NDAC 33.1-14-06-01
Requirements
Cite as N.D. Admin. Code ยง 33.1-14-06-01
1.
All new boilers, except those exempt by law, to be installed in North Dakota must be reported
to the chief boiler inspector by the owner or user and by the installer.
2.
A miniature boiler, except one exempt by law, may not be installed in North Dakota unless it
has been constructed, inspected, and stamped in conformity with section 1 of the American
Society of Mechanical Engineers Code and is approved, registered, and inspected in
accordance with this article.
3.
A miniature boiler having the standard stamping of another state that has adopted a standard
of construction equivalent to the standard of North Dakota may be accepted by the inspector.
However, the person desiring to install the same shall make application for the installation and
shall file with this application the manufacturer's data report covering the construction of the
boiler in question.
4.
All new installation boilers, including reinstalled boilers, must be installed in accordance with
the requirements of the American Society of Mechanical Engineers Code and these
regulations.
5.
The owner or user shall install a carbon monoxide detector or alarm in equipment rooms
where fuel-fired boilers and/or fuel-fired pressure vessels are located in accordance with the
authority having jurisdiction.