NDAC 33.1-14-04-02
Appurtenances - Piping and tests
Cite as N.D. Admin. Code ยง 33.1-14-04-02
1.
The inspector shall inspect all boilers and connected appurtenances for their safe operation
and all pressure piping connecting them to the appurtenances and all piping up to and
including the first stop valve, or the second stop valve when two are required.
2.
Any pressure piping to the boiler, such as water column, blowoff valve, feedwater regulator,
superheater, economizer, stop valves, etc., which are shipped connected to the boiler as a
unit, must be hydrostatically tested with the boiler and witnessed by an inspector.
3.
All economizers, whether separately fired or not, and when located within the scope of boiler
external piping, must be constructed to section I of the American Society of Mechanical
Engineers Code. All superheaters must be constructed to section I of the American Society of
Mechanical Engineers Code.
4.
The chief boiler inspector may waive American society of mechanical engineers section I
boiler external piping requirements for new and secondhand boilers of less than forty
horsepower output if the boiler external piping is mechanically installed (i.e., no welding), the
piping does not exceed two inch [5.08 centimeters] national pipe standard in size, the piping is
schedule eighty minimum, and the boiler maximum allowable working pressure does not
exceed one hundred fifty pounds per square inch [1034.22 kilopascals] gauge.