NDAC 33.1-14-09-15
Provisions for thermal expansion in hot water systems
Cite as N.D. Admin. Code ยง 33.1-14-09-15
1.
All hot water heating systems incorporating hot water tanks or fluid relief columns must be so
installed as to prevent freezing under normal operating conditions.
2.
Systems with open expansion tank. If the system is equipped with an open expansion tank, an
indoor overflow from the upper portion of the expansion tank must be provided in addition to
an open vent, the indoor overflow to be carried within the building to a suitable plumbing
fixture or to the basement.
3.
Closed-type systems. If the system is of the closed type, an airtight tank or other suitable air
cushion must be installed that will be consistent with the volume and capacity of the system,
and must be suitably designed for a hydrostatic test pressure of two and one-half times the
allowable working pressure of the system. Expansion tanks for systems designed to operate
above thirty pounds per square inch [206.85 kilopascals] must be constructed in accordance
with the American Society of Mechanical Engineers Code, section VIII, division 1. Except for
prepressurized tanks, provisions must be made for draining the tank without emptying the
system. Provisions must also be made for changing of all tanks without emptying the system.
4.
Expansion tank capacities for gravity hot water systems. Based on two-pipe system with
average operating water temperature one hundred seventy degrees Fahrenheit [76.7 degrees
Celsius], using cast iron column radiation with heat emission rate one hundred fifty British
thermal units per hour per square foot [158.25 x 10 to the 3rd power joules per .0929 square
meter] equivalent direct radiation.
Square Feet of Installed Equivalent Direct Radiation
Tank Capacity, Gallons
Up
to
350
18
Up
to
450
21
Up
to
650
24
Up
to
900
30
Up
to
1,100
35
Up
to
1,400
40
Up
to
1,600
2-30
Up
to
1,800
2-30
Up
to
2,000
2-35
Up
to
2,400
2-40
5.
Expansion tank capacities for forced hot water systems. Based on average operating water
temperature one hundred ninety-five degrees Fahrenheit [90 degrees Celsius], a fill pressure
twelve pounds per square inch gauge [82.74 kilopascals] and a maximum operating pressure
thirty pounds per square inch gauge [206.84 kilopascals].
System Volume, Gallons
Nonpressurized Tank
Capacity Gallons
Prepressurized Tank
Capacity Gallons
100
15
9
200
30
17
300
45
25
400
60
33
500
75
42
1,000
150
83
2,000
300
165
Note: System volume includes volume of water in boiler, radiation, and piping, not including
the expansion tank.
6.
Expansion tanks for hot water supply systems must be constructed in accordance with the
American Society of Mechanical Engineers Code, section VIII, division 1 if over five gallons in
size of water and air.