NDAC 33.1-24-08-25
Periodic testing of spill prevention equipment and containment sumps used for interstitial monitoring of piping and periodic inspection of overfill prevention equipment
Cite as N.D. Admin. Code ยง 33.1-24-08-25
1.
Owners and operators of underground storage tank systems with spill and overfill prevention
equipment and containment sumps used for interstitial monitoring of piping must meet these
requirements to ensure the equipment is operating properly and will prevent releases to the
environment:
a.
Spill prevention equipment, such as a catchment basin, spill bucket, or other spill
containment device, and containment sumps used for interstitial monitoring of piping
must prevent releases to the environment by meeting one of the following:
(1)
The equipment is double walled and the integrity of both walls is periodically
monitored at a frequency not less than the frequency of the walkthrough inspections
described in section 33.1-24-08-26. Owners and operators shall begin fulfilling
paragraph 2 of subdivision a of subsection 1 and conduct a test within thirty days of
discontinuing periodic monitoring of this equipment; or
(2)
The spill prevention equipment and containment sumps used for interstitial
monitoring of piping are tested at least once every three years to ensure the
equipment is liquid tight by using vacuum, pressure, or liquid testing in accordance
with one of the following criteria:
(a)
Requirements developed by the manufacturer;
NOTE: Owners and operators may use this option only if the manufacturer has
developed requirements.
(b)
Code of practice developed by a nationally recognized association or
independent testing laboratory; or
(c)
Requirements determined by the department to be no less protective of human
health and the environment than the requirements listed in subparagraphs a
and b of paragraph 2 of subdivision a of subsection 1.
b.
Overfill prevention equipment must be inspected at least once every three years. At a
minimum, the inspection must ensure that overfill prevention equipment is set to activate
at the correct level specified in subsection 3 of section 33.1-24-08-10 and will activate
when a regulated substance reaches that level. Inspections must be conducted in
accordance with one of the criteria in subparagraphs a through c of paragraph 2 of
subdivision a of subsection 1.
2.
Owners and operators must begin meeting these requirements as follows:
a.
For underground storage tank systems in use on or before April 1, 2018, the initial spill
prevention equipment test, containment sump test, and overfill prevention equipment
inspection must be conducted not later than April 1, 2021.
b.
For underground storage tank systems brought into use after April 1, 2018, these
requirements apply at installation.
3.
Owners and operators must maintain records as follows, in accordance with section
33.1-24-08-24, for spill prevention equipment, containment sumps used for interstitial
monitoring of piping, and overfill prevention equipment:
a.
All records of testing or inspection must be maintained for three years; and
b.
For spill prevention equipment and containment sumps used for interstitial monitoring of
piping not tested every three years, documentation showing that the prevention
equipment is double walled and the integrity of both walls is periodically monitored must
be maintained for as long as the equipment is periodically monitored.
NOTE: To paragraph 2 of subdivision a of subsection 1 and subdivision b of subsection 1 the
following code of practice may be used to comply with paragraph 2 of subdivision a of
subsection 1 and subdivision b of subsection 1: Petroleum Equipment Institute Publication
RP1200, "Recommended Practices for the Testing and Verification of Spill, Overfill, Leak
Detection and Secondary Containment Equipment at UST Facilities".