NDAC 33.1-14-05-13
Steam stop valves
Cite as N.D. Admin. Code ยง 33.1-14-05-13
1.
Each discharge outlet, except safety valve, safety relief valves, reheater inlet and outlet, or
superheater inlet connections, must be fitted with a stop valve located at an accessible point
in the steam-delivery line and as near the boiler nozzle as is convenient and practicable.
When such outlets are over two inch [50.8 millimeter] pipe size, the valve or valves used on
the connection must be of the outside-screw-and-yoke-rising-spindle type so as to indicate
from a distance by the position of its spindle whether it is closed or open, and the wheel may
be carried either on the yoke or attached to the spindle. A plug-cock-type valve may be used
provided the plug is held in place by a guard or a gland, the valve is equipped to indicate from
a distance whether it is closed or open, and the valve is equipped with a slow-opening
mechanism. In the case of a single boiler and prime mover installation, the stop valve required
herein may be omitted provided the prime mover throttle valve is equipped with an indicator to
show whether the valve is open or closed and is designed to withstand the required
hydrostatic pressure test of the boiler.
2.
When the boilers are connected to a common header, the connection from each boiler having
a manhole opening must be fitted with two stop valves having an ample free-blow drain
between them. The discharge of this drain must be visible to the operator while manipulating
the valve. The stop valves must consist preferably of one automatic nonreturn valve (set next
to the boiler) and a second valve of the outside-screw-and-yoke type must be used. Where
intercommunicating systems of different pressures are installed, every boiler on each system
must be equipped with an automatic nonreturn valve set next to the boiler.
3.
When more than one stop valve is required, it must have a pressure rating at least equal to
that required for the expected steam temperature and pressure at the valve, or the pressure
rating at least equal to eighty-five percent of the lowest set pressure of any safety valve on the
boiler drum and for the expected temperature of the steam at the valve, whichever is greater.
4.
All valves and fittings on steam lines must have a pressure rating of at least one hundred
pounds per square inch [689.48 kilopascals] in accordance with the applicable American
National Standards Institute Standard.