NDAC 33.1-24-05-104
Assessment of existing tank system's integrity
Cite as N.D. Admin. Code ยง 33.1-24-05-104
1.
For each existing tank system that does not have secondary containment meeting the
requirements of section 33.1-24-05-106, the owner or operator shall determine that the tank
system is not leaking or is unfit for use. Except as provided in subsection 3, the owner or
operator shall obtain and keep on file at the facility a written assessment reviewed and
certified by a qualified professional engineer, in accordance with subsection 4 of section
33.1-24-06-03, that attests to the tank system's integrity by January 12, 1988.
2.
This assessment must determine that the tank system is adequately designed and has
sufficient structural strength and compatibility with the wastes to be stored or treated, to
ensure that it will not collapse, rupture, or fail. At a minimum, the assessment must consider of
the following:
a.
Design standards, if available, according to which the tank and ancillary equipment were
constructed;
b.
Hazardous characteristics of the wastes that have been and will be handled;
c.
Existing corrosion protection measures;
d.
Documented age of the tank system if available (otherwise, an estimate of the age); and
e.
Results of a leak test, internal inspection, or other tank integrity examination such that:
(1)
For nonenterable underground tanks, the assessment must include a leak test that
is capable of taking into account the effects of temperature variations, tank end
deflection, vapor pockets, and high-water table effects; and
(2)
For other than nonenterable underground tanks and for ancillary equipment, this
assessment must include either a leak test, as described above, or other integrity
examination that is certified by a qualified professional engineer in accordance with
subsection 4 of section 33.1-24-06-03, that addresses cracks, leaks, corrosion, and
erosion.
Note: The practices described in the American petroleum institute publication, guide
for inspection of refinery equipment, chapter XIII, "Atmospheric and Low-Pressure
Storage Tanks", fourth edition, 1981, may be used, where applicable, as guidelines
in conducting other than a leak test.
3.
Tank systems that store or treat materials that become hazardous waste subsequent to
July 14, 1986, must conduct this assessment within twelve months after the date that the
waste becomes a hazardous waste.
4.
If, as a result of the assessment conducted in accordance with subsection 1, a tank system is
found to be leaking or unfit for use, the owner or operator shall comply with the requirements
of section 33.1-24-05-109.