinders or containers must meet the requirements of
the National Fire Protection Association 99, Standard for Health Care Occupancies, 2012
edition.
7.
Electrically powered exhaust ventilation must be provided in all soiled areas, wet areas, toilet
rooms, and storage rooms. Clean storage rooms may also be ventilated by supplying and
returning air from the building's air-handling system. The facility shall provide for adequate
ventilation to assure an odor-free, comfortable environment.
8.
Office space and other areas must be furnished with desks, chairs, lamps, cabinets, benches,
worktables, or other furnishings essential to the proper use of the area.
9.
The facility shall provide a dedicated staff toilet room.
10.
An essential electrical source must provide lighting for at least a ninety-minute duration during
an interruption of the normal electrical supply. Illumination must be automatic and is permitted
to be met by means such as:
a.
Two separate electric lighting systems with independent wiring. One system is permitted
to be supplied from an outside source, such as a public utility service, and the other from
an electric generator on the premises driven by an independent source of power, or
b.
An electric circuit, or circuits, used only for means of egress illumination, with two
independent electric sources arranged so that, on the failure of one, the other will
automatically and immediately operate. One such source is permitted to be a connection
from a public utility, or similar outside power source, and the other an approved storage
battery with suitable provisions to keep it automatically charged.
11.
Emergency lighting for safe egress and access shall be evaluated for all facilities. Each patient
room must have general lighting and night lighting.
12.
Functional testing shall be conducted monthly for not less than thirty minutes for generators
and not less than thirty seconds for battery-powered lighting. Functional testing shall also be
conducted annually for a minimum of ninety minutes.