NDAC 33.1-14-03-14
Pressure reducing valves
Cite as N.D. Admin. Code ยง 33.1-14-03-14
1.
Where pressure reducing valves are used, one or more relief or safety valves must be
provided on the low-pressure side of the reducing valve in case the piping or equipment on
the low-pressure side does not meet the requirements for the full initial pressure. The relief of
safety valves must be located adjoining or as close as possible to the reducing valve. Proper
protection must be provided to prevent injury or damage caused by the escaping steam from
the discharge. Capacity of the relief valves must be such that the pressure rating of the lower
pressure piping or equipment shall not be exceeded in case the reducing valve sticks open.
2.
The use of hand-controlled bypasses around reducing valves is permissible. The bypass if
used around a reducing valve may not be greater in capacity than the reducing valve unless
the piping or equipment is adequately protected by relief valves or meets the requirements of
the high-pressure system.
3.
A pressure gauge must be installed on the low-pressure side of a reducing valve.
4.
All low-pressure headers and their outlets must be protected by a safety valve or valves
whose combined capacity is equivalent to the total amount of steam that can pass from the
high-pressure system to the lower pressure system.