NDAC 33.1-24-08-23
Repairs allowed
Cite as N.D. Admin. Code ยง 33.1-24-08-23
Owners and operators of underground storage tank systems must ensure that repairs will prevent
releases due to structural failure or corrosion as long as the underground storage tank system is used
to store regulated substances. The repairs must meet the following requirements:
1.
Repairs to underground storage tank systems must be properly conducted in accordance with
a code of practice developed by a nationally recognized association or an independent testing
laboratory;
NOTE: The following codes of practice may be used to comply with this subsection: National
Fire Protection Association Standard 30, "Flammable and Combustible Liquids Code";
American Petroleum Institute Recommended Practice RP 2200, "Repairing Crude Oil,
Liquefied Petroleum Gas, and Product Pipelines"; American Petroleum Institute
Recommended Practice RP 1631, "Recommended Practice for the Interior Lining and Periodic
Inspection Underground Storage Tanks"; National Fire Protection Association Standard 326,
"Standard for the Safeguarding of Tanks and Containers for Entry, Cleaning, or Repair";
National Leak Prevention Association Standard 631, Chapter A, "Entry, Cleaning, Interior
Inspection, Repair, and Lining of Underground Storage Tanks"; Steel Tank Institute
Recommended Practice R972, "Recommended Practice for the Addition of Supplemental
Anodes to STI-P3ยฎ Tanks"; NACE International Standard Practice SP 0285, "External Control
of Underground Storage Tank Systems by Cathodic Protection"; or Fiberglass Tank and Pipe
Institute Recommended Practice T-95-02, "Remanufacturing of Fiberglass Reinforced Plastic
(FRP) Underground Storage Tanks".
2.
Repairs to fiberglass-reinforced plastic tanks may be made by the manufacturer's authorized
representatives or in accordance with a code of practice developed by a nationally recognized
association or an independent testing laboratory;
3.
Metal pipe sections and fittings that have released product as a result of corrosion or other
damage must be replaced. Noncorrodible pipes and fittings may be repaired in accordance
with the manufacturer's specifications;
4.
Repairs to secondary containment areas of tanks and piping used for interstitial monitoring
and to containment sumps used for interstitial monitoring of piping must have the secondary
containment tested for tightness according to the manufacturer's instructions, a code of
practice developed by a nationally recognized association or independent testing laboratory,
or according to requirements established by the department within thirty days following the
date of completion of the repair. All other repairs to tanks and piping must be tightness tested
in accordance with subsection 3 of section 33.1-24-08-33 and subsection 2 of section
33.1-24-08-34 within thirty days following the date of the completion of the repair except as
provided in subdivisions a through c:
a.
The repaired tank is internally inspected in accordance with a code of practice developed
by a nationally recognized association or an independent testing laboratory;
b.
The repaired portion of the underground storage tank system is monitored monthly for
releases in accordance with a method specified in subsections 4 through 9 of section
33.1-24-08-33; or
c.
Another test method is used that is determined by the department to be no less
protective of human health and the environment than those listed above;
NOTE: The following codes of practice may be used to comply with subsection 4 of this
subsection: Steel Tank Institute Recommended Practice R012, "Recommended Practice
for Interstitial Tightness Testing of Existing Underground Double Wall Steel Tanks"; or
Fiberglass Tank and Pipe Institute Protocol, "Field Test Protocol for Testing the Annular
Space of Installed Underground Fiberglass Double and Triple-Wall Tanks with Dry
Annular Space"; Petroleum Equipment Institute Recommended Practice RP1200,
"Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection
and Secondary Containment Equipment at UST Facilities".
5.
Within six months following the repair of any cathodically protected underground storage tank
system, the cathodic protection system must be tested in accordance with subsections 2
and 3 of section 33.1-24-08-21 to ensure that it is operating properly; and
6.
Within thirty days following any repair to spill or overfill prevention equipment, the repaired spill
or overfill prevention equipment must be tested or inspected, as appropriate, in accordance
with section 33.1-24-08-25 to ensure it is operating properly.
7.
Underground storage tank system owners and operators must maintain records, in
accordance with section 33.1-24-08-24, of each repair until the underground storage tank
system is permanently closed or undergoes a change-in-service pursuant to section
33.1-24-08-61.