NDAC 33.1-24-08-10
Performance standards for new underground storage tank systems
Cite as N.D. Admin. Code § 33.1-24-08-10
In order to prevent releases due to structural failure, corrosion, or spills and overfills for as long as
the underground storage tank system is used to store regulated substances, all owners and operators
of new underground storage tank systems must meet the following requirements. In addition, except for
suction piping that meets the requirements of subparagraphs a through e of paragraph 2 of
subdivision a of subsection 2 of section 33.1-24-08-31, tanks and piping installed or replaced after
January 1, 2009, must be secondarily contained and use interstitial monitoring in accordance with
subsection 7 of section 33.1-24-08-33. Secondary containment must be able to contain regulated
substances leaked from the primary containment until they are detected and removed and prevent the
release of regulated substances to the environment at any time during the operational life of the
underground storage tank system. For cases where the piping is considered to be replaced, the entire
piping run must be secondarily contained.
1.
Tanks. Each tank must be properly designed and constructed, and any portion underground
that routinely contains product must be protected from corrosion in accordance with a code of
practice developed by a nationally recognized association or independent testing laboratory
as specified below:
a.
The tank is constructed of fiberglass-reinforced plastic.
NOTE: The following codes of practice may be used to comply with this subdivision:
Underwriters Laboratory Standard 1316, "Glass-Fiber-Reinforced Plastic Underground
Storage Tanks for Petroleum Products Alcohols, and Alcohol-Gasoline Mixtures"; or
Underwriters Laboratories of Canada S615, "Standard for Reinforced Plastic
Underground Tanks for Flammable and Combustible Liquids".
b.
The tank is constructed of steel and cathodically protected in the following manner:
(1)
The tank is coated with a suitable dielectric material;
(2)
Field-installed cathodic protection systems are designed by a corrosion expert;
(3)
Impressed current systems are designed to allow determination of current operating
status as required in subsection 3 of section 33.1-24-08-21; and
(4)
Cathodic protection systems are operated and maintained in accordance with
section 33.1-24-08-21 or according to guidelines established by the department.
NOTE: The following codes of practice may be used to comply with this subdivision:
Steel Tank Institute "Specification STI-P3® Specification and Manual for External
Corrosion Protection of Underground Steel Storage Tanks"; Underwriters Laboratories
Standard 1746, "External Corrosion Protection Systems for Steel Underground Storage
Tanks"; Underwriters Laboratories of Canada S603, "Standard for Steel Underground
Tanks for Flammable and Combustible Liquids", and S603.1, "Standard for External
Corrosion Protection Systems for Steel Underground Tanks for Flammable and
Combustible Liquids", and S631, "Standard for Isolating Bushings for Steel Underground
Tanks Protected with External Corrosion Protection Systems"; Steel Tank Institute
Standard F841, "Standard for Dual Wall Underground Steel Storage Tanks"; or NACE
International Standard Practice SP 0285, "External Corrosion Control of Underground
Storage Tank Systems by Cathodic Protection"; and Underwriters Laboratories Standard
58, "Standard for Steel Underground Tanks for Flammable and Combustible Liquids".
c.
The tank is constructed of steel and clad or jacketed with a noncorridble material.
NOTE: The following codes of practice may be used to comply with this subdivision:
Underwriters Laboratories Standard 1746, "External Corrosion Protection Systems for
Steel Underground Storage Tanks"; Steel Tank Institute ACT-100® Specification F894,
"Specification for External Corrosion Protection of FRP Composite Steel Underground
Storage Tanks"; Steel Tank Institute ACT-100-U® Specification F961, "Specification for
External Corrosion Protection of Composite Steel Underground Storage Tanks"; or Steel
Tank Institute Specification F922, "Steel Tank Institute Specification for Permatank®".
d.
The tank is constructed of metal without additional corrosion protection measures
provided that:
(1)
The tank is installed at a site that is determined by a corrosion expert not be
corrosive enough to cause it to have a release due to corrosion during its operating
life; and
(2)
Owners and operators maintain records that demonstrate compliance with the
requirements of paragraph 1 of this subdivision for the remaining life of the tank.
e.
The tank construction and corrosion protection are determined by the department to be
designed to prevent the release or threatened release of any stored regulated substance
in a manner that is no less protective of human health and the environment than
subdivisions a through d.
2.
Piping. The piping that routinely contains regulated substances and is in contact with the
ground must be properly designed, constructed, and protected from corrosion in accordance
with a code of practice developed by a nationally recognized association or independent
testing laboratory as specified below:
a.
The piping is constructed of a noncorrodible material.
NOTE: The following codes of practice may be used to comply with this subdivision:
Underwriters Laboratories Standard 971, "Nonmetallic Underground Piping for
Flammable Liquids"; Underwriters Laboratories of Canada Standard S660, "Standard for
Nonmetallic Underground Piping for Flammable and Combustible Liquids".
b.
The piping is constructed of steel and cathodically protected in the following manner:
(1)
The piping is coated with a suitable dielectric material;
(2)
Field-installed cathodic protection systems are designed by a corrosion expert;
(3)
Impressed current systems are designed to allow determination of current operating
status as required in subsection 3 of section 33.1-24-08-21; and
(4)
Cathodic protection systems are operated and maintained in accordance with
section 33.1-24-08-21 or guidelines established by the department.
NOTE: The following codes of practice may be used to comply with this subdivision:
American Petroleum Institute Recommended Practice 1632, "Cathodic Protection of
Underground Petroleum Storage Tanks and Piping Systems"; Underwriters Laboratories
Subject 971A, "Outline of Investigation for Metallic Underground Fuel Pipe"; Steel Tank
Institute Recommended Practice R892, "Recommended Practice for Corrosion
Protection of Underground Piping Networks Associated with Liquid Storage and
Dispensing Systems"; NACE International Standard Practice SP 0169 "Control of
External Corrosion on Underground Submerged Metallic Piping Systems", NACE
International Standard Practice SP 0285, "External Corrosion Control of Underground
Storage Tank Systems by Cathodic Protection".
c.
The piping is constructed of metal without additional corrosion protection measures
provided that:
(1)
The piping is installed at a site that is determined by a corrosion expert to not be
corrosive enough to cause it to have a release due to corrosion during its operating
life; and
(2)
Owners and operators maintain records that demonstrate compliance with the
requirements of paragraph 1 for the remaining life of the piping.
d.
The piping construction and corrosion protection are determined by the department to be
designed to prevent the release or threatened release of any stored regulated substance
in a manner that is no less protective of human health and the environment than the
requirements in subdivisions a through c.
3.
Spill and overfill prevention equipment.
a.
Except as provided in subdivisions b and c, to prevent spilling and overfilling associated
with product transfer to the underground storage tank system, owners and operators
must use the following spill and overfill prevention equipment:
(1)
Spill prevention equipment that will prevent release of product to the environment
when the transfer hose is detached from the fill pipe (for example, a spill catchment
basin); and
(2)
Overfill prevention equipment that will:
(a)
Automatically shut off flow into the tank when the tank is no more than
ninety-five percent full;
(b)
Alert the transfer operator when the tank is no more than ninety percent full by
restricting the flow into the tank or triggering a high-level alarm; or
(c)
Restrict flow thirty minutes prior to overfilling, alert the transfer operator with a
high-level alarm one minute before overfilling, or automatically shut off flow into
the tank so that none of the fittings located on top of the tank are exposed to
product due to overfilling.
b.
Owners and operators are not required to use the spill and overfill prevention equipment
specified in subdivision a if:
(1)
Alternative equipment is used that is determined by the department to be no less
protective of human health and the environment than the equipment specified in
paragraphs 1 and 2 of subdivision a; or
(2)
The underground storage tank system is filled by transfers of no more than
twenty-five gallons [94.63 liters] at one time.
c.
Flow restrictors used in vent lines may not be used to comply with paragraph 2 of
subdivision a of subsection 3 when overfill prevention is installed or replaced after April 1,
2018.
d.
Spill and overfill prevention equipment must be periodically tested or inspected in
accordance with section 33.1-24-08-25.
4.
Dispenser systems. Each underground storage tank system must be equipped with under-
dispenser containment for any new dispenser system installed after September 28, 2018:
a.
A dispenser system is considered new when both the dispenser and the equipment
needed to connect the dispenser to the underground storage tank system are installed at
an underground storage tank facility. The equipment necessary to connect the dispenser
to the underground storage tank system includes check valves, shear valves, unburied
risers or flexible connectors, or other transitional components that are underneath the
dispenser and connect the dispenser to the underground piping.
b.
Under-dispenser containment must be liquid-tight on its sides, bottom, and at any
penetrations. Under-dispenser containment must allow for visual inspection and access
to the components in the containment system or be periodically monitored for leaks from
the dispenser system.
5.
Installation. The underground storage tank system must be properly installed in accordance
with a code of practice developed by a nationally recognized association or independent
testing laboratory and in accordance with the manufacturer's instructions.
NOTE: Tank and piping system installation practices and procedures described in the
following codes of practice may be used to comply with the requirements of this subsection:
American Petroleum Institute Publication 1615, "Installation of Underground Petroleum
Storage System"; Petroleum Equipment Institute Publication RP100, "Recommended
Practices for Installation of Underground Liquid Storage Systems"; or National Fire Protection
Association Standard 30, "Flammable and Combustible Liquids Code" and Standard 30A,
"Code for Motor Fuel Dispensing Facilities and Repair Garages".
6.
Certification of installation. All owners and operators must ensure that one or more of the
following methods of certification, testing, or inspection is used to demonstrate compliance
with subsection 5 by providing a certification of compliance on the underground storage tank
notification form in accordance with section 33.1-24-08-12:
a.
The installer has been certified by the tank and piping manufacturers;
b.
The installer has been certified or licensed by the department;
c.
The installation has been inspected and certified by a registered professional engineer
with education and experience in underground storage tank system installation;
d.
The installation has been inspected and approved by the department;
e.
All work listed in the manufacturer's installation checklists has been completed; or
f.
The owner and operator have complied with another method for ensuring compliance
with subsection 5 that is determined by the department to be no less protective of human
health and the environment.