NDAC 33.1-24-02-61
Assessment of existing tank system's integrity
Cite as N.D. Admin. Code ยง 33.1-24-02-61
1.
Tank systems must meet the secondary containment requirements of section 33.1-24-02-63,
or the remanufacturer or other person that handles the hazardous secondary material must
determine that the tank system is not leaking or is unfit for use. Except as provided in
subsection 3, a written assessment reviewed and certified by a qualified professional engineer
must be kept on file at the remanufacturer's facility or other facility that stores or treats the
hazardous secondary material that attests to the tank system's integrity.
2.
This assessment must determine that the tank system is adequately designed and has
sufficient structural strength and compatibility with the materials to be stored or treated, to
ensure that it will not collapse, rupture, or fail. At a minimum, this assessment must consider
the following:
a.
Design standards, if available, according to which the tank and ancillary equipment were
constructed;
b.
Hazardous characteristics of the materials that have been and will be handled;
c.
Existing corrosion protection measures;
d.
Documented age of the tank system, if available (otherwise, an estimate of the age); and
e.
Results of a leak test, internal inspection, or other tank integrity examination such that:
(1)
For nonenterable underground tanks, the assessment must include a leak test that
is capable of taking into account the effects of temperature variations, tank end
deflection, vapor pockets, and high water table effects; and
(2)
For other than nonenterable underground tanks and for ancillary equipment, this
assessment must include either a leak test, as described above, or other integrity
examination that is certified by a qualified professional engineer that addresses
cracks, leaks, corrosion, and erosion.
Note: The practices described in the American Petroleum Institute (API) Publication,
Guide for Inspection of Refinery Equipment, Chapter XIII, "Atmospheric and
Low-Pressure Storage Tanks," 4th edition, 1981, may be used, where applicable, as
guidelines in conducting other than a leak test.
3.
If, as a result of the assessment conducted in accordance with subsection 1, a tank system is
found to be leaking or unfit for use, the remanufacturer or other person that stores or treats
the hazardous secondary material shall comply with the requirements of section
33.1-24-02-66.