NDAC 33.1-24-05-150
Monitoring and inspections
Cite as N.D. Admin. Code § 33.1-24-05-150
1.
The owner or operator shall conduct, at a minimum, the following monitoring while incinerating
hazardous waste:
a.
Combustion temperature, waste feed rate, and the indicator of combustion gas velocity
specified in the permit must be monitored on a continuous basis;
b.
Carbon monoxide must be monitored on a continuous basis at a point in the incinerator
downstream of the combustion zone and prior to release to the atmosphere; and
c.
Upon request by the department, sampling and analysis of the waste and exhaust
emissions must be conducted to verify that the operating requirements established in the
permit achieve the performance standards of section 33.1-24-05-147.
2.
The incinerator and associated equipment (pumps, valves, conveyors, pipes, etc.) must be
completely inspected at least daily for leaks, spills, fugitive emissions, and signs of tampering.
3.
The emergency waste feed cutoff system and associated alarms must be tested at least
weekly to verify operability, unless the applicant demonstrates to the department that weekly
inspections will unduly restrict or upset operations and that less frequent inspection will be
adequate. At a minimum, operational testing must be conducted monthly.
4.
This monitoring and inspection data must be recorded and the records must be placed in the
operating record required by section 33.1-24-05-40 and maintained in the operating record for
five years.