NDAC 33.1-14-07-06
Feeding and feedwater piping
Cite as N.D. Admin. Code ยง 33.1-14-07-06
1.
Every miniature boiler must be provided with at least one feed pump or other mechanical
feeding device except if the following conditions exist:
a.
If the boiler is connected to a water main or system having sufficient pressure to feed the
boiler at any time while under pressure.
b.
If the fuel burned is such that all heat input can be discontinued instantaneously by the
operation of a valve, cock, or switch, thereby permitting the boiler pressure to be quickly
lowered to a point where water can be introduced from the connection of the water main.
c.
If the boiler is operated without extraction of steam (closed system) in which case the
boiler is filled, when cold, through the connection or opening provided in accordance with
the following rule.
2.
Each miniature boiler must be fitted with a feedwater connection that may not be less than
one-half inch [12.7 millimeter] iron pipe size. The feed piping must be provided with a check
valve near the boiler and a valve or check between the check valve and the boiler.
3.
Feedwater may be introduced through the blowoff connection if the boiler is operated without
extraction of steam (closed system).
4.
Feedwater may not be introduced through the water column or gauge glass connections while
the boiler is under pressure.