NDAC 33-07-04.2-15
Details
Cite as N.D. Admin. Code ยง 33-07-04.2-15
All details must meet the following requirements:
1.
Soap in a soap dispenser must be provided at all lavatories and sinks used by personnel for
handwashing.
2.
In new construction, boiler rooms must not be located under any portion of the facility.
3.
Ceilings must be acoustically treated in corridors in resident areas, nurses stations, and dining
and activity areas.
4.
Noise reduction criteria shown in the following table apply to partition, floor, and ceiling
assembly construction in resident areas:
Airborne Sound
Transmission
Class (STC)*
Impact
Insulation
Class (IIC)**
Location
Partitions
Floors
Floors
Resident room to resident room
45
45
51
Public space to resident room ***
50
50
51+
Service areas to resident room ++
55
55
55+
Footnotes:
* Sound transmission class (STC) must be determined by tests in accordance with
methods set forth in ASTM Standard E 90 and ASTM Standard E 413.
** Impact insulation class (IIC) must be determined in accordance with criteria set forth in
HUD FT/TS 24.
*** Public space includes lobbies, dining rooms, recreation rooms, treatment rooms, and
similar spaces.
+ Impact noise limitation applicable only when corridor, public space, or service area is
over resident's room.
++ Service areas include kitchens, elevators, elevator machine rooms, laundries, garages,
maintenance rooms, boiler and mechanical equipment rooms, and similar spaces of high
noise or vibration or both. Mechanical equipment located on the same floor or above or
below the residents' rooms, offices, nurses' stations, and similar occupied spaces must
be effectively isolated from such spaces with respect to noise and vibration.
NOTE: The requirements set forth in this table assume installation methods which will not
appreciably reduce the efficiency of the assembly as tested. Location of electrical
receptacles, grilles, duct work, and other mechanical items, and blocking and sealing of
partitions at floors and ceilings must not compromise the sound isolation required.