NDAC 33.1-14-09-21
Emergency shutoff switches
Cite as N.D. Admin. Code ยง 33.1-14-09-21
1.
A manually operated emergency shutoff switch or circuit breaker must be located just outside
the boiler room door and marked for easy identification. Consideration should be given to the
type and location of the switch to safeguard against tampering. If the boiler room door is on
the building exterior, the switch must be located just inside the door. If there is more than one
door to the boiler room, there must be a switch located at each door.
2.
The emergency switch or circuit breaker must disconnect all power to the burner controls.
3.
This requirement is limited to single and modular boilers exceeding four hundred thousand
British thermal units per hour input installed after January 1, 2006.